Each of the 11 residential towers will need to comply with the code for the building project to be compliant. Though the towers are identical, their orientations differ.
The longer walls of Towers A-E face north-south, i.e., 0° and 180°. Towers F-I face 345° and 165°. Towers J and K face east-west, i.e., 90° and 270°. As per Table 8 in Annexure 6, Towers A-E and F-I can be considered having the same orientation. Thus, for this project, compliance may be shown for one of Towers A-I and one of Towers J and K.
In this example, compliance of Tower C, as marked in Figure 9, is being shown.
Figure 9 Building for compliance check on the layout of project (Example 1)
Bureau of Energy Efficiency (BEE)
| 39 |
ANNEXURE 8
ANNEXURES
The longer sides of this tower face north-south. It has 112 dwelling units (DUs), 16 DUs on each floor. Half of the DUs face north and the rest face south.
Table 18Envelope areas of the building (Example 1)
Orientation
Total wall length (m), exposed to ambient
Total wall height (m), exposed to ambient
Envelope area (m2)
North
51.58
21.06
1086.27
South
51.58
21.06
1086.27
East
31.00
21.06
652.86
West
31.00
21.06
652.86
Envelope area (m2), excluding roof
3478.26
Step 1: Openable window-to-floor area ratio $( mathsf { W F R } { { 0 , mathsf { p } } } )$
1.1: Calculation of total openable area ( A o p e n a b l e )
Each flat consists of three windows, one door opening to the balcony, and two ventilators. As all of them are casement openings, 90% of the opening area is considered openable.
Table 19Openable area calculation (Example 1)
Opening name
Opening area (m2)
Openable area (m2)
Remarks
W1
1.92
1.73
W2
1.04
0.94
90% openable(Table 5)
W3
1.28
1.15
D (opening into balcony)
1.87
1.69
V (2 nos)
0.52
0.47
Openable area for each flat
5.97
Openable area for 112 flats ( Aopenable )
668.81
1.2: Calculation of total carpet area A c a r p e t
A c a r p e t = n o . of DUs x carpet area of 1 DU = II2 × 26.6 = 2979.20 m²
1.3: Calculate the openable window-to-floor area ratio (WFR )
WFRop=AcarpetAopenab
Rajkot is in the composite climate. As per Table 1, the minimum WFRop for this climate is 12.5%. Thus, this project complies with this requirement.
ANNEXURE 8
Step 2: Visible Light Transmittance (VLT)
Annexure 8Examples of Code Compliance
Example 1: A 7-storey housing project in Rajkot is trying to comply with the residential code. There are 11 identical residential towers in this project. The carpet area of each dwelling unit (DU) is 26.6 m2.
There are three windows (W1, W2, W3) and one door (D) in each DU exposed to ambient. The windows are either fully glazed or partially glazed (glass and PVC panels) and are casement windows. The door is opaque with PVC panel. Each DU has two ventilators (V) in the bath and toilet, which face a ventilation shaft. The details of the exposed door, windows, and ventilators are given below.
Figure 7 Layout plan of the project (Example 1)
Bureau of Energy Efficiency (BEE)
| 37 |
ANNEXURE 8
Figure 8 Plan of a typical DU (Example 1)
Table 16Details of exposed doors, windows, and ventilators (Example 1)
Opening window/door/ ventilator
Opening width (m)
Opening height (m)
Opening area (m2)
Width of glass in Opening (m)
Height of glass in Opening (m)
Glass area in opening (m2)
Opaque area (m2)
W1
1.20
1.60
1.92
1.20
0.53
0.64
1.28
W2
0.80
1.30
1.04
0.80
0.43
0.35
0.69
W3
0.80
1.60
1.28
0.80
1.60
1.28
0.00
D
0.75
2.50
1.87
0.00
0.00
0.00
1.87
V (2 nos)
0.65
0.40
0.26
0.65
0.40
0.26
0.00
38
ANNEXURE 8
Material details are as follows:
Table 17Details of construction material (Example 1)
Wall
200 mm AAC blocks with plaster on both sides. U-value 0.78 W/m2.K
Roof
150 mm RCC with 40 mm polyurethane foam (PUF) insulation
Glass in windows
Single clear glass with SHGC 0.80, VLT 85%, and U-value 5.80 W/m2.K
PVC panel
4 mm thick PVC panel used in doors and windows. U-value 5.23 W/m2.K
Does this project comply with the code?
2.1: Calculation of window-to-wall ratio (WWR)
There are three windows and one door in each DU exposed to ambient. The windows are either fully glazed or partially glazed (glass and PVC panels). The door is opaque with PVC panel.
Table 20Calculation of window-to-wall ratio (Example 1)
Orientation
Opening name
Opening area (m2)
Non-opaque (glass) area in opening (m2)
No. of openings
Total opening area (m2)
Total non-opaque (glass) area (m2)
North
W1
1.92
0.64
56
107.52
35.62
North
W2
1.04
0.35
56
58.24
19.26
North
W3
1.28
1.28
56
71.68
71.68
North
D
1.88
0.00
56
105.00
0.00
South
W1
1.92
0.64
56
107.52
35.62
South
W2
1.04
0.35
56
58.24
19.26
South
W3
1.28
1.28
56
71.68
71.68
South
D
1.88
0.00
56
105.00
0.00
Total
684.88
253.16
Step 4: RETV of the building envelope (except roof)
4.1: Calculation of envelope area, in every orientation
Table 22Calculation of envelope area for each orientation (Example 1)
Orientation
Area (m2)
U value (W/m2.K)
North
Non-opaque (glass) area
126.56
5.80
Opaque area 1 (AAC wall)
743.83
0.78
Opaque area 2 (PVC panel in doors and windows)
215.88
5.23
South
Non-opaque (glass) area
126.56
5.80
Opaque area 1 (AAC wall)
743.83
0.78
Opaque area 2 (PVC panel in doors and windows)
215.88
5.23
East
Non-opaque (glass) area
0.00
Opaque area 1 (AAC wall)
652.86
0.78
Opaque area 2 (PVC panel in doors and windows)
0.00
West
Non-opaque (glass) area
0.00
Opaque area 1 (AAC wall)
652.86
0.78
Opaque area 2 (PVC panel in doors and windows)
0.00
Total Envelope Area, Aenvelope
3478.26
(The U values of AAC block and PVC sheet are calculated the same way as that shown for the roof. The thermal conductivity of AAC block is 0.184 W/m.K and that of PVC is 0.19 W/m.K.)
Bureau of Energy Efficiency (BEE)
| 43 |
ANNEXURE 8
Table 23Calculationof equivalent SHGC of non-opaque openings for each orientation (Example 1) 4.2: Calculation of equivalent SHGC of non-opaque openings, for each orientation
3.1: Calculation of thermal transmittance of roof $left( mathcal { V } { r o o ^ { prime } } right)$
The roof of this building comprises the following material layers.
ANNEXURE 8
Table 21Roof construction details (Example 1)
Material layer
Thickness, t (m)
Thermal conductivity, k (W/m.K)
Thermal resistance of material, R= t/k (m2.K/W)
China mosaic tile
0.007
1.500
0.005
Concrete (laid to slope)
0.050
1.740
0.029
Polyurethane foam (PUF)
0.040
0.023
1.739
Cement screed
0.020
0.720
0.028
RCC slab
0.150
1.580
0.095
Internal plaster
0.015
0.720
0.021
Sum of all material thermal resistance
1.917
Total thermal resistance,
Bureau of Energy Efficiency (BEE)
4.3: Calculation of RETV
Rajkot is in the composite climate zone. Thus, the RETV equation, with applicable coefficients, is:
As per Table 2, for WWR of 0.073 (range 0–0.30), the minimum required VLT is 27%. The glass used in this project has a VLT of 85% (as per certified specification for the product). Thus, this project complies with this requirement. Also, it complies with the recommended value.
Step 3: Thermal transmittance of roof langle U roof rangle
This is less than the maximum RETV of 15 W/m2. Hence it complies with this requirement.
The building complies with all four requirements and hence complies with the code.
Example 2: The same project given in Example 1 is built in Shimla. All specifications of the project remain the same except that all windows (W1, W2, W3) are fully glazed and sliding. The details of the exposed door, windows, and ventilators for this project are given below.
Table 25Details of exposed door, windows, and ventilators (Example 2)
Opening window/door/ventilator
Opening width (m)
Opening height (m)
Opening area (m2)
Width of glass in opening (m)
Height of glass in opening (m)
Glass area in opening (m2)
Opaque area (m2)
W1
1.20
1.60
1.92
1.20
1.60
1.92
0.00
W2
0.80
1.30
1.04
0.80
1.30
1.04
0.00
W3
0.80
1.60
1.28
0.80
1.60
1.28
0.00
D
0.75
2.50
1.87
0.00
0.00
0.00
1.87
V (2 nos)
0.65
0.40
0.26
0.65
0.40
0.26
0.00
46
| 47 |
ANNEXURE 8
Material details are as follows:
Table 26Details of construction material (Example 2)
Wall
200 mm AAC blocks with plaster on both sides. U-value 0.78 W/m2.K
Roof
150 mm RCC with 40 mm polyurethane foam (PUF) insulation. U-value 0.47 W/m2.K
Glass in windows
Single clear glass with SHGC 0.80, VLT 85%, and U-value 5.80 W/m2.K
PVC panel
4 mm thick PVC panel used in doors. U-value 5.23 W/m2.K
Does this project comply with the code?
Compliance check:
Each of the 11 residential towers will need to comply with the code for the building project to be compliant. The compliance of one of the towers is being shown.
The longer sides of this tower face north-south. It has 112 dwelling units (DUs), 16 DUs on each floor. Half of the DUs face north and the rest face south.
Table 27Envelope areas of the building (Example 2)
Orientation
Total wall length (m), exposed to ambient
Total wall height (m), exposed to ambient
Gross wall area (m2)
North
51.58
21.06
1086.27
South
51.58
21.06
1086.27
East
31.00
21.06
652.86
West
31.00
21.06
652.86
Envelope area (m2), excluding roof
3478.26
Step 1: Openable window-to-floor area ratio ( | | / F bar R o p rangle
1.1: Calculation of total openable area (Aopenable)
Each flat consists of three windows, one door opening to the balcony, and two ventilators. As all the windows are sliding windows, 50% of the window opening area is considered openable. The door and ventilators are 90% openable.
ANNEXURE 8
Table 28Calculation of openable areas (Example 2)
Opening name
Opening area (m2)
Openable area (m2)
Remarks
W1
1.92
0.96
50% openable (Table 5)
W2
1.04
0.52
W3
1.28
0.64
D
1.87
1.69
90% openable (Table 5)
V (2 nos)
0.52
0.47
Openable area for each flat
4.28
Openable area for 112 flats (A_openable)
478.86
Bureau of Energy Efficiency (BEE)
1.2: Calculation of total carpet area A c a r p e t
A c a r p e t = n o . of DUs x built-up area of 1 DU = II2 × 26.6 = 2979.20 m²
1.3: Calculate the openable window to floor area ratio (WFR )
2.1: Calculation of window-to-wall ratio (WWR)
There are three windows and one door in each DU exposed to ambient. The windows are fully glazed. The door is opaque with PVC panel.
ANNEXURE 8
Table 29Calculation of window-to-wall ratio (Example 2)
Orientation
Opening name
Opening area (m2)
Non-opaque area in opening (m2)
No. of openings
Total opening area (m2)
Total non-opaque area (m2)
North
W1
1.92
1.92
56
107.52
107.52
North
W2
1.04
1.04
56
58.24
58.24
North
W3
1.28
1.28
56
71.68
71.68
North
D
1.88
0.00
56
105.00
0.00
South
W1
1.92
1.92
56
107.52
107.52
South
W2
1.04
1.04
56
58.24
58.24
South
W3
1.28
1.28
56
71.68
71.68
South
D
1.88
0.00
56
105.00
0.00
Total
684.88
474.88
WWR
3.1: Calculation of thermal transmittance of roof (Uroof)
The roof of this building is the same as that of Example 1, i.e., U r o o f is 0.47 W/m2.K. This is less than the maximum U r o o f value of 1.2 W/m ². K Hence it complies with this requirement.
Step 4: Thermal transmittance of building envelope (except roof) for cold climatic zone (Uenvelope,cold)
Shimla is in the cold climate zone. Hence, the thermal transmittance of the building envelope (except roof) will be calculated.
4.1: Calculation of thermal transmittance of building envelope (Uenvelope,cold)
In this case, the U values of the wall (i.e., AAC block with 15 mm plaster on both sides), the opaque door component (i.e., PVC sheet), and the non-opaque components (glass used in windows) need to be combined as per the relative areas of each.
U envelope,cold
49
Note:
l Net AAC block area = Envelope area – Total opening area
l Opaque door area= Total opening area – Total non-opaque area
U values of the AAC block and the PVC sheet are calculated the same way as that shown for the roof. The thermal conductivity of AAC block is 0.184 W/m.K and that of PVC is 0.19 W/m.K
l U value of the glass used is given as 5.80 W/m2.K (as per certified specification for the product)
This is less than the maximum U e n v e l o p e , c o l d value of 1.8 W/m2.K. Hence it complies with this requirement.
The building complies with all four requirements and hence complies with the code.
ANNEXURE 8
opaque
i
×
ωi
)
}
non - opaquei
×
ωi
)
}
eqi
×
ωi
)
}
WFRop=AcarpetAopenable=2979.20478.86=16.1%
Shimla is in the cold climate zone. As per Table 1, the minimum W F R o p for this climate is 8.33%. Thus, this project complies with this requirement.
Step 2: Visible Light Transmittance (VLT)
=
AenvelopeAnon - opaque=
3478.26474.88=
0.136
As per Table 2 , for WWR of 0.136 (range 0–0.30), the minimum required VLT is 27%. The glass used in this project has a VLT of 85% (as per certified specification for the product). Thus, this project complies with this requirement. Also, it complies with the recommended value.
Step 3: Thermal transmittance of roof langle U roof rangle
=AACblock wall area+Opaque door area+Non - opaque area(AACblock wall area×Uvalue ofAAC)+(Opaque door area×Uvalue ofPVC)+(Non - opaque area×Uvalue of glass)=2793.38+210.00+474.88(2793.38×0.78)+(210.00×5.23)+(474.88×5.80)=1.73W/m2.K