For determining the exits required, the number of
persons within any floor area or the occupant load shall be based on the actual number of occupants declared, but in no case less than that specified in Table 3. The occupant load of a mezzanine floor discharging to a floor below shall be added to that floor occupancy and the capacity of the exits shall be designed for the total occupancy load thus established.
The occupant load of each story considered individually
Table 3 Occupant Load
(Clauses 4.3 and 4.4.2.1)
| Sl No. | Group of Occupancy | Occupant Load Factor (m2/person) |
| (see Note 1) | ||
| (1) | (2) | (3) |
| i) | Group A: Residential | 12.50 |
| ii) | Group B: Educational | 4.00 |
| iii) | Group C: Institutional (see Note 2): | |
| a) Indoor patients area | 15.00 | |
| b) Outdoor patients area | 10.0 | |
| iv) | Group D: Assembly: | |
| a) Concentrated use without fixed seating | 0.65 | |
| b) Less concentrated use without fixed seating (see Note 3) | 1.40 | |
| c) Fixed seating | see Note 4 | |
| d) Dining areas and restaurants with seating and table | 1.80 | |
| v) | Group F: Mercantile: | |
| a) Street floor and sales basement | 3.00 | |
| b) Upper sales floor | 6.00 | |
| c) Storage/warehouse, receiving and the like | 20.00 | |
| vi) | Group E: Business | 10.00 |
| vii) | Group G: Industrial | 10.00 |
| viii) | Group H: Storage (see Note 5) | 30.00 |
| ix) | Group J: Hazardous | 10.00 |
Notes
1 Gross area shall be the floor area as defined in 2.35. All factors expressed are in gross area unless marked net.
2 Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums, ete, where sleeping accommodation is provided, shall be calculated at not less than 7.5 m² gross floor area/person.
3 These shall include gymnasium, table tennis room, billiard room and other gaming rooms, library, swimming pool and like.
4 In case of assembly occupancy having fixed seats, the occupant load shall be determined by multiplying the number of seats by 1.2. 5 Car parking areas under occupancy other than storage shall also be 30 m² per person.
shall be required to be used in computing the number of means of egress at each story, provided that the required number of means of egress is not decreased in the direction of egress travel.
The assembly occupancies and call centres shall be required to display, limiting occupant load details positioned in a conspicuous place near the entrance of each of such respective occupancy to avoid possible overcrowding and overloading. The display shall preferably be engraved on a metal plate of not less than 300 mm × 200 mm, with letters of height and width not less than 50 mm, with detail of occupancy, area and occupancy load (see figure below).
The capacity of any open mezzanine/balcony shall be added to the capacity of the floor below for the purpose of determining exit capacity.
Maximum Occupancy
Persons Permitted Within This Space/room