Chapter 9Provision for High Rise and Tall Buildings
9.1 High Rise Building :
Buildings higher than 15m of height without stilts and above 17.5 m of height with stilts shall be considered as high-rise buildings.
Note:—These provisions shall be in addition to the Chapter 2 for plan sanction procedure, Chapter 4 for procedure during construction, Chapter 5 for Zoning regulations and Chapter 6 for Space requirement for different parts of Building.
9.1.1 Plot Area :
Plots to be used for high rise development should be located in an approved Layout plan, Comprehensive plans or subdivision plans as prepared and approved by competent authorities as per policy of the Government of India/State Governments.
9.1.2 Means of access :
The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for movement of fire service vehicles. If archway is provided over the main entrance the height. of the archway shall not be at a height less than 5m.
9.2Building components :
9.2.1 Doorways :
(a) Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
(b) No exit doorway shall be less than 1m in width. Doorways shall be not less than 2 m in height. Doorways for bathrooms, water closet, stores etc. shall be not less than 0.75 m wide.
(c) Exit doorways shall open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 0.9 m, overhead or sliding doors shall not be installed.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 147
(d) Exit door shall not open immediately upon a flight of stairs, a landing equal to at least the width of the door shall be provided in the stairway at each doorway, level of landing shall be the same as that of the floor which it serves.
(e) Exit doorways shall be openable from the side which they serve without the use of a key.
(f) Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
9.2.2 Revolving Doors :
Revolving door shall not be provided as a means of fire exit.
9.2.3Stairways :
(a) A staircase shall not be arranged round a lift shaft.
(b) The staircase shall be ventilated to the atmosphere at each landing and a vent at the top; the vent openings shall be of 0.5 sq. m. in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 Pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1 m above the surrounding roof. Glazing or glass bricks if used in staircase, shall have fire resistance rating of minimum 2 hour.
(c) The minimum width of staircase shall be as table given below :—
Table 91 : Minimum width of staircase for different types of buildings
Type of Building
Width
Residential buildings (dwellings)
1.0 m
Residential hotel buildings
1.5 m
Assembly buildings like auditorium, theatres and cinemas
2.0 m
Educational buildings up to 30 m in height
1.5 m
Institutional buildings like hospitals
2.0 m
All other buildings
1.5 m
(d) The minimum width of treads without nosing shall be 0.25 m for staircase for residential buildings. In the case of other buildings, the minimum tread shall be 0.3 m. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 0.19 m in the case of residential buildings and 0.15 m in the case of other buildings and shall be limited to 15 risers per flight.
(e) Handrails shall be provided with a minimum height of 0.9 m from the centre of the tread.
(f) The minimum headroom in a passage under the lading of a staircase and under the staircase shall be 2.2 m.
(g) Access to main staircase shall be gained through adequate fire resistance rating (for various types of construction for structural and non-structural members shall be as given in Table 1 of Part IV of the NBC 2016 and for building elements/components such as walls, columns, beams and floors shall have the requisite fire resistance rating in accordance with the accepted standards at Tables 2 to 18 of Part IV of the NBC, 2016). Automatic closing doors placed in the enclosing walls of the staircases. It shall be a swing type door opening in the direction of the escape.
(h) No living space, store or other fire risk shall open directly into the staircase or staircases.
(i) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
(j) The exit sign with arrow indicating the way to the escape route shall be provided at a height of 1.5 m from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further all landings of floor shall have floor indication boards indicating the number of floors. The floor indication board shall be placed
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 149
on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5x 0.5 m and it shall be prominently on the wall facing the staircase.
(k) In case of single staircase, it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. However, the second staircase may lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door (Table 1 of Part IV of the NBC, 2016 and Tables 2 to 18 of Part IV of the NBC, 2016) or through a fire protected corridor.
9.2.4Lifts :
General requirements of lifts shall be as follows:—
(a) All the floors shall be accessible for 24 hours by the lifts. The lifts provided in the buildings shall not be considered as a means of escape in case of emergency. In a dual line arrangement (lifts opposite to each other) the lobby may be between 1.5 times to 2.5 times the depth of one car. For inline (single line) arrangements the lobby may be typically half of the above recommendations.
(b) Grounding switch, at ground floor level, to enable the fire service to ground the lift shall also be provided.
(c) The lift machine room shall be separate and no other machinery shall be installed therein.
(d) Walls of lift enclosures and lift lobby shall have fire rating of 2 hour; ((Table 1 of Part IV of the NBC, 2016 and Tables 2 to 18 of Part IV of the NBC, 2016) lifts shall have a vent at the top of area not less than 0.2 sq. m.
(e) Lift car door shall have a fire resistance rating of 1 hour.
(f) Lift lobby doors in lift enclosures shall have fire resistance as per Section (Table 1 of Part IV of the NBC, 2016 and Tables 2 to 18 of Part IV of the NBC, 2016).
(g) Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least 1 hour.
(h) If the lift shaft and lobby is in the core of the building, a positive pressure between 25 and 30 Pa shall be maintained in the lobby and a positive pressure of 50 Pa shall be maintained in the lift shaft. The mechanism for pressurization shall act automatically with the fire alarm; it shall be possible to operate this mechanically also.
(i) Lifts if communicating with the basement, the lift lobby of the basements shall be pressurized with self-closing door with fire resistance rating (Table 1 of Part IV of the NBC, 2016 and Tables 2 to 18 of Part IV of the NBC, 2016). Telephone or other communication facilities shall be provided in lift cars and to be connected to fire control room for the building.
(j) Exit from the lift lobby, if located in the core of the building, shall be through a self-closing fire door of half an hour fire resistance.
(k) Suitable arrangements such as providing slope in the floor of lift lobby shall be made to prevent water used during fire-fighting, etc., at any landing from entering the lift shafts.
(l) A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the locations of the stairways. Alternate source of power supply shall be provided for all the lifts through a manually operated changeover switch.
9.2.5Basements :
(a) Basement shall be permitted within the building envelope only.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 151
(b) Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 per cent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills or breakable stall board lights or pavement lights or by way of shafts. Alternatively, a system of air inlets shall be provided at basement floor level and smoke outlets at basement ceiling level. Inlets and extracts may be terminated at ground level with stall board or pavement lights as before, but ducts to convey fresh air to the basement floor level have to be laid. Stall board and pavement lights should be in positions easily accessible to the fire brigade and clearly marked ‘SMOKE OUTLET’ or ‘AIR INLET’ with an indication of area served at or near the opening.
(c) The staircase of basements shall be of enclosed type having fire resistance rating (Table 1 of Part IV of the NBC, 2016 and Tables 2 to 18 of Part IV of the NBC, 2016). The staircase shall be situated at the periphery of the basement to be entered at ground level only, from outside open air. The staircase shall communicate with basement through a lobby with self-closing doors with fire resistance rating as per relevant NBC Code mentioned above.
(d) For travel distance Table 9—2 given below shall be followed. If travel distance exceeds that given in the table below, additional staircases shall be provided.
Table 92 : Travel Distance for Occupancy and Type of Construction
Group of Occupancy
Maximum Travel Distance Construction (m)
Type 1 &2
Type 3 & 4
1
2
3
Residential (A)
30.0
22.5
Educational (B)
30.0
22.5
Institutional (C)
30.0
22.5
Assembly (D)
30.0
30.0
Business (E)
30.0
30.0
152 The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. [No. 39-4
(m) For Pressurization Specifications of various building components refer NBC, 2016 Chapter 4 Fire and Life Safety Clause 4.10 Pressurization of Staircases (Protected Escape Routes).
1
2
3
Mercantile (F)
30.0
30.0
Industrial (G)
45.0
Construction type 3 and 4 not permitted.
Storage (H)
30.0
Construction type 3 and 4 not permitted.
Hazardous (J)
22.5
Construction type 3 and 4 not permitted.
Notes:—
· For fully sprinkled building, the travel distance may be increased by 50% of the values specified above.
· Ramps shall be counted as one of the means of escape wherever permitted in National Building Code, 2016.
(e) In multi-story basements, intake ducts may serve all basement levels, but each basement level and basement compartment shall have separate smoke outlet duct or ducts. Ducts so provided shall have the same fire resistance rating as the compartment itself. Fire rating may be taken as the required smoke extraction time for smoke extraction ducts.
(f) Mechanical extractors for smoke venting system from lower basement levels shall also be provided. The system shall be of such design as to operate on actuation of heat/smoke sensitive detectors or sprinklers, if installed, and shall have a considerably superior performance compared to the standard units. It shall also have an arrangement to start it manually.
(g) Mechanical extractors shall have an internal locking arrangement, so that extractors shall continue to operate and supply fans for HVAC shall stop automatically with the actuation of fire detectors.
(h) Mechanical extractors shall be designated to permit 30 air changes per hour in case of fire or distress call. However, for normal operation, air changes schedule shall be as given in Part 8, Building Services, Section 3, Air-conditioning, Heating and Mechanical Ventilation of National Building Code, 2016.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 153
(i) Mechanical extractors shall have an alternative source of supply.
(j) Ventilating ducts shall be integrated with the structure and made out of brick masonry or reinforced cement concrete and when this duct crosses the transformer area or electrical switchboard, fire dampers shall be provided.
(k) Use of basements for kitchens working on gas fuel shall not be permitted, unless air conditioned. The basement shall not be permitted below the ward block of a hospital/nursing home unless it is fully sprinkled. Building services such as electrical sub-stations, boiler rooms in basements shall comply with the provisions of the Indian Electricity Act/Rules. Boiler room shall be provided at the first basement along the periphery wall with fire resistance rating Table 1 of Part IV of the NBC, 2016 and Tables 2 to 18 of Part IV of the NBC, 2016) or shall be separated with the blast wall.
(l) If cut-outs are provided from basements to the upper floors or to the atmospheres, all sides cut-out openings in the basements shall be protected by sprinkler head at close spacing so as to form a water curtain in the event of a fire.
(m) It is essential to make provisions for drainage of any such water on all floors to prevent or minimize water damage of the contents. The drain pipes should be provided on the external wall for drainage of water from all floors. On large area floors, several such pipes may be necessary which should be spaced 30 m apart. Care shall be taken to ensure that the construction of the drain pipe does not allow spread fire/smoke from floor to floor.
9.3Building Services :
9.3.1 Staircase and Corridor Lighting :
(a) The staircase and corridor lighting shall be on separate service and shall be independently connected so as it could be operated by one switch installation on the ground floor, easily accessible to fire-fighting staff at any time irrespective of the position of the individuate control of the light points, if any.
(b) Staircase and corridor lighting shall also be connected to alternate supply from parallel high-tension supply or to the supply from the stand-by generator.
(c) Emergency lights shall be provided in staircase and corridor/passageway, horizontal exits, refuge area; and all wires and other accessories used for emergency light shall have fire retardant property.
9.3.2 Electrical Services :
(a) The electric distribution cables/wiring shall be laid in separate duct the duct shall be sealed at every floor with non-combustible materials having the same fire resistance as that of the duct. Low and medium voltage wiring running in shaft and in false ceiling shall run in separate conduits.
(b) Water mains, telephone cables, intercom cables, gas pipes or any other service line shall not be laid in the duct for electric cables. Use of bus ducts/solid rising mains instead of cables is preferred.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 157
(c) The provision of dedicated telecommunication ducts for all new building proposals is mandatory for conveyance of telecommunication and other data cables.
(d) Separate circuits for water pumps lifts, staircases and corridor lighting and blowers for pressurizing system shall be provided directly from the main switchgear panel (for detailed specifications refer NBC, 2016, chapter 4 Fire and Life Safety).
9.3.3 Alternate Source of Electric Supply :
A stand-by electric generator shall be installed to supply power to staircase and corridor lighting circuits, fire lifts, the stand-by fire pumps, pressurization fans and blowers, smoke extraction and damper system in case of failure of normal electric supply. The generator shall be capable of taking starting current of all the machines.
9.3.4 Air-conditioning :
Air-conditioning shall conform to the following :—
(a) Escape routes like staircases, common corridors, lift lobbies, etc. shall not be used as return air passage.
(b) The ducting shall be constructed of sufficient gauge metal in accordance with good practice.
(c) Wherever the ducts pass through fire walls or floors, the opening around the ducts shall be sealed with materials having fire resistance rating of the compartment.
(d) Where duct crosses a compartment which is fire rated, the ducts shall be fire rated for same fire rating. Further depending on services passing around the duct work, which may get affected in case of fire temperature rising, the ducts shall be insulated.
(e) Metallic ducts shall be used even for the return air instead of space above the false ceiling.
(f) Where plenum is used for return air passage, ceiling and its fixtures shall be of non-combustible material.
(g) The materials used for insulating the duct system (inside or outside) shall be of non-combustible material; glass wool shall not be wrapped or secured by any material of combustible nature.
(h) Air ducts serving main floor areas, corridors, etc. shall not pass through the staircase enclosure.
(i) The air-handling units shall be separate for each floor and air ducts for every floor shall be separated and in no way inter-connected with the ducting of any other floor.
(j) If the air-handling unit serves more than one floor, the recommendations given above shall be compiled with in addition to the conditions given below.
(k) Proper arrangements by way of automatic fire dampers working on smoke detector/or fusible link for isolating all ducting at every floor from the main riser shall be made—
(i) When the automatic fire alarm operates, the respective air-handling units of the air-conditioning system shall automatically be switched off.
(ii) The vertical shaft for treated fresh air shall be of masonry construction.
(iii) The air filters of the air-handling units shall be of non-combustible materials or fire rated.
(iv) The air-handling unit room shall not be used for storage of any combustible materials.
(v) Inspection panels shall be provided in the main trunking to facilitate the cleaning of ducts of accumulated dust and to obtain access for maintenance of fire dampers.
(vi) No combustible material shall be fixed nearer than 150 mm to any duct unless such duct is properly enclosed and protected with non-combustible material (glass wool or spyglass with neoprene facing enclosed and wrapped with aluminium sheeting) at least 3.2 mm thick and which would not readily conduct heat.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 159
9.3.5 Transformers :
(a) If transformers are housed in the building below the ground level it shall be necessarily in the first basement in separate fire resistance room of 4 hours rating. Transformer shall be dry type and shall be kept in an enclosure with walls, doors and cut-outs having fire resistance rating of 4 hour. The room shall necessarily be at the periphery of the basement having separate and direct access from open area at ground floor through a fire escape staircase. The entrance to the room shall be provided with a steel door of 2 hours fire rating. A curb of a suitable height shall be provided at the entrance in order to prevent the flow of oil from ruptured transformer into other parts of the basement. The switchgears shall be housed in a separate room separated from the transformer bays by a fire-resisting wall with fire resistance not less than 4 hours.
(b) The transformer shall be protected by an automatic foam sprinkler system. When housed at ground floor level it/they shall be cut-off from the other portion of premises by Fire Resisting Walls of 4 hours rating.
(c) A tank of RCC construction of adequate capacity shall be provided at lower basement level, to collect the oil from the catch pit in case of emergency. The pipe connecting the catch-pit to the tank shall be of non-combustible construction and shall be provided with a flame-arrester.
(d) The electric sub-station shall be located in a separate building in accordance to I.E. Rules 68(I) and 64(I) (a).
(e) If this is not possible due to site conditions, the sub-station shall be located on the ground floor. As far as possible substation shall not be installed in a basement, for such situations special provisions like mechanical ventilation, wherever required, cable ducting, cable trays, top/bottom entry of HV/LV cable, hooks on Transformer(s) & HV panels, adequate fire detection and fire-fighting arrangement, adequate drainage, effective measures to prevent flooding etc. shall be provided. Adequate precautions shall also be taken for water proofing to
prevent seepage of water. A ramp shall also be provided with a slope, not steeper than 1 in 7, for easy movement of equipment to and from sub-station.
(f) Fire regulations-The installations shall be carried out in conformity with the local regulations and rules thereunder wherever they are in force. At other places NBC, 2016 guidelines shall be followed.
9.3.6 Gas supply :
(a) Town Gas/L.P. Gas Supply Pipes-Where gas pipes are run in buildings, the same shall be run in separate shafts exclusively for this purpose and these shall be on external walls, away from the staircases. There shall be no interconnection of this shaft with the rest of the floors.
(b) LPG distribution pipes shall always be below the false ceiling. The length of these pipes shall be as short as possible. In the case of kitchen cooking range area, apart from providing hood, covering the entire cooking range, the exhaust system should be designed to take care of 30 CUM per minute per sq.m. of hood protected area. It should have grease filters using metallic grill to trip oil vapours escaping into the fume hood.
Note:—For detailed information on gas pipe installations, reference may be made to Para 9 ‘Plumbing Services, Section 3 Gas Supply’, of NBC, 2016.
(c) For large/commercial kitchens all wiring in fume hoods shall be of fiber glass insulation. Thermal detectors shall be installed into fume hoods of large kitchens for hotels, hospitals and similar areas located in high rise buildings. Arrangements shall be made for automatic tripping of the exhaust fan in case of fire.
(d) If LPG is used, the same shall be shut off. The voltage shall be of 24 V or 100 V DC operated with the external rectifier. The valve shall be of the hand re-set type and shall be located in an area segregated from cooking ranges. Valves shall be easily accessible. The hood shall have manual facility for steam or carbon dioxide gas injection,
No. 39 4 - ]
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 161
depending on duty condition; and Gas meters shall be housed in a suitably constructed metal cupboard located in a well-ventilated space, keeping in view the fact that LPG is heavier than air and town gas is lighter than air.
9.3.7 Boiler Room :
Further, the following additional aspects may be taken into account in the location of Boiler/Boiler Room:—
(a) The boiler shall not be allowed in sub-basement but be allowed in the first basements away from the escape routes.
(b) The boilers shall be installed in a fire resisting room of 4 hours fire resistance rating, and this room shall be situated on the periphery of the basement. Catch pit shall be provided at the low level. Entry to this room may be provided with a composite door of two-hour fire resistance.
(c) The boiler room shall be provided with fresh air inlets and smoke exhausts directly to the atmosphere.
(d) Foam inlets shall be provided on the external walls of the building at the ground floor level to enable the fire services to use foam in case of fire.
(e) The furnace oil tank for the boiler, if located in the adjoining room shall be separated by fire resisting wall of 4-hour rating. Entry to this room shall be provided with a composite door of 2-hour fire resistance. A curb of suitable height shall be provided at the entrance in order to prevent the flow of oil into the boiler room in case of tank rupture.
9.3.8 Helipad :
Buildings above 200 m in height, helipad may be provided.
9.3.9 Disaster Management (Fire Safety) :
Refer Part 4 of NBC 2016 for minimum requirements for firefighting installations.
9.3.10 Structural Safety :
As per provisions made for Structural Safety in Chapter 6 of MBBL 2016 and from Section 12.2.5.1 of NBC 2016 or its latest version.
The application for seeking building permit shall be accompanied with a report of Architect/Structural Engineer certifying that the proposed structure has been designed structurally keeping in view the safety measures against earthquakes as indicated in the following Bureau of Indian Standards (B.I.S.).
List of Codes Published by CED 39 (Earthquake Code Committee) of Bureau of Indian Standards
Sr. No.
Code No
Year of Revised Publicat-ion
Year of Reaffir-mation
Title
1
2
3
4
5
1
IS 13935
2009
2014
Seismic Evaluation, Repair and Strengthening of Masonry Buildings-Guidelines.
2
IS 1893: Part 1
2016
Criteria for Earthquake Resistant Design of Structure-Part 1 : General Provisions and Buildings.
3
IS 4326
2013
Earthquake resistant design and construction of buildings-Code of practice.
4
IS 13920
2016
Ductile Design and Detailing of Reinforced Concrete Structures Subjected to Seismic Force-Code of Practice (First Revision).
5
IS 13827
1993
2013
Improving earthquake resistance of earthen buildings-Guidelines.
6
IS 13828
1993
2013
Improving earthquake resistance of low strength masonry buildings-Guidelines.
7
IS 1893: Part 2
2014
Criteria for Earthquake Resistant Design of Structures-Part 2 Liquid Retaining Tanks.
No. 39-4] The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 163
1
2
3
4
5
8
IS 1893: Part 3
2014
Criteria for Earthquake Resistant Design of Structures Part 3 Bridges and Retaining Walls.
9
IS 1893: Part 4
2015
Criteria for Earthquake Resistant Design of Structures Part 4 Industrial Structures Including Stack-Like Structures (First Revision).
9.3.11 Sustainable Environment and Buildings :
Refer CHAPTER 11 : of this document.
9.3.12 General :
(a) Architectural elements such as louvers, pergolas, other sunshine materials should be free from FAR.
(b) Any architectural roof top structures would also be permitted out of FAR if not used for habitable or commercial purposes.
(c) Building elements such as sky bridges and landscape terraces which are meant for community purposes only shall be permitted free of FAR.
(d) Services can be permitted on roofs with adequate screening for the same.
(e) Service floors shall not be counted in FAR. Service area on habitable floors may be considered free from FAR.
(f) Atrium/Atria at any floor will be counted only once in the FAR. Atrium may be enclosed by light roofing or R. C. C. as per NBC, 2016.
(g) Scissor staircase would be permitted provided all travel distance and fire norms are adhered to.
(h) Stilts in high-rise will not be restricted to height. of 2.4m as long as it is used for parking.
(i) Multilevel car parking with car lifts would be permitted with adequate fire safety.
9.4 Tall Building :
Building with height more than 50 m shall be considered as Tall buildings. All the provisions and norms applicable for High Rise Building shall be also applicable for Tall Buildings. In addition to that, Tall Buildings shall be allowed only on the roads having minimum ROW 60m with standard service lanes.
(a) An Opening to the glass façade of min. width 1.5 m and height 1.5 m shall be provided at every floor at a level of 1.2 m from the flooring facing compulsory open space as well as on road side. Construction that complies with the fire rating of the horizontal segregation and has any gap packed with a non-combustible material to withstand thermal expansion and structural movement of the walling without the loss of seal against fire and smoke.
(b) Mechanism of Opening: The openable glass panel shall be either left or right shall have manual opening mechanism from inside as well as outside. Such openable panels shall be marked conspicuously so as to easily identify the openable panel from outside.
(c) Fire seal to be provided at every floor level between the external glazing and building structure.
(d) The glazing used for the façade shall be of toughened (tempered) safety glass as per I.S.2553.
155
(e) To avoid fire propagation vertically from one floor to another floor, a continuous glass I must be separated internally by a smoke/fire seal which is of non-combustible material having a fire resistance rating of not less than 2 hours.
(f) Service ducts and shafts shall be enclosed by walls and doors with fire resistance rating (clause Error! Reference source not found. of Error! Reference source not found.). All such ducts/shafts shall be properly sealed and stopped fire ingress at all floor levels.
(g) A vent opening at the top of the service shaft shall be provided having an area between one-fourth and one-half of the area of the shaft.
(h) The openable vent of minimum 2.5% of the floor area shall be provided. The openable vent can be pop out type or bottom hinged provided with fusible link opening mechanism and shall also be integrated with Automatic Smoke Detection System
(i) Alternate vertical glass panels of the façade shall be openable type with the mechanism mentioned above in order to ventilate the smoke.
(j) Refuge areas covered with the glass façade shall have all the panels fully openable (either left or right hinged) both from inside as well as outside.
(k) Glass quality and Practice of use of Glass in buildings shall have to be in conformity with the BIS codes as given in Table 9—3 below:—
Table 93: Glass quality and Use of glass in buildings
IS Code
Specifications
1
2
2553 (Part 1):1990
Specification for safety glass: Part 1 General purpose (third revision)
2835:1987
Specification for flat transparent sheet glass (third revision)
438:1994
Specification for silvered glass mirrors for general purposes (second revision)
156 The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. [No. 39-4
1
2
5437:1994
Specification for figured rolled and wired glass (first revision).
14900:2000
Specification for transparent float glass.
16231 Part 1
General methodology for selection
16231 Part 2
Energy and Light.
16231 Part 3
Fire and Loading
16231 Part 4
Safety related to Human Impact
9.2.6Compartmentation :
(a) The building shall be suitably compartmentalized so that fire/smoke remains confined to the area where fire incident has occurred and does not spread to the remaining part of the building.
(b) Compartmentation and Pressurization method shall be adopted (as per clause 4.10 of Part 4 of NBC, 2016) to
154 The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. [No. 39-4
protect escape routes against ingress of smoke, or toxic gases into the escape routes will be prevented. Pressurization shall be adopted for high rise buildings and building having mixed occupancy/multiplexes having covered area more than 500 m.
9.2.7 Corridors :
(a) Exit corridors and passageways shall be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.
(b) The minimum width of a corridor in a residential building shall be 1.0 m for single loaded and 1.8 m for double loaded and in all other buildings shall be 1.5 m.
(c) Where stairways discharge through corridors and passageways, the height of corridors and passageways shall be not less than 2.4 m.
(d) All means of exit including staircases lifts lobbies and corridors shall be ventilated.
10
IS 4967
1968
2015
Recommendations for Seismic instrumentation for river valley projects.
11
IS 4991
1968
2013
Criteria for blast resistant design of structures for explosions above ground.
12
IS 6922
1973
2013
Criteria for safety and design of structures subject to under-ground blasts.