5.2.7.1 Solar Water Heating
Hospitality and Healthcare in all climatic zones and all buildings in cold climate zone with a hot water system, shall have solar water heating equipment installed to provide for:
(a) at least 20% of the total hot water design capacity if above grade floor area of the building is less than 20,000 m2
(b) at least 40% of the total hot water design capacity if above grade floor area of the building is greater than or equal to 20,000 m2
Exception to § 5.2.7.1: Systems that use heat recovery to provide the hot water capacity required as per the building type and size.
5.2.7.2 Heating Equipment Efficiency
Service water heating equipment shall meet or exceed the performance and minimum efficiency requirements presented in available Indian Standards
(a) Solar water heater shall meet the performance/ minimum efficiency level mentioned in IS 13129 Part (1&2).
(b) Gas Instantaneous water heaters shall meet the performance/minimum efficiency level mentioned in IS 15558 with above 80% Fuel utilization efficiency.
(c) Electric water heater shall meet the performance/ minimum efficiency level mentioned in IS 2082.
(d) For evacuated tube collector the storage tanks shall meet the IS 16542:2016, tubes shall meet IS 16543:2016 and IS 16544:2016 for the complete system.
5.2.7.3 Other Water Heating System
Supplementary heating system shall be designed to maximize the energy efficiency of the system and shall incorporate the following design features in cascade:
(a) Maximum heat recovery from hot discharge system like condensers of air conditioning units,
(b) Use of gas fired heaters wherever gas is available, and
(c) Electric heater as last resort.
COMFORT SYSTEMS
COMFORT SYSTEMS
5.2.7.4 Piping Insulation
Piping insulation shall comply with §5.2.4.1. The entire hot water system including the storage tanks, pipelines shall be insulated conforming to the relevant IS standards on materials and applications.
5.2.7.5 Heat Traps
Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a non-recirculating system shall have heat traps on both the inlet and outlet piping.
5.2.7.6 Swimming Pools
All heated pools shall be provided with a vapor retardant pool cover on or at the water surface. Pools heated to more than 32°C shall have a pool cover with a minimum insulation value of R-4.1.
5 . 3 P r e s c r i p t i v e R e q u i r e m e n t s
Compliance shall be demonstrated with the prescriptive requirements in this section. Supply, exhaust, and return or relief fans with motor power exceeding 0.37 kW shall meet or exceed the minimum energy efficiency requirements specified inTable 5-9 through Table 5-11 except the following need not comply with the requirement
(a) Fans in un-ducted air conditioning unit where fan efficiency has already been taken in account to calculate the efficiency standard of the comfort system.
(b) Fans in Health Care buildings having HEPA filters.
(c) Fans inbuilt in energy recovery systems that pre-conditions the outdoor air.
| System type | Fan Type | Mechanical Efficiency | Motor Efficiency(As per IS 12615) |
|---|---|---|---|
| Air-handling unit | Supply, return and exhaust | 60% | IE 2 |
| System type | Fan Type | Mechanical Efficiency | Motor Efficiency (As per IS 12615) |
|---|---|---|---|
| Air-handling unit | Supply, return and exhaust | 65% | IE 3 |
| System Type | Fan Type | Mechanical Efficiency | Motor Efficiency (As per IS 12615) |
|---|---|---|---|
| Air-handling unit | Supply, return and exhaust | 70% | IE 4 |
5.3.1 Chillers
Chillers shall meet or exceed the minimum efficiency requirements as per Standards and Labelling Program of BEE for ECBC+ and Super ECBC buildings.
i. Minimum 3 Star rated chillers is required for ECBC+ compliance and
ii. 5 star rated chiller to meet Super ECBC compliance.