Restriction on permission.-Without prejudice to any other stipulation in these bye-laws, no permission to construct a building on a site shall be granted:
A. In areas of natural waterways or drains, as detailed in the Development Plan, and drainage plan as modified from time to time;
B. If the orientation of such building is not in harmony with the surroundings, as may be decided by the Art Commission;
C. If the use to which the site is proposed to be put does not conform to the use earmarked in the Development Plan;
D. If the building is to be constructed over or under a municipal drain, sewerage line, electrical line, water main, any other government or public land, or public utility services;
E. If the foundation of the external wall along a street is located at a distance less than 1 meters from the edge of the street or road margin including the drain;
F. As Bihar is located in Seismic Zone III, IV and V if the Structural Plans are not prepared taking this into account.
G. In case of areas which get flooded, the Structural Plans are not prepared taking this into account.
30. Requirement of Site.-
A. No building shall be constructed on any site on any part of which there is deposited refuse, excreta or other offensive matter objectionable to the Authority. Until such refuse has been removed therefrom and the site has been prepared or left in a manner suitable for building purposes to the satisfaction of the Authority;
B. No permission to construct a building on site shall be granted, it the site is within nine (9) meters of the highest water mark of a tank, unless the owner satisfies the Authority that he will take such measures as will prevent any risk of the domestic drainage of the building passing into the tank. Further the Authority may require the floor of the lowest storey of such building to be raised above the normal maximum flood level of the adjoining ground or to such other level as the Authority may specify;
C. Wherever the dampness of a site or the nature of the soil renders such precautions necessary, the ground surface of the site between the walls of any building erected thereon shall be rendered damp-proof to the satisfaction of the Authority:
D. Any land, passage or other area within the cartilage of a building shall, if the Authority so requires, be effectively drained by surface water drains or other means;
E. If the foundation of the external wall along a street is located at a distance less than 1 meters from the edge of the street or road margin including the drain;
The written approval of the Authority shall be obtained for connecting any sub-soil or surface water drain to a sewer;
Distance from Electric lines.-As provided in clause-6.4 of National Building Code-2005 no verandah, balcony or the like shall be allowed to be erected or re-erected or any additions or alterations made to a building within the distances quoted below in accordance with the Indian Electricity Rules between the building and any overhead electric supply line. The minimum distance from the electric line shall be as per Table 5.
Table - 5: Minimum distance from electric line
Vertical distance in meters
Horizontal distance in meters
Low and medium voltage lines and service lines
2.5
1.2
High voltage lines up to and including 11,000 Volt
3.7
1.2
High voltage lines above 11,000 volt and up to and including 33,000 Volt
3.7
2.0
Extra high voltage line beyond 33,000 Volt
3.7 (Plus 0.3 meters for every additional 33,000 volts or part thereof)
2.0 (Plus 0.3 meters for every additional 33,000 volts or part thereof)
Plantation.-In every building area, at least 5 % of the land shall be covered by plantation (tree cover), but in case of multi-storied buildings/ Group Housing / Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover). Internal gardens within the building shall be encouraged.
Means of Access.-(1) Every building/ plot shall abut on a public/private means of access like streets /roads of duly formed of width as specified in these byelaws or specified in the Master Plan/ Development/Zonal Plan/Scheme.
Bihar Building Bye-Laws
89(1524)/(472-74) A.m. 6 d
: ;
The minimum width of the road/street required for access to building in an existing colony not developed by any authorized agency such as Regional Development Authority, Municipality, Housing Board, Co-operative societies, Government and Semi government organization shall be as per Table 6.
Table 6Length of road limitation
Old Area
Sl.No.
Maximum Length of the road in Meter
Minimum width of road of street in Meter
(i)
(ii)
(iii)
1
Upto 25 meter
3.6 meter or 12 feet
2
Exceeding 25 meter and upto 100 meter
4.8 meter or 16 feet
3
Exceeding 100 meter
6.10 meter or 20 feet
Note-On less than 20 feet wide roads the encroachement from both sides will be removed by measuring 10 feet from the centre line of the width of roads declared by or belonging to Road Construction Department. Patna Municipal, Authority, Housing Board, Co-operative Societies, Government and Semi-Government Organizations. In other cases maximum 10 feet land from such revenue plot on either side will be taken into account to make it 20 feet wide road and the construction falling in between the said width of road will be removed as an encroachment.Similarly 6 feet and 8 feet land from each Revenue plot on either side will be taken into account to make it 12 feet and 16 feet wide road correspondingly.
New Area (Residential)
1
75
6.10 (20 ft.)
2
250
9.10 (30 ft.)
3
400
12.20 (40 ft.)
4
1000
18.30 (60 ft.)
5
ahove 1000
24.40 (80 ft.)
Note- If the developments only on one side of the means of access, the prescribed widths maybe reduced by 1.0 meter each case. In no case, development on plots shall be permitted unless it is accessible by a public street of width not less than 6 m.
New Area (Non residential)
1
200
12.20 (40 ft.)
2
400
15.00 (50 ft.)
3
600
18.30 (60 ft.)
4
above 600
24.40 (80 ft.)
Further, in no case the means of access shall be lesser in width than the internal access ways in layouts and subdivision.
Bihar Building Bye-Laws
-Laws
4718m/4712-14 ### b q
-61~
N-II
9.10 (30 ft.)
2.5
Nil
S+5
18
the parking floors or provision for parking shall be used for any other purposes. Mezzanine floors or any floor partition shall be computed under FAR and counted as a floor.
N-III
12.20 (40 ft.)
2.5
2.0
Maximum Height 24 meter
N-IV
18.30 (60 ft.)
2.5
2.5
No restriction on height and number of floors however it may be regulated by the master plan/development plan/zonal plan
N-V
24.40 (80 ft.)
3.00
2.5
N-VI
27.40 (90 ft.)
3.25
3.0
N-VII
30.50 (100 ft.)
3.50
3.5
(2) While sanctioning the plans on building with a road width of 12 feet and 16 feet the Authority shall ensure that enough parking spaces for vehicles have been made within the building and that the vehicles shall not parked on the road. Provisions related to length of the road in Table 6 shall be adhered to.
(3) Additional FAR up to 10% upto a maximum of 0.25 shall be allowed for dwelling units meant exclusively for LIG/EWS in a group housing scheme.
(4) In case of Educational, Institutional and Assembly building the maximum permissible FAR shall be 1.50 for plots up to 1000 sq. m. and 1.75 for plots above 1000 sq. m.
(5) In case of transport related activities such as; railway yards, railway station, bus stands, bus shelters, transport depot, airport, special warehousing, cargo terminals etc. the maximum permissible FAR shall be 1.50.
(6) In case of Industrial buildings the maximum FAR shall be 0.5 for polluting and hazardous industries. In case of non-polluting and household industries the maximum FAR shall be 1.5.
(7) The FAR and Height of the building may also be regulated by the master plan/development plan or the zonal plan.
(8) In case the plot is affected by a road widening and the owner of the plot voluntarily surrenders the affected portion of his land to the Authority without any claim of compensation or through a TDR (Transferable Development Right) scheme implemented by the Government the owner shall be entitled to build on the remaining plot an area, calculated on the basis of the FAR as applied to the total area prior to such surrender. Provided that the surrender of the land shall be effected by a deed of transfer to be executed by the owner in favour of the Authority for widening of road.
(ii) Habitable Rooms
(a) Height: The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab). In the case of pitched roof, the average height of rooms shall not be less than 2.75 m. The minimum clear head room under a beam, folded plates or eaves shall be 2.4 m. In the case of air-conditioned rooms, a height of not less than 2.4 m measured from the surface of the floor to the lowest point of air-conditioning duct or the false ceiling shall be provided. These requirements shall apply to residential, business and mercantile buildings. For educational and industrial buildings, the following minimum requirements apply:
• Educational : Ceiling height 3.6 m for all Buildings regions;
- Industrial: Ceiling height 3.6 m, except Buildings when air-conditioned, 3 meter (Factory Act 1948 and Rules therein shall govern such heights, where applicable).
(b) Size: The area of habitable room shall not be less than 9.5 Sq meter, where there is only one room with a minimum width of 2.4 m. Where there are two rooms, one of these shall not be less than 9.5 Sq meter and the other not less than 7.5 Sq meter, with a minimum width of 2.1 m.
(iii)Kitchen
(a) Height: The height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom slab) shall not be less than 2.75 m, except for the portion to accommodate floor trap of the upper floor.
ye-Laws
任印 57###/412-19 ###/d e
Bihar Buliding Bye-Laws
-66-
(b) Size: The area of a kitchen where separate dining area is provided, shall be not less than 5.0 Sq meter with a minimum width of 1.8 m. Where there is a separate store, the area of the kitchen maybe reduced to 4.5 Sq meter. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 Sq meter with a minimum width of 2.1 m.
(c) Other Requirements: Every room to be used as kitchen shall have:
- unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
• an impermeable floor;
- a flue, if found necessary; and
- a window or ventilator or opening of sufficient size.
(iv)Bathrooms and Water-Closets
(a) Height: The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.4 meter.
(3) Capacities of Exits-
(a) The unit of exit width used to measure capacity of any exit shall be 50cm. A clear width of 25cm. shall be counted as an additional half unit. Clear width less than 25cm. shall not be counted for exit width,
(b) The occupancies per unit exit which shall be as given in Table 20.
Table 20Number of occupants as per type of occupancy
S.N
Type of Occupancy
Number of occupants per unit exit
Stair Case
Door
(1)
(2)
(3)
(4)
1
Residential
25
75
2
Educational
25
75
Bihar Building Bye-Laws
Hily
(1)/(2)x - 1 > 0
[NO TEXT]
-68
3
Institutional
25
75
4
Assembly
60
90
5
Business
50
75
6
Mercantile
50
75
7
Industrial
50
75
8
Storage
50
75
9
Hazardous
25
10
5/12/4 A### d
Q
-54-
(2) No building construction activity shall happen on a road with a width of less than 12 ft. (Including Road Widening) in old area.
(3) In case of areas notified as New Areas by the authority with the approval of the department, no construction shall be allowed where the means of access is less than 20 feet.
(4) Unless and otherwise specified, development of plots shall not be permitted unless it is accessible by a public/private street with the width specified in these bye laws. The width of the road may be increased in a master plan/development plan/zonal plan but under no circumstance the provisions for width of road shall be less than the provisions made under these bye laws.
(5) In case of institutional, administrative, assembly, industrial and other non-residential and commercial activities, the minimum road width shall be 12.20 meters.
(6) In case public land is not available for the road, the plot owners on both sides of the road shall equally surrender their right over the land to the authority to accommodate the road width. The centre line of the road shall be taken as reference for such surrenders.
(7) While calculating the width of the street for the purpose of sanctioning the building plan, the average width will be taken into consideration. The building plan shall be approved on the basis of the average width of the road as notified by the authority.
(8) In case of a private road, which gives access to one or more buildings, the owner of the said private road shall develop the road and storm water drain as required by the Local Authority, and transfer the same to the Registered Residents' Welfare Association for maintenance.
(9) Access from Highways/ Important Roads.-No premises other than highway amenities like petrol pumps, motels, etc, shall have an access direct from highways and other roads designated by the Road ConstructionDepartment. The Road Construction Department shall notify a list of road, which shall not provide direct access to a specified class of buildings. The Authority shall maintain a register of such roads, which shall be open to public inspection at all times during office hours and published on the web site. These provisions shall, however, be subject to the provisions of the relevant State Highway Act, and National Highway Act.
(10) The provisions of road width shall be strictly enforced. There shall be no construction over the prescribed road width. Any violation shall be treated as an offence under the Bihar Municipal Act 2007 in addition to provision for removal of land encroachment under the relevant Acts.
(1) General
Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants, in case of fire or other emergency.
(a) In every building exit shall comply with the minimum requirement of exit except those not essential for general public use.
(b) All exits shall be free from obstructions.
(c) No building shall be altered so as to reduce the number, width of protection of exits to less than that required.
(d) Exits shall be clearly visible and the routes to reach the exits shall be clearly marked and signposted to guide the population of floor concerned.
(e) Adequate and reliable illumination shall be provided for exits.
(f) Fire fighting equipment shall be suitably located and clearly marked.
(g) Alarm devices shall be installed to ensure prompt evacuation of the population concerned.
(h) All exits shall provide continuous means of egress to the exterior of building or to an exterior open space leading to street.
(i) Exits shall be so arranged that they may be reached without passing through another occupied unit.
(2) Arrangement of exits- Exits shall be so located so that the travel distance on the floor shall not exceed 20 meters for residential, educational, institutional, and hazardous occupancies and 30 meters for assembly, business mercantile, industrial and storage occupancies.
Explanation:
(A). Lifts and escalators shall not be considered as an exit.
(B). Travel distance' means the distance from any point in the floor area to any exit measured along the path or egress except that when the floor areas are sub-divided into rooms, used singly or of rooms and served by suite corridors and passage, the travel distance may be measured from the corridor entrance of such rooms or suites to the nearest staircase or verandah having access to the street.
(C). For the dormitory portions of homes for the aged, orphanages, mental hospitals, etc. these multipliers will be doubled.
(D). The plinth or covered area shall include, in addition to the main assembly rooms or space, any occupied connecting room or space in the same storey or in the storey above or below where entrance is common to such rooms and space and they are available for use by the occupants of the assembly place.
(E). No deductions shall be made in the gross area of the corridors, closets or other sub-divisions; all space serving the particular assembly occupancy shall be reckoned.
Other requirements of Exits-
(a) Every exit doorway shall open into a enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
(b) No exit doorway shall be less than 100c.m, in width. Doorways shall be not less than 200 c.m. in height.
(c) Exit doorways shall open outwards, that is away from the room but shall not obstruct the travel along any exit. No door, when opened shall reduce the required width of stairway or landing to less than 90cm. Over head or sliding doors shall not be installed.
(d) Exit door shall not open immediately upon a flight or stairs; a landing equal to at least the width of the door shall be provided in the stairway at each doorway; level of landing shall be the same as that of the floor which it serves.
(e) Exit doorways shall be openable from the side which they serve without the use of key.
(5) Other Exists
(i) Revolving Doors-
Bihar Building Bye-Laws
-69
(a) Revolving doors shall not be used as required exits except in residential, business and mercantile occupancies, but shall not constitute more than half the total required door width.
(b) When revolving door is considered as required exit way the following assumptions shall be made.
- Each revolving door shall be constituted on half unit exit width.
■ Revolving door shall not be located at the foot of a stairway. Any stairway served by a revolving door shall discharge through a lobby or foyer.
(2) Access Path/ Walk Way:
Access path from plot entry and surface parking to building entrance shall be minimum of 1800 mm. wide having even surface without any steps. Slope, if any, shall not have gradient greater than 5%. Selection of floor materials shall be made suitably to attract or to guide visually impaired persons (Limited to coloured floor material whose colour and brightness is conspicuously different from that of the surrounding floor material or the material that emit different sound to guide visually impaired persons hereinafter referred to as "guiding floor material"). Finishes shall have non slip surface with a texture traversable by a wheel chair. Curbs wherever provided should blend to a common level.
(ii) Stairways -
(a) Interior stairs shall be constructed of non-combustible materials throughout.
(b) Interior staircase shall be constructed as a self-contained unit with at least one side adjacent to an external wall and shall be completely.
(c) A staircase shall not be arranged round a lift shaft unless the latter is entirely enclosed by a material of fire-resistance rating as for that type of construction itself.
(d) Hollow combustible construction shall not be permitted.
(e) The minimum width of an internal staircase shall be 100 cm.
(f) The minimum width of treads without nosing shall be 25 cm. for an internal staircase for residential building. In the case of other buildings the minimum tread shall be 30 cm. The treads shall be constructed and maintained in a manner to prevent slipping.
(g) The maximum height of riser shall be 10 cm, in the case of residential buildings and 15 cm, in the case of other buildings. They shall be limited to 12 per flight.
(h) Hand rails shall be provided with a minimum height of 90 cm. from the centre of the trend.
(9) Exclusive multistory parking blocks can be provided within the required setback area without reducing the driveway for the fire tender to the extent of minimum 6 meters. This will not be included in the calculation of FAR.
(10) FAR shall not include
A. Basements or cellars and space under a building constructed on stilts and used only as a parking space, and air conditioning plant room used as accessory to the principal use;
B. Stilt Parking
Bihar Building Bye-Laws
[Signature]
C. Exclusive Multi Storey Parking made only for the purpose of parking vehicles and not put to any other use.
D. Electric cabin or substation, watchman booth of maximum size of 3sq.m. with minimum width or diameter of 1.732 m., pump house, garbage shaft, space required for location of fire hydrants, electric fittings and water tank, society room of maximum 12 sq.mtr.
E. Projections and accessories buildings as specifically exempted from the open space/setback requirement.
F. Staircase room and lift rooms above the topmost storey, architectural features, and chimneys and elevated tanks of dimensions as permissible under the NBC; the area of the lift shaft shall be taken only on one floor.
G. 50% of the area of projected balcony as per bye laws 45(4) shall not include.
(11) Additional FAR may be allowed for Government Buildings/ Government Projects with the prior approval of the Government.
Height of a building.-(1) The height of the building shall be governed by the limitations of Floor Area Ratio, open space (setbacks), and the width of the street facing the plot described as detailed below:
A. The maximum height of a building shall in no case exceed (1.5 times X the width of the road on which the plot abuts) + the front setback. It shall be applicable only in case of unused permissible FAR for plots abutting on road of average existing width not less than 9.10 m wide.
B. If a building abuts on two or more streets of different widths, the building shall be deemed to face upon the street that has the greater width and the height of the building shall be regulated by the width of the street.
Provided that the roads on the other sides shall also conform to provisions made under bye law 33.
(2) Notwithstanding anything contained in sub-bye law (1) the height restrictions with respect to approach Funnels and Transitional area of Airport as detailed in Table -17 and 18 shall be adhered to. Any height restrictions imposed by the Airport Authorities shall be adhered to.
(3) Notwithstanding anything contained in the Tables under sub-bye law(1), no Radio Aerial, T.V. Antenna, Cell phone tower or such similar type of installations exceeding 52 metres in height shall be erected without prior permission of the concerned Civil Aviation Authority/ Airport Authority.
(4) No building structure or installation exceeding the height indicated in the said Tables shall be permitted unless the applicant produces a 'No-Objection Certificate' from the Airport Authority.
Table- 17: Height restriction with respect to approach funnels
Distance from nearest runway end (in metres)
Maximum Permissible height above the elevation of the nearest runway end
A###
so12 - so24/2 - 14
b q
Bihar Building Bye-Laws
-63-
Up to 360
0
361 to 510
6
511 to 660
9
661 to 810
12
811 to 960
15
961 to 1110
18
1111 to 1260
21
1261 to 1410
24
1411 to 1560
27
More than 1560
30
Table -18Height restriction with respect to transitional area
Distance of the Inner Boundary of the Transitional Area (Outer Boundary of the Air Port) [Metres]
Maximum Permissible height above the elevation of the airport reference point [metres]
Up to 21
0
22 to 42
3
43 to 63
6
64 to 84
9
85 to 105
12
106 to 126
15
127 to 147
18
148 to 168
21
169 to 189
24
190 to 210
27
More than 210 M
30
Off Street Parking Space.-(1) In all buildings including Apartment buildings/ Group Housing, Hotels, Restaurants and Lodges, business buildings, commercial buildings, Institutional buildings like hospitals, Educational buildings like schools and colleges, multi-storied buildings/complexes etc. and all other non-residential activities provision shall be made for parking spaces as per the requirements mentioned in Table 19.
(2) The parking spaces may be provided in (for all schemes)
A. Basements or cellars
B. on stilt floor
C. open parking area
D. exclusive multi-level parking or
E. Roof top parking in case of commercial/IT/ITES and corporate building
F. A combination of any or all of the above.
Any provision made for parking shall not be included in the FAR calculation.
Table 19: Parking space for different category of occupancies
Ing Bye-Laws
Bye Laoa/12/4
Bye Laoa/12/4
-64-
SI.No.
Category of building/ activity
Parking area to be provided as percentage of total built up area
(1)
(2)
(3)
1
Shopping malls, Shopping malls with Multiplexes/ Cineplexes, Cinemas, Retail shopping centre and marriage halls and banquet halls
35
2
IT / ITES complexes, Hotels, Restaurants, Lodges, Nursing Homes, Hospitals, Institutional and other commercial buildings, Assembly buildings, offices, and Industrial buildings and High-rise buildings and complexes.
30
3
Residential Building, Residential apartment buildings, Group Housing, Clinics and small offices upto 50 sqm.
25
(3) Off-street parking spaces shall be provided with adequate vehicular access to a street and the area of drives, aisles and such other provisions required for adequate maneuvering of vehicles.
(4) If the total off-street parking space required under these bye laws is provided by a group of property owners at a place for their mutual benefit, such parking spaces may be construed as meeting the off-street parking requirement, however, subject to the approval of the Authority. The Authority may also decide to develop such parking spaces and charge property owners to bear proportionate cost.
(5) Garage with locking facilities shall be included in the calculation of floor space for determining the requirement of parking space, unless this is provided in the basement of a building or under a building constructed on stilts with no external walls.
(6) The parking spaces to be provided shall be in addition to the open spaces (setback) required around a building under these bye laws.
(7) Misuse of the area specified for parking of vehicles for any other use shall be summarily removed / demolished by the Authority.
(8) For parking spaces in basements and upper storey of parking floors, at least two ramps of minimum 3.6 m width or one ramp of minimum 5.4 m width and in maximum 1:10 slope shall be provided. Such ramps may be permitted in the side and rear setbacks after leaving 3.60 meter space for movement of fire-fighting vehicles. Access to these may also be accomplished through provisions of mechanical lifts. The slab over which the fire tender shall move shall be cable of taking the load of fire engine, fire vehicle of atleast 45 tonnes.
(9) Up to 10% of cellar may be utilized for utilities and non-habitation purpose like A/C plant room, Generator room, Electrical installations, laundry etc.
[Illegible Handwriting]
for L = (2)/(472) · 14 Ahm. L Q
-65-
Bihar Building Bye-Laws
(10) At least 15% of the parking space in group housing, apartment buildings shall be earmarked for visitors. Such parking space shall be indicated by painting "Visitor's Parking" on the floor. The Visitors parking facility shall be open to all visitors and shall not be settled with any occupant.
(11) All buildings with a height of 15 m and above will have parking space earmarked for ambulance, fire tender and physically challenged persons. Such spaces shall be clearly indicated by painting on the floor the purpose for which the parking space is reserved.
(12) Apart from use of Basement for Services/Parking/ Storage, it may be used for other activities like library, Study Room, Games Room and Laundry only in case of Residential and Institutional Buildings.
Requirement of Parts of Building.-The various parts of the buildings shall have the following minimum specifications.
(i) Plinth
(a) Main Buildings: The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm from the surrounding ground level.
(b) Interior Courtyards and Covered Parking: Every interior courtyard shall be raised at least 150 mm above the determining ground level and shall be satisfactorily drained.
(b) Size: The area of a bathroom shall not be less than 1.8 Sq meter with a minimum width of 1.2 m. The floor area of water-closet shall be 1.2 Sq meter with a minimum width of 1.0 m. If bath and water-closet are combined, its floor area shall not be less than 2.8 Sq meter with a minimum width of 1.2 m.
(c) Other Requirements : Every bathroom or water-closet shall:
- be so situated that at least one of its walls shallopen to external air;
- not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
- have the platform or seat made of water-tight non-absorbent material be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
- be provided, with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
- have a window or ventilator, opening to a shaft or open space, of area not less than 0.3m² with side not less than 0.3m.
(d) No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking
Bihar Building Bye-Laws
-67-
space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
(v) Parapet
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
42. Staircase/Exit Requirements.-
Minimum size of plots and road width.(1) The minimum size of plots and road width for different categories of building is given in Table 7.
sin'k
Bihar Building Bye-Laws
In the
3714-5024-12-14
-55-
Table - 7: Category wise size of plots
Category
Min. road width(m)
Min. size of plot in Sq. m.
Marriage Halls
12.20
1000
Cinema, Multiplex, Shopping Malls, Convention centers, Game centers,
18.30
2000
Social clubs and amenities
12.20
1000
Multi storey car parking
12.20
1000
Office buildings
12.20
300
Primary/Upper Primary school
12.20
2000
High School, Residential school
12.20
6000
+2 College / Junior college
12.20
4000
Degree College
12.20
6000
Technical educational institution
12.20
10000
Petrol pumps / Filling stations
12.20
500
Restaurant
12.20
500
LPG storages
12.20
500
Places of congregation
12.20
500
Public libraries
12.20
300
Conference hall
18.30
1000
Community hall
12.20
500
Nursing homes/polyclinics
12.20
300
Hotel (below three star)
12.20
2000
Hotel (three star and above)
18.30
2000
R&D Lab
18.30
1500
Group Housing
12.20
4000
Note: (i) In exceptional cases the Authority may consider revising the minimum size of plot with the approval of the Government.
(ii) The above (requirement) area of minimum size of the plot may be relaxed by 5% while sanctioning the plan.
(2) No high rise building (building with a height of 15 meters and above) shall be allowed on a plot size less than 800 sq. meters.
Minimum setbacks & Height for non-high rise buildings.-(1)The minimum setbacks and height of buildings permissible in a given size/plot for residential in non-high rising category shall be as per Table 8 and 9. The minimum setback for commercial and mercantile buildings shall be as per Table 10 and 11.
Table - 8: Minimum setbacks and height of residential buildings
Sno.
Average Depth of plot(In meters)
Building Height Upto G+2Maximum-10m
Building Height Upto G+3Maximum-12m
Building Height Upto G+4Maximum-15m
Minimum Front set back (m)
Minimum Rear Set back(m)
Minimum Front set back (m)
Minimum Rear Set back (m)
Minimum Front set back (m)
Minimum Rear Set back (m)
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
Bihar Building Bye-Laws
Laws
(b) 1-2-14 A00 b
V
-56~
1
Upto 10m
1.5
0.90
No construction shall be permitted
No construction shall be permitted
2
Exceeding 10m & upto 15 m
1.5
1.2
2.5
1.8
No construction shall be permitted
3
Exceeding 15m & upto 21 m
1.8
1.5
3.6
2.0
4.0
3.0
4
Exceeding 21m & upto 27 m
2.5
1.8
4.0
2.5
4.5
3.6
5
Exceeding 27m & upto 33m
3.0
2.5
4.0
3.0
5.0
4.0
6
Exceeding 33m & upto 39m
3.0
3.0
4.5
4.0
5.5
4.0
7
Exceeding 39m & upto 45m
4.0
4.0
5.0
4.0
6.0
4.0
8
More the 45m
4.0
4.0
6.0
4.0
6.0
4.5
Table 9.Minimum side set backs for residential buildings
Sl no.
Average Width of plot (In meters)
Building Height Upto G+2Maximum-10m
Building Height Upto G+3Maximum-12m
Building Height Upto G+4Maximum-15m
Minimum Side Set back(m)
Minimum Side Set back (m)
Minimum Side Set back (m)
Minimum Side Set back (m)
Minimum Side Set back (m)
Minimum Side Set back (m)
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
1
Upto 10m
NIL
NIL
No construction shall be permitted
No construction shall be permitted
2
Exceeding 10m & upto 15 m
0.75
0.75
1.5
1.5
No construction shall be permitted
3
Exceeding 15m & upto 21 m
1.0
1.0
1.5
1.5
2.0
2.0
4
Exceeding 21m & upto 27 m
1.5
1.5
2.0
2.0
2.5
2.5
5
Exceeding 27m & upto 33m
1.5
1.5
2.5
2.5
3.0
3.0
6
Exceeding 33m & upto 39m
2.0
2.0
3.0
3.0
3.66
3.66
7
Exceeding 39m & upto 45m
3.0
3.0
3.66
3.66
4.00
4.00
8
More the 45m
3.66
3.66
4.00
4.00
4.00
4.00
Table: 10 Minimum front and rear setback for commercial/mercantile buildings
Sl no.
Average Depth of plot (In meters)
Building Height up to 15 m
Minimum Front set back (m)
Minimum Rear Set back(m)
Bihar Building Bye-Laws
hely
(1)/(2)x + 1 = (1)/(4)
-57-
(i)
(ii)
(iii)
(iv)
1
Upto 10 m (height of the building shall be restricted to 10m)
4.5
2.0
2
Exceeding 10 m and up to 15 m
4.5
3.0
3
Exceeding 15m and up to 21 m
5.5
4.0
4
Exceeding 21 m and upto 27 m
6.0
4.0
5
Exceeding 27 m and upto 33 m
6.5
4.0
6
Exceeding 33 m and upto 39 m
7.0
4.5
7
Exceeding 39 m and upto 45 m
7.5
4.5
8
More than 45 m
8.0
4.5
Table 11Minimum side setbacks for commercial/mercantile buildings
Sl no.
Average Width of plot (In meters)
Building Height upto 15m
Minimum Left set back (m)
Minimum Right Set back(m)
(i)
(ii)
(iii)
(iv)
1
Upto 10 m (height of the building shall be restricted to 10 m)
Nil
Nil
2
Exceeding 10 m and upto to 15 m
2.0
2.0
3
Exceeding 15 m and upto 21 m
2.5
2.5
4
Exceeding 21 m and upto 27 m
3.0
3.0
5
Exceeding 27 m and upto 33 m
4.0
4.0
6
Exceeding 33 m and upto 39 m
4.0
4.0
7
Exceeding 39 m and upto 45 m
5.0
5.0
8
More than 45 m and upto 45 m
5.5
5.5
Table 12.Openspaces around industrial buildings
SINO.
Plot Size
Minimum Front set back (m)
Minimum Rear Set back (m)
Minimum Sides Set back (m)
(i)
(ii)
(iii)
(iv)
(v)
1
550 Sqm to 1000 Sqm.
9.0
4.5
4.5
2
1000 Sqm. to 5000 Sqm.
10.0
6.0
6.0
3
5000 Sqm. to 30000 Sqm.
12.0
9.0
9.0
4
Above 30000 Sqm.
15.0
12.0
10.0
Table 13.Minimum set back for industrial buildings constructed over plot size upto 550 sq m
Sl no.
Width of Plot
Minimum Front set back (m)
Minimum Rear Set back (m)
Minimum Sides Set back (m)
Bye-Laws
bye
39kDa/12.14
A/m/
√
-58
buy
(i)
(ii)
(iii)
(iv)
(v)
1
Upto 10 mtrs.
3.0
3.0
1.5
2
Above 10 mtrs. &upto 12 mtrs.
4.0
3.0
2.0
3
Above 12 mtrs. &upto 15 mtrs.
5.0
3.0
3.0
4
Above 15 mtrs. &upto 18 mtrs.
6.0
4.0
4.0
5
Above 18 mtrs.
6.0
4.5
4.5
Minimum setbacks for high rise buildings.-(1)For high-rise/ multi-storied buildings, the open spaces around the building unless or otherwise specified shall be as given in the Table 14.
Table -14Minimum exterior open spaces around the buildings for all type of high rise buildingsunless otherwise specified
SI.No.
Height of the Building Upto (m.)
Exterior open spaces to be left out on all sides in m.
(front setback)
Side and back
1
More than 15 and upto 18
6.5
4.5
2
more than 18 and upto 21
7.5
4.5
3
More than 21 and upto 24
8.0
5.0
4
More than 24 and upto 27
9
6
5
More than 27 and upto 30
10
7
6
More than 30 and upto 35
11
7
7
More than 35 and upto 40
12
8
8
More than 40 and upto 45
13
8
9
More than 45 and upto 50
14
9
10
More than 50
15
9
(2) In no case the minimum setbacks shall be less than those specified in Bye Law 37 for high rise buildings in the mentioned category.
(3) In case of multi storied buildings the exterior open space around a building shall be of hard surface capable of taking load of fire engine weighting up to 45 tonnes.
General Conditions for Setback.-(1)The minimum distance between two buildings will not be less than 1/3rd of the height of the taller building or 18m whichever is lower. However the minimum width of the internal road shall not be less than 4.5 meters.
Bihar Building Bye-Laws
In all cases, the width of such open space between the buildings on a plot shall not be less than the setback specified for the tallest building subject to a minimum of three meters within a plot.
(2) The setbacks/open spaces for other occupancies shall be as below;
A. Educational buildings - In case of educational buildings the open spaces around the building shall not be less than 6 meter. The front set back shall be 9 metres.
B. Institutional buildings - The open spaces around the building shall not be less than 6 m. The front setback shall be 9m.
C. Assembly buildings- The open space in front shall be not less than 12m and the other open spaces around the building shall not be less than 6m.
D. Malls and Multiplex— The front set back shall not be less than 12 m, the rear set back shall not be less than 7 m and the side set back shall not be less than 7m.
E. Commercial & Storage buildings - In case of plots with more than 1000 sq.mtr. area, the open spaces around the building shall not be less than 6.0m. The front setback shall be 9m. In all other cases it shall be as per Table 10.
F. Industrial buildings –The setbacks shall be as per Table 12 and 13.
G. Hazardous occupancies - the open spaces around the building shall not be less than 9 m. The front set back shall be 12m.
H. Slum Improvement-The setback norms shall not apply to slums taken up under an approved programme of the Government subject to the specific sanction of the Government.
I. IT, ITES Buildings-Abutting on 12 m R/W or more R/W the setback, height, number of floors and FAR shall be applicable as per commercial building in respect of corresponding road width.
(3) The setbacks shall be calculated on the basis of highest provision of setback mentioned either in the above table or mentioned in these Bye Laws.
(4) The setbacks are to be left after leaving the affected area of the plot/site, if any, for road widening.
(5) Where a site abuts more than one road, then the front setback should be insisted towards the bigger road width and for the remaining side or sides, Side and rear setback shall be insisted.
e-Laws
in P. 3216402/4.12.44.60/m/2
-60
(6) For Plots above 300 sq.m a minimum 1m wide continuous green planting strip in the periphery sides are required to be developed and maintained within the side or rear setback.
(7) For narrow plots having extent not more than 400 sq.m and where the length is 4 times of the width of the plot, the setbacks on sides may be compensated in front and rear setbacks so as to ensure that the overall aggregate setbacks are maintained in the site, subject to maintaining a minimum of side setback of 1m in case of buildings of height up to 10 m and minimum of 2m in case of buildings of height up to 12 m without exceeding overall permissible plinth area.
(8) The master plan/development plan/zonal plan shall also specify a building line for various areas. The setbacks shall accordingly be changed without reducing the minimum required setbacks under these bye laws.
Floor Area Ratio.-(1) The Floor Area Ratio (F.A.R) for buildings shall be decided on the basis of the road width on which the plot/site abuts as per Table 15 and 16.
Table - 15: Road width and FAR table for (OLD AREA).
Category
Road Width (in meter)
FAR
Floor
Maximum Height (in meter)
Conditions
Residential
Nonresidential
O-I
3.60 (12 ft.)
1.5
Nil
G+2
10
O-II
4.80 (16 ft.)
1.8
Nil
G+2
10
O-III
6.10 (20 ft.)
2.0
Nil
G+3,S+3
12
Parking shall be allowed on any floor.Under no circumstances the parking floors or provision for parking shall be used for any other purposes.Mezaninine floors or any floor partition shall be computed under FAR and counted as a floor.
O-IV
9.10 (30 ft.)
2.5
Nil
S+5
18
O-V
12.20 (40 ft.)
2.5
2.0
Maximum Height 24 meter
O-VI
18.30 (60 ft.) and above
2.5
2.5
No restriction on height and number of floors however it may be regulated by the master plan/development plan/zonal plan.
Table 16Road width and FAR table (NEW AREA)
Category
Road Width (in meter)
FAR
Floors
Maximum Height (in meter)
Conditions
Residential
Non residential
N-I
6.10 (20 ft.)
2.0
Nil
G+3, S+3
12
Parking shall be allowed on any floor. Under no circumstances
Bihar: Building Bye-Laws
(4). Building requirements:
The specified facilities for the buildings for handicapped persons shall be as follows:
(A). Approach at plinth level: Every building must have at least one entrance accessible to the handicapped and shall be indicated by proper signage.
Bihar Building Bye-Laws
-75-
Bihar Building Bye-Laws
This entrance shall be approached through a ramp together with stepped entry.
(B). Ramp Approach: Ramp shall be finished with non-slip material. Minimum width of ramp shall be 1800 mm. with maximum gradient1:12, length of ramp shall not exceed 9 meter having 800 mm high hand rail on both sides extending 300mm beyond top and bottom of the ramp. Minimum gap from the adjacent wall to the hand rail shall be 50mm.
(C). Stepped Approach: For stepped approach width of tread shall not be less than 300 mm. and maximum riser shall be 150 mm. Provision of 800 mm. high hand rail on both sides of the stepped approach similar to the ramp approach shall be made.
(D). Exit/Entrance Door: Minimum clear opening of the entrance door shall be 900mm and it shall not be provided with a step that obstructs the passage of a wheel chair user. Threshold shall not be raised more than 12 mm.
(E). Entrance Landing: Entrance landing shall be provided adjacent to ramp with the minimum dimension 1800mm X 2000 mm. The entrance landing that adjoins the top end of a slope shall be provided with floor materials to attract the attention of visually impaired persons (limited to colored floor material whose color and brightness is conspicuously different from that of the surrounding floor material or the material that emits different sound to guide visually impaired persons hereinafter referred to as "guiding floor material"). Finishes shall have a non-slip surface with a texture traversable by a wheel chair. Curbs wherever provided must blend to a common level.
(F). Corridor connecting the entrance/exit for the handicapped: The corridor connecting the entrance/exit for handicapped leading directly outdoors to a place where information concerning the overall use of the specified building can be provided to visually impaired persons either by a person or by signs, shall be provided as follows:
i. Guiding floor materials, shall be provided or devices that emit sound to guide visually impaired persons,
ii. The minimum width shall be 1250 mm.
iii. In case there is a difference of level, slope ways shall be provided with a slope of 1:12
iv. Hand rails shall be provided for ramps/slope ways at a height of 800mm.
(5) Stair ways: One of the stairways near the entrance/exit for the handicapped shall have the following provisions:
76-
-77-
(A). The minimum width shall be 1350 mm.
(B). Height of the riser shall not be more than 150mm and width of the tread300mm. The steps shall not have abrupt (square) nosing.
(C). Maximum number of risers on a flight shall be limited to 12.
(D). Hand rails shall be provided on both sides and shall extend 30mm on the top and bottom of each flight of steps.
Lifts: Wherever lift is required as per bye-laws, provision of at least one lift shall be made for the wheel chair user with the following cage dimensions of lift recommended for passenger lift of 13 persons capacity by Bureau of Indian Standards.
Clear internal depth: 1100mm
Clear internal width: 2000mm.
Entrance door width: 900 mm.
(A). A handrail not less than 600 mm. long at 1000mm. above floor level shall be fixed adjacent to the control panel.
(B). The lift lobby shall be of an inside measurement of 1800 mm x 1800mm or more.
(C). The time of an automatically closing door shall be minimum 5 seconds and the closing speed should not exceed 0.25 meter/sec.
(D). The interior of the cage shall be provided with a device that audibly indicates the floor the cage has reached and indicates that the door of the cage for entrance/exit is either open or closed.
(E). The control panel shall have marking in Braille to help visually impaired.
(7) Toilets: One special Water Closet, in a set of toilets shall be provided for the use of handicapped with essential provision of washbasin near the entrance for the handicapped.
(A). The minimum size shall be 1500 × 1750 mm.
(B). Minimum clear opening of the door shall be 900mm and the door shall swing out.
(C). Suitable arrangement of vertical/horizontal handrails with 50mmclearance from wall shall be made in the toilet.
(D). The Water Closet seat shall be 50mm from the floor.
(8) Drinking Water: Suitable provision of drinking water shall be made for handicapped near the special toilet provided for them.
(9) Designing for Children: In a building meant for the predominant use of the children, it is necessary to suitably alter the height of the handrail and other fittings and fixtures.
Bihar Building Bye-Laws
Rainwater harvesting system.-Provision of rainwater harvesting shall be mandatory for allsizes of plots.-The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area. Percolation Pits shall be filled with small pebbles or brick jali or river sand and covered with perforated concrete slabs. Apart from this, the following requirements are optional and may be provided depending on site conditions.
(A). Terrace Water Collection: The terrace shall be connected to a sump or the well through a filtering tank by PVC pipe. A valve system shall be incorporated to enable the first part of the rainwater collected to be discharged out or to the soil if it is dirty. A filtering tank measuring 0.36 Sq. m. can be constructed near the sump. The tank can be divided by a perforated slab and one part should be filled by small pebbles and other by brick jali. The bottom portion of the tank should have aslope to avoid stagnation of water.
(B). Open Ground: Where there is open ground, a portion of topsoil shall be removed and replaced with river sand to allow slow percolation of rain water. Any other method proved to be effective in conservation and harvesting of rainwater may be adopted in each and every construction taken up.
Signs and outdoor display structures.-Signs and outdoor display structures shall be governed by therelevant provisions of the area where no specific guideline for the above structures is framed; the Authority shall prescribe the guidelines with approval of Government.
ICT Landing Points.-Every multi storied building complex shall have provision for Information and Communication Technology (ICT) landing point in the form of a room near the main entrance gate of dimension not less than 3 m x 4 m. and having 3 m. clear height. The room shall have two fire proofs doors of 1.2 m. width opening outwards along with adequate ventilation in the form of windows/ ventilators. Such room shall not be counted in coverage and FAR calculations.
Builder to register an association.- The builder shall cause to register an Association of apartment owners as required under The Bihar Apartment Ownership Act 2006, before occupancy certificate for 50% or more of the floor area is given.
The Builder shall submit a copy of the agreement it has entered into with the apartment owners' society. This agreement shall contain the terms of maintenance of public utilities.
Reference to the standards.-The following standards shall be referred while preparing the design of the building :
[Illegible]
Bihar Building Bye-Laws
(a) The standards relating to water and sanitation requirements for various occupancies and uses, shall be referred to as per section-1 of part-9 of NBC of India, 2005 group-5,
(b) Construction of energy efficient building shall be referred to Energy Conservation Building Code, 2007
(c) Guidelines for installation of solar water heating system shall be referred to as Annexure-II.
56. Life Safety.-
The building design shall comply to the provisions of life safety as mentioned in National Building Code 2005(Group-1 Part-IV Fire and Life Safety-4) wherever applicable and the applicant shall reflect compliance of these provisions in completion certificate.
(3) Parking:
For parking of vehicles of handicapped people the following provisions shall be made:
(A). Surface parking for two car spaces shall be provided near entrance for the physically handicapped persons with maximum travel distance of 30 meter from building entrance.
(B). The width of parking bay shall be minimum 3.6 meter.
(C). The information stating that the space is reserved for handicapped persons shall be conspicuously displayed.
(D). Guiding floor materials shall be provided or a device which guides visually impaired persons with audible signals or other devices which serves the same purpose shall be provided.
(iii) Fire Escape or external stairs-
(a) Fire escapes shall not be taken into account in calculating the evacuation time of a building.
(b) All fire escapes shall be directly connected to the ground.
(c) Entrance to fire escape shall be separate and remote from the internal staircase.
(d) The route of fire escape shall be free from obstructions at all times except a doorway leading to the fire escape which shall have the required fire resistance.
(e) Fire escape shall be constructed of non-combustible materials.
(f) Fire escape stairs shall have straight flight not less than 75 cm. wide with 20cm. treads and riser not more than 19 cm. The number of riser shall be limited to 16 per flight.
Bihar Building Bye-Laws
(g) Handrails shall be of a height not less than 100 cm.
(iv) Spiral Stair (Fire escape)- The use of spiral staircase shall be limited to low occupant load and to a building of height 9m. unless they are connected to platforms, such as balconies and terraces to allow escapes to pause. A spiral fire escape shall be not less than 150cm. in diameter and shall be designed to give adequate headroom.
(v) Ramps-
(a) Ramps with a slope of not more that 1:10 may be substituted or for and shall comply with all the requirements of required stairway as to enclosure, capacity and limiting dimensions; large slopes shall be provided for special uses but in no case greater than 1:8. The ramp with a slope between 1:10 to 1:8 shall be allowed only upto height of 2.4 Meter.
(b) For any height more than 2.4 Meter the slope of ramp shall not exceed 1:20.
(c) For all slops exceeding 1:10 and where the use is such as to involve danger of slipping the ramp shall be surfaced with approved non-stipping materials.
(d) Ramps with slope upto 1:20 shall be counted towards the covered area for calculating the fees.
(e) The ramps shall not be within required minimum setbacks.
(f) The ramps can be permitted in Basement, Semi-basement, within the minimum set back provided it should not obstruct the movement of fire-engine.
(g) Ramps for Hospital- In case of Hospital, ramp shall not be greater than 1:20.
Interior open space.-(1) At least one side of all the rooms intended for human habitation, if such room does not abut on the front or the rear or the side setbacks, shall abut on an interior open space whose minimum dimension shall be 3 meters X 3 meters in cases of buildings up to a height of 12 meters. In cases where the height of the building is more than 12 meters, the width of the interior open space shall be increased at the rate of one meter for every additional 3 (three) meters height. This provision shall be applicable to all categories of buildings, namely, residential, group housing, commercial, institutional, administrative, assembly.
(2) For ventilating the spaces for water closets and bathrooms ventilation shafts shall be provided with size as provided under clause - 8.2.5(b), Group 1, Part-3 of National Building Code of India -2005 (Published by Bureau of Indian Standards) as bye laws for ventilation shaft.
Height exemption of a building.-The following appurtenant structures shall not be included in the height of the building.
(A). Roof tanks and their supports (with support height not exceeding 1 m.)
Bihar Building Bye-Laws
(B). Ventilating, air conditioning, lift rooms and similar service equipment.
(C). Stair cover (mumty) not exceeding 3.0 m. in height and
(D). Chimneys, parapet walls and architectural features not exceeding 1.2m. in height.
Exemption in Open space.-(1) Every open space provided either in the interior or exterior in respect of any building shall be kept free from any erection thereon and shall be open to the sky and no cornice, roof, or weather shade of more than 0.75 m. in width shall overhang or project over such open space.
(2) A portico of up to 2.5 m, width and 4.6 m, length with a minimum height of 2.4m from the plinth level may be permitted within the side setback. A garage is permissible at the rear end of side open space provided no openings are located on the side and rear boundary. Access to the top of the portico/garage should not affect the privacy of the neighboring plot.
(3) The portico provided as above should not rest on the boundary wall and should be open to provide through access to the rear. In case the Portico is not a cantilevered one and supported by pillars the area shall be included in the FAR.
(4) No projected balcony shall be allowed on setback less than 1.5 meters. Projected balcony shall be allowed with a width of 0.6 meters where the setback is between 1.5 meters to 2.5 meters. For setback more than 2.5 meters projected balcony shall be allowed with a width of 0.9 meters. Projected balcony shall only be allowed on the second floor and above floors. It may be allowed on first floor subject to condition that it shall not obstruct the clear vehicular and pedestrian movement around the building including movement of fire tender. 50% of the area on the projected balcony shall be taken into account for calculation of floor area,
Mezzanine.-Mezzanine floor may be permitted above any floor in all types of buildings up to an extent of one-third of the actual covered area of that floor. All Mezzanine floors shall be counted toward FAR calculation, except the mezzanine floor over the ground floor.
The mezzanine floor shall have a minimum height of 2.2 m. The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 Sq meter. The aggregate area of such mezzanine floor in a building shall in no case exceed one-third the plinth area of the building.
Basement Cellar.-(1) Basements/cellars shall not be permitted in low lying area and without adequate drainage facilities to ensure drainage from the basement. Basement shall not be allowed in flood prone areas.
(2) Construction of basements/cellars may be allowed by the Authority in accordance with the provisions contained in the development plan applicable to the concerned area.
(3) The basements/cellars shall only be put to the following uses;
Bihar Building Bye-Laws
-72+
(A). Storage of household or other non-combustible material
(B). Strong room, bank cellars etc;
(C). Installation of air-conditioning equipments and other machines used for service and utilities of building;
(D). Parking places.
(4) Individual residential and small commercial buildings, plot size minimum 500 Sq. Meter may have one basement. However maximum two basements/cellars may be permitted to be constructed for other buildings leaving the prescribed set back/open space applicable to thebuilding.Further, in case of apartment/group housing/commercial/corporate & IT/ITES buildings the basements may be allowed to be constructed under the entire plot area leaving 3 meter space from the boundary of the premises subject to the following;
(i) In all such cases the owners have to indemnify the Authority against any damage caused by her/him/them to the adjacent property. (Form-XV).
(ii) The portion of the basement projecting out of the building line shall flush with the ground.
(5) The basements shall be used exclusively for parking/ services/storage.
(6) The basement shall fulfill the following requirements:
(A). Every basement shall be in every part at least 2.5 m. in height from the floor to the soffit of the roof slab or ceiling;
(B). Adequate ventilation shall be provided for the basement. The standard of ventilation shall be the same as required by the particular occupancy according to bye laws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans (one exhaust fan for 50 Sq.m. of basement area), air conditioning system etc;
(C). The minimum height of the ceiling of upper basement shall be 1.20 m and the maximum, 1.5 m above the average surrounding ground level;
(D). Adequate arrangement shall be made, so that surface drainagedoes not enter the basement;
(E). The walls and floors of the basement shall be water-tight and be so designed that the effect of the surrounding soil and moisture, if any, are taken in to account in design and adequate damp proofing treatment is given;
(F). The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors shall be provided. Where the staircase is continuous in the case of buildings
-73-
served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floor.
(G). Open ramps shall be permitted if they are constructed within the building line subject to provision of (D) above.
(H). The ramp providing access to basement to be used for parking shall have a gradient not steeper than 1:10 and this shall not obstruct the clear vehicular and pedestrian movement around the building including movement of fire tender (6 meter).
Provision of Lift.-(1) Lift shall be provided for buildings above 15 m. height in case of apartments, group housing, commercial, institutional and office buildings.
(2) The Number and capacity of lift shall be provided as specified in the National Building Code.
(3) Lift shall be provided at the rate of one lift for twenty dwelling units, or part thereof for residential buildings and at the rate of one lift per one thousand Sq.m. or part thereof of built-up area per floor for non-residential buildings. Built-up area on ground floor and two upper floors shall be excluded in computing the above requirement.
(4) Notwithstanding anything contained in these bye laws in case of building with 21 m. or more in height, at least two lifts shall be provided.
(5) All lifts shall be inspected at least once a year by the agency designated by the Authority. The Authority can also outsource the inspection of lifts.
Heritage Zone.-(1) The Authority may notify the Heritage Zones in consultation with the Archaeological Survey of India, State Department of Art Culture and Youth and the Art Commission.
(2) Conservation of Heritage Buildings, Heritage Precincts and Natural features: Conservation of buildings, artifacts, structures, areas and precincts of historic and /or aesthetic and/or architectural and /or cultural significance (Heritage buildings and heritage precincts) and/or natural features of environmental significance shall be taken up by the Authority in accordance with the relevant provisions in-force and those framed from time to time.
Barrier free access for the physically challenged person.-Barrier free environment is one, which enables people with disabilities to move about safely and freely and to use all facilities within the built environment. The goal of barrier free design is to provide an environment that supports the independent functioning of individuals so that they can get into and participate in all activities without assistance.
The main purpose is to integrate disabled and elderly persons fully into the society. In view of the above, the Government of India has enacted the Disabilities Act, 1955.
Bihar Building Bye-Laws
g₁S₁w₁/4h₂w₂
-74-
Section 44, 45 and 46 of the said Act stipulates that the appropriate Governments, local authorities to ensure provisions of barrier free facilities in all new Government buildings and public utilities roads and transport. Also, in 1996 Government of India enacted another person with Disabilities (Equal Opportunity, Protection of Rights and Full Participation) Act for the Barrier Free Environment for differently abled persons.
(1) Site development:
Level of the roads, access paths and parking areas shall be described in the plan along with specification of the materials.