Lighting systems and equipment shall comply with the mandatory provisions of clause 7.2 and the prescriptive criteria of clause 7.3 and clause 7.3.4. The lighting requirements in this section shall apply to:
(a) Interior spaces of buildings
(b) Exterior building features, including facades, illuminated roofs, architectural features, entrances, exits, loading docks, and illuminated canopies.
(c) Exterior building grounds lighting that is provided through the building's electrical service
Exceptions to clause 7.1:
a) Emergency lighting that is automatically off during normal building operation and is powered by battery generator, or other alternate power source
b) Lighting in dwelling units
7.2Mandatory Requirements
7.2.1 Lighting Control
7.2.1.1 Automatic Lighting Shutoff
2 2Interior lighting systems in buildings larger than 500m (5,000 ft ) shall be equipped with an automatic control device. Within these buildings, all office 2 2areas less than 30 m (300ft )enclosed by walls or ceiling-height partitions, all meeting and conference rooms, all school classrooms, and all storage spaces shall be equipped with occupancy sensors. For other spaces, this automatic control device shall function on either:
(a) Ascheduled basis at specific programmed times. An independent program 2 2schedule shall be provided for areas of no more than 2500 m (25000 ft ) and not more than one floor; or,
(b) Occupancy sensors that shall turn the lighting off within 10 minutes of an occupant leaving the space. Light fixtures controlled by occupancy sensors shall have a wall-mounted, manual switch capable of turning off lights when the space is occupied.
Exception to clause 7.2.1.1: Lighting systems designed for 24 hour use.
Lighting
7.2.1.2 Space Control
Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall:
(a) Control a maximum of 2 5 0 m 2 2(2500 ft ) for a space less than or equal to 2 2 21000 m (10000 ft ), and a maximum of 1000 m (10000 ft2) for a space 2 2greater than 1000 m (10000 ft )
(b) Be capable of overriding the shutoff control required in clause 7.2.1.1 for no more than 2 hours.
(c) Be readily accessible and located so the occupant can see the control.
Exception to clause 7.2.1.2 (c): The required control device may be remotely installed if required for reasons of safety or security. A remotely located device shall have a pilot light indicator as part of or next to the control device and shall be clearly labeled to identify the controlled lighting.
7.2.1.3: Control in Day lighted areas
2 2Luminaries in day lighted areas greater than 25m (250 ft ) shall be equipped with either a manual or automatic control device that:
(a) Is capable of reducing the light output of the luminaries in the day lighted areas by at least 50%, and
(b) Controls only the luminaries located entirely within the day lighted area.
7.2.1.4: Exterior Lighting Control
Lighting for all exterior applications not exempted in clause 7.3.4 shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required.
7.2.1.5 Additional control
The following lighting applications shall be equipped with a control device to control such lighting independently of general lighting:
2a) Display/Accent Lighting: Display or accent lighting greater than 300m 2(3000 ft ) area shall have a separate control device
b) Case Lighting: Lighting in cases used for display purposes greater than 2 2300m (3000 ft ) area shall be equipped with a separate control device.
c) Hotel and Motel Guest Room Lighting: Hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that-
Lighting
controls all permanently installed luminaries and switched receptacles.
(d) Task Lighting: Supplemental task lighting including permanently installed under shelf or under cabinet lighting shall have a control device integral to the luminaries or be controlled by a wall-mounted control device provided the control device compiles with clause 7.2.1.2 ( c)
(e) Non-visual Lighting: Lighting for non-visual applications, such as plant growth and food-warming, shall be equipped with a separate control device.
(f) Demonstration Lighting: Lighting equipment that is for sale or for demonstrations in lighting education shall be equipped with a separate control device accessible only to authorized personnel.
7.2.2 Signage/ Advertising Signage
Internally-illuminated exit signs shall not exceed 5W/sft. The lighting power density in case of signage/ advertisement signage should not exceed 5 W/sft for internally illuminated signage and 2.5 W/sft for externally illuminated signage. They all shall use LEDs
7.2.3 Exterior Building Grounds Lighting
Lighting for exterior building grounds luminaries which operate at greater than 100W shall contain lamps having a minimum efficacy of 60 lm/W, LED type unless the luminaries is controlled by a motion sensor or exempt under clause 7.1.
7.3Perspective Requirements
7.3.1 Interior Lighting Power
The installed interior lighting power for a building separately metered or permitted portion of a building shall be calculated in accordance with clause 7.3.4 and shall not exceed the interior lighting power allowance determined in accordance with either clause 7.3.2 or clause 7.3.3. Tradeoffs of interior lighting power allowance among portions of the building for which a different method of calculation has been used are not permitted.
Exception to clause 7.3 : The following lighting equipment and applications shall not be considered when determining the interior lighting power allowance, nor shall the wattage for such lighting be included in the installed interior lighting power. However, any such lighting shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device.
(a) Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments
Lighting
(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.
(c) Lighting specifically designed for medical or dental procedures and lighting integral to medical equipment.
(d) Lighting integral to food warming and food preparation equipment
(e) Lighting for plant growth or maintenance
(f) Lighting in spaces specifically designed for use by the visually impaired.
(g) Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions
(h) Lighting in interior spaces that have been specifically designated as a registered interior historic landmark.
(i) Exit signs
(j) Lighting that is for sale or lighting educational demonstration systems
(k) Lighting for theatrical purposes, including performance, stage, and film or video production
(l) Athletic playing areas with permanent facilities for television broadcasting.
7.3.2 Building Area Method
Determination of interior lighting power allowance (watts) by the building area method shall be in accordance with the following:
(a) Determine the allowed lighting power density from Table 7.1 for each appropriate building area type.
(b) Calculate the gross lighted floor area for each building area type.
( c) The interior lighting power allowance is the sum of the products of the gross lighted floor area of each building area times the allowed lighting power density for that building area types.
Table 7.1Interior Lighting Power-Building Area Method (LPD- Lighting Power Density)
Building Area Type
LPD (W/m 2)
Building Area Type
LPD (W/m2)
Automotive facility
9.7
Multifamily Residential
7.5
Convention Centre
12.9
Museum
11.8
Dining: Bar Lounge/Leisure
14.0
Office
10.8
Dining: Cafeteria/Fast Food
15.1
Parking Garage
3.2
Lighting
Dining: Family
17.2
Performing Arts Theater
17.2
Dormitory/Hostel
10.8
Police/Fire station
10.8
Gymnasium
11.8
Post Office/Town Hall
11.8
Healthcare-clinic
10.8
Religious Building
14.0
Hospital/Health Care
12.9
Retail/Mall
16.1
Hotel
10.8
School/University
14.0
Library
14.0
Sports Arena
11.8
Manufacturing facility
14.0
Transportation
10.8
Motel
10.8
Warehouse
8.6
Motion Picture Theater
12.9
Workshop
15.1
In cases where both a general building area type and a specific building area type are listed, the specific building area type shall apply.
7.3.3 Space Function Method
Determination of interior lighting power allowance (watts) by the space function method shall be in accordance with the following:
a) Determine the appropriate building type from Table 7.2 and the allowed lighting power density.
b) For each space enclosed by partitions 80% or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Include the floor area of balconies or other projections. Retail spaces do not have to comply with the 80% partition height requirements.
a) The interior lighting power allowance is the sum of the lighting power allowances for all spaces. The lighting power allowance for a space is the product of the gross lighted floor area of the space times the allowed lighting power density for that space.
Lighting
Table 7.2Interior Lighting Power-Space Function Method
Space Function
LPD (W/m 2)
Space Function
LPD (W/m2)
Office-enclosed
11.8
For Reading Area
12.9
Office-open plan
11.8
Hospital
Conference/Meeting/Multipurpose
14.0
For Emergency
29.1
Classroom/Lecture/Training
15.1
For Recovery
8.6
Lobby*
14.0
For Nurse Station
10.8
For Hotel
11.8
For Exam Treatment
16.1
For Performing Arts Theater
35.5
For Pharmacy
12.9
For Motion Picture Theater
11.8
For Patient Room
7.5
Audience/Seating Area*
9.7
For Operating Room
23.7
For Gymnasium
4.3
For Nursery
6.5
For Convention Center
7.5
For Medical supply
15.1
For Religious Buildings
18.3
For Physical Therapy
9.7
For sports Arena
4.3
For Radiology
4.3
For Performing Arts Theater
28.0
For Laundry - Washing
6.5
For Motion Picture Theatre
12.9
Automotive - Service Repair
7.5
7.3.4 Installed Interior Lighting Power
The installed interior lighting power calculated for compliance with 7.3 shall include all power used by the luminaires, including lamps, ballasts, current regulators, and control devices except as specifically exempted in 7.1.
Exception to clause 7.3.4: If two or more independently operation lighting systems in a space are controlled to prevent simultaneous user operation, the interior lighting power shall be based solely on the lighting system with the highest power.
7.3.4.1 Luminaire Wattage
Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the following:
(a) The wattage of incandescent luminaries with medium base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the luminaires
(b) The wattage of luminaries containing permanently installed ballasts shall be the operating input wattage of the specified lamp/ballast combination based on values from manufacturers' catalogs or values from independent testing laboratory reports
(c) The wattage of all other miscellaneous luminaire types not described in (a) or (b) shall be the specified wattage of the luminaires
(d) The wattage of lighting track, plug-in bus way, and flexible-lighting systems that allow the addition and/ or relocation of luminaires without altering the wiring of the system shall be the larger of the specified wattage of the luminaires included in the system or 135W/m(45W/ft).Systems with integral overload protection, such as fuses or circuit breakers, shall be rated at 100% of the maximum rated load of the limiting device
7.3.5 Exterior Lighting Power
For building exterior lighting applications specified in Table 7.3, the connected lighting power shall not exceed the specified lighting power limits specified for each of these applications. Trade-offs between applications is not permitted. Exterior lighting for all other applications (except those included in the Exceptions to 7.3.4) shall comply with the requirements of 7.2.3.
Lighting
Table 7.3Exterior Building lighting Power
Exterior Lighting Applications
Power Limits
Building entrance (with canopy)
13W/m² (1.3W/ft²) of canopied area
Building entrance (without canopy)
90W/m² (30 W/lin f) of the door width
Building exit
60W/m² (20 W/lin f) of the door width
Building facades
2 W/m² (0.2 W/ft²) of vertical façade area
Exception to 7.3.5: Lighting used for the following exterior application is exempt when equipped with an independent control device:
(a) Specialized signal, directional, and marker lighting associated with transportation
(b) Lighting used to highlight features of public monuments and registered historic landmark structures or buildings
(c) Lighting that is specifically designated as required by a health or life safety statute, ordinance, or regulation
7.3.6 Lighting Type and Efficiency
All fluorescent tube lights shall be of energy efficient or BEE star rated as specified in clause 3.1.4.6.No in candescent bulb shall be used for ordinary lighting applications.