15.9.1. Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupant, in case of fire or other emergency as per clauses 4.2 to 4.4.2.5 of Part 4 of the National Building Code of India, 2016/this part of regulations.
15.9.2 General Requirements:
The following general requirements shall apply to exits.—
(a) Unless otherwise specified, lifts, escalators, moving walks and revolving doors shall not be considered as exits and shall not constitute any part of the required exit.
(b) Every exit, exit passageway and exit discharge shall be continuously maintained free of all obstructions or impediments to full use in the case of fire or other emergency.
(c) Every building having human occupancy shall be provided with exits sufficient to permit safe egress of occupants in case of fire or other emergency.
(d) In every building or structure, exits shall comply with the minimum requirements of this Part of regulations, except those not accessible for general public use.
(e) No building shall be so altered as to reduce the number, width or protection of exits to less than that required.
(f) For non-naturally ventilated areas, fire doors with 120 minutes fire resistance rating shall be provided and particularly at the entrance to lift lobby and stair well where a ‗funnel or flue effect‘ may be created, inducing an upward spread of fire, to prevent spread of fire and smoke.
(g) Exits shall be so arranged that they may be reached without passing through another occupied unit/passage in others control, if they pose challenge or restriction in means of egress.
(h) Doors in exits shall open in the direction of exit. In case of Group D Assembly Buildings and Group C Institutional Buildings (Sub division C-1 Hospitals and Sanatoria), exit door shall not open immediately upon a flight of stair and all such entries to the stair shall be through a landing, so that such doors do not impede movement of people descending from a higher floor when fully opened (see Sketch No. 8A).While for other occupancies, such doors shall not reduce the pathway in the landing by more than half the width of such staircase (see Sketch No. 8B). Overhead or sliding doors shall not be installed.
(i) At least half of the required exit stairs from upper floors (rounded to the next higher number) shall discharge directly to the exterior or through exit passageways.
120–
(j) Unless otherwise specified, all the exits and exit passageways to exit discharge shall have a clear ceiling height of at least 2.4 meter. However, the height of exit door shall be at least 2.0 meter (see Sketch No. 9.)
(k) Where changes in elevation of more than 300 mm are encountered in the exits, ramps or sloped surfaces shall be used with handrails and floor finish materials that contrast with the adjacent finish materials.
(l) The capacity of the means of egress required from any storey of the building shall not be reduced along the path of egress travel until arrival to the exit discharge.
(m) The lifts, escalators, moving walks, turnstiles and revolving doors shall not be considered in determining the required capacity of means of egress for the individual floors or the building.
(n) Turnstiles or similar devices that restrict travel to one direction or that are used to restrict unauthorized entry shall not be so placed as to obstruct any required means of egress. Alternative door openings of required exit width shall be available within 3 meter of such devices, if installed.
(o) Suitable means shall be provided so that all access controlled exit doors, turnstiles, boom barriers and other such exits shall automatically operate to open mode during emergencies like fire, smoke, acts of terrorism, etc., so that people can safely and quickly egress into safe areas outside. If required, a master controlling device may be installed at a strategic location to achieve this.
(p) Penetrations into and openings through an exit are prohibited except those necessary like for the fire protection piping, ducts for pressurization and similar life safety services. Such openings as well as vertical passage of shaft through floors shall be protected by passive systems.
(q) Walking surfaces in exit access shall comply with the following requirements for smooth exit:
(i) Walking surfaces shall be nominally levelled.
(ii) The slope of walking surface in the direction of travel shall not exceed 1 in 20 unless the ramp requirements are met.
(iii) Slope perpendicular to the direction of travel shall not exceed 1 in 48.
(iv) Walking surfaces shall be slip resistant along the entire path of travel.
15.9.3. Number of Exits: The minimum required number of exits in a building shall be determined based on occupant load (see Table XXI as specified in regulation 15.8.1) and width required per person (see Table XXII as specified in regulation 15.9.5) as appropriate to the type of exit for respective occupancies, subject to complying with maximum travel distance requirement (see Table XXIII as specified in regulation 15.9.6).