5.1 Fire Extinguishers/Fixed Firefighting Installations
5.1.1 All buildings depending upon the occupancy use and height should be protected by fire extinguishers, hose reels, wet riser, down-comer, yard hydrants, automatic sprinkler installation, deluge system, high/medium velocity water spray, foam, water mist systems, gaseous or dry powder system, manual/automatic fire alarm system, etc, in accordance with the provisions of various clauses given below, as applicable:
a)These fire extinguishing equipment and their installation should be in accordance with accepted standards [F(17)]. The extinguishers should be mounted at a convenient height to enable its quick access and efficient use by all in the event of a fire incidence. The requirements of fire extinguishers/yard hydrant systems/wet riser/down-comer installation, etc, should be as specified inTable 7A to Table 7J. See also Table 7K and Table 7M for guidance, on base calculation for capacity of water storage tanks and fire pumps. The requirements regarding size of mains/risers should be as given in Table 8. The typical arrangements of down-comer and wet riser installations, as also the pumping system are shown in Fig. 15, Fig. 16 and Fig. 17.The wet riser should be designed for zonal distribution ensuring that unduly high pressures are not developed in risers and hose-pipes.
b) First-aid firefighting appliances should be provided and installed in accordance with good practice [F(18)]. The firefighting equipment and accessories to be installed in buildings for use in firefighting should also be in accordance with the accepted standard [F(17)] and should be maintained periodically so as to ensure their perfect serviceability at all times.
c) Valves in fixed firefighting installations should have supervisory switch with its signalling to fire alarm panel or to have chain(s), pad lock(s), label, and tamper-proof security tag(s) with serial number to prevent tampering/unauthorized operation. These valves should be kept in their intended open' position.
d) In addition to wet riser or down-comer, first-aid hose reels should be installed in buildings (where required underTable 7A to Table 7J) on all the floors, in accordance with accepted standard [F(19)]. The first-aid hose reel should be connected directly to the riser/down-comer main and diameter of the hose reel should not be less than 19 mm.
e) Wet risers should be interconnected at terrace level to form a ring and cut-off should be provided for each connection to enable repair/ maintenance without affecting rest of the system.