| NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. | NS = Not Suitable S = Suitable NOTES 1Wet sprinklers are acceptable for all areas where pre-action sprinklers or closed water mist is suitable. 2DG rooms should be protected with total flooding open nozzles where water mist is being deployed. 3Spray system should be supplemented with suitable foam, if ignitable liquids or water miscible liquids are involved. 4Water mist system should be selected based on 3rdparty independent test carried out for the specific application, flow rate, density, etc. The products in terms of functionality and the performance should be based on actual test results and certifications, and should NOT be prescriptive. 5Water mist solution selected, total flooding with sprinklers, total flooding with open nozzles, wet system, pre-action system should comply based on actual test results, and certifications. |