A building should be designed to keep occupants comfortable. This means providing temperature, air motion and relative humidity within acceptable range for a thermally comfortable condition. In a carefully designed building, the walls, roofs, windows and interior surfaces alone can maintain comfortable interior temperatures for a large part of the year; especially for moderate climate zones.
The desired air temperatures can often be achieved by passive design strategies (a combination of building form, orientation, shading and materials), but controlling humidity, achieved by mechanical systems.
Thus, although passive measures will improve thermal comfort, air-conditioning may still be required for maintaining comfort conditions through the year.
Introduction to HVAC
Heating, Ventilation and Air Conditioning (HVAC) systems are used to heat or cool buildings to maintain indoor thermal comfort conditions that are acceptable to the human body.
Given the predominantly hot climate in India, coupled with increasing economic prosperity and aspirations, the energy demand for space cooling is rising rapidly in India. HVAC system account for nearly 40 percent of the energy used by commercial buildings in India.
The design as well as efficiency of such systems could further impact the energy consumption of
buildings. The process of optimization must begin with load calculation, and include system design, system selection and installation, commissioning, and ultimately – operations & maintenance. Innovative low-energy comfort systems are highly recommended for augmenting energy savings.
The best HVAC design considers all the interrelated building systems while addressing indoor air quality, thermal comfort, energy consumption, and environmental benefits. Optimizing both the design and the benefits requires that the architect and mechanical system designer address these issues early in the schematic design phase and continually revise subsequent decisions throughout the remaining design process. It is also essential that a process be implemented to monitor proper installation and operation of the HVAC system throughout construction.
Installing a HVAC system can be a significant capital cost to a project, especially for large commercial buildings. A poorly designed HVAC system can easily nullify the benefits of an energy-conserving building design.
In addition to providing heating and cooling, HVAC systems also provide ventilation. This is especially important where air conditioned buildings tend to be sealed. Fresh air from outside is required to flush out the indoor pollutants and odors. This is important for the health, productivity and comfort of occupants.
Chapter 5Comfort Systems & Controls
Comfort Systems & Controls
The second step in achieving energy efficiency is to use efficient cooling/heating equipment to provide thermally comfortable environment to occupants. Beyond equipment efficiency, the interactions of the overall system with all its components and their control mechanism is an important factor in achieving energy reduction. Low energy comfort systems that are climate appropriate can further help in improving energy efficiency.
MANDATORY
PRESCRIPTIVE
VENTILATION
MINIMUM SPACE CONDITIONING EQUIPMENT EFFICIENCIES
PUMPS
COOLING TOWERS
ECONOMIZERS
TOTAL SYSTEM EFFICIENCY - ALTERNATIVE COMPLIANCE APPROACH
CONTROLS
VARIABLE FLOW HYDRONIC SYSTEMS
LOW ENERGY COMFORT SYSTEM
ADDITIONAL CONTROLS FOR ECBC+ AND SuperECBC BUILDINGS
ENERGY RECOVERY
ADDITIONAL CONTROLS FOR SuperECBC BUILDINGS
PIPING AND DUCTWORK
SYSTEM BALANCING
SERVICE HOT WATER HEATING
5.COMFORT Systems & Controls
Environmental concern
The electricity used by the HVAC systems in buildings are supplied from power plants that burn fossil fuels like coal. This is responsible for greenhouse gas emissions which is globally known to cause climate change. Such emissions are attributed as indirect emissions to buildings since the source of emissions is at the power plant and not at the point of use. Energy efficient HVAC systems will use less electricity over its
operational lifetime reducing the indirect emissions from buildings.
Apart from the issue of energy use, the use of refrigerants in the HVAC systems is responsible for ozone layer depletion. Most of the refrigerants are greenhouse gases which are responsible for climate change. When refrigerant gases leak from the HVAC equipment during operations or when they are replenished, they end up in the atmosphere. This is called direct emissions from buildings.
The building sector offers many opportunities to reduce the greenhouse gas emissions playing a significant role in environment protection. Thus, building energy efficiency along with energy efficient HVAC system is important to address both direct and indirect greenhouse gas emissions from buildings.
Although compliance with this Code shall ensure an acceptable system performance, designers are encouraged to consider options that exceed these requirements.
Fundamentals of air conditioning
Air conditioning systems fundamentally transport heat. Heat is removed from a space to provide cooling and released into a heat sink. There are three basic heat sinks – air, water and ground.
Mechanical cooling permits to move heat from lower temperature zone (inside the building) to a higher temperature zone (outside the building), which would otherwise be impossible. Let’s understand this better with a water analogy. A submerged building can be compared to a building surrounded by heat in summer. The natural tendency of the water is to flow into the building. Only by pumping it uphill can it be removed from the building. In the same way, natural tendency of heat is to flow into the building from the higher outdoor temperatures. The only way to remove this heat is to pump it
out with a refrigeration machine. This is what a refrigerator and air conditioning machines do.
Figure 5.1 Air conditioning analogy
Air conditioners pump heat by using the latent heat of evaporation to pick up heat in one place (by changing liquid to gas) and then releasing the heat through condensation at another place (by changing gas to liquid). There are two basic methods of producing cool air in buildings
1. Compression refrigeration cycle
2. Absorption refrigeration cycle
Compression refrigeration cycle
The compression cycle is the most common. Basic components of a compression air conditioning system include a compressor, condenser (air-cooled or water cooled), and an evaporator. A gaseous working fluid, called as refrigerant, circulates in coils within the system. The compressor and condenser are usually located on the exteriors and the evaporator is located on the interiors.
Figure 5.2 Refrigeration cycle
Low pressure liquid refrigerant in the evaporator absorbs heat from the surrounding air or water and gets converted into vapour. It then reaches the compressor where it gets converted to high pressure vapour due to compression. In this process, the temperature of the high pressure vapour increases significantly.
The next step is the condenser where the refrigerant condenses to a high-pressure liquid. Heat rejection at the condenser is achieved by using air or water. The high-pressure liquid refrigerant then goes through the expansion valve and converts into low-pressure liquid ready for heat transfer in the evaporator. This is the refrigeration cycle which continues within the system.
Where the Refrigerant Evaporates, IT Absorbs Heat and Cooling Takes Place. Where IT Condenses, IT Releases Heat
Depending on the size and type of the HVAC system, the evaporator and the condenser can be separated or a combined unit. Further there can be many pumps in the system. The condenser can be water cooled or air cooled. But the fundamental refrigeration cycle remains the same. These are discussed in detail in the further sections.
Absorption refrigeration cycle
The absorption cycle produces cooling using heat such as steam, hot water or gas. This system is often appropriate when a source of low-cost heat is available.
The absorption refrigeration cycle works on the same principle as the compressive cycle. Additionally, there is another principle, which is:
Some liquids have a strong tendency to absorb certain vapors (e.g. water vapor is absorbed by liquid lithium bromide or ammonia).
There are no moving parts in this system. Electricity is used only to operate the pumps.
In the chamber A, water evaporates at low temperature (around 4oC) under high vacuum condition. In this process, it draws heat from the incoming chilled water and further cools it down (output). Thus, water is working as the refrigerant here. This chamber is called the evaporator. In order to keep evaporating, the water in the evaporator must be constantly supplied in order for it to keep evaporating.
The water vapour then migrates to chamber B, where it is absorbed by the lithium bromide solution. This chamber is called the absorber. Consequently, the vapor pressure is reduced in the absorber which in turn creates a vacuum in the evaporator. Due to this the water vapor can evaporate to continue the cooling process. Eventually, the lithium bromide will become too dilute to further absorb water.
In chamber C, an external heat source boils the water off the lithium bromide. This is called the generator. The heating media can be steam, hot water, gas or oil. The concentrated lithium bromide is then returned to the absorber, while the water vapor is condensed back into water in chamber D called the condenser. The last step is to return the liquid water back to the evaporator
so that the cycle can continue. Lithium Bromide - water absorption refrigeration systems have a Coefficient of Performance (COP) in the range of 0.65 – 0.70 and can provide chilled water at 6 . 7 ° C with a cooling water temperature of 3 0 ° C . Systems capable of providing chilled water at 3 ° C are also available.
Ammonia based systems operate at above atmospheric pressures and are capable of low temperature operation (below 0 ° C ) . Absorption machines of capacities in the range of 10–1500 tons are available. Although the initial cost of absorption system is higher than compression system, operational cost is much lower-if waste heat is used.
Figure 5.3 Vapor absorption cycle
The ECBC does not specify requirement for efficiency of the vapor absorption system. But requirements for components such as pumps and motors are covered in the Code. The ECBC specifies minimum equipment efficiencies for all HVAC equipment including chillers, unitary air conditioner, split air conditioner, packaged air conditioner, and boilers.
Types of air conditioning systems
There are primarily two main types of air conditioning systems:
A direct expansion or “DX” type system in the form of room air conditioners, split
system and packaged air conditioners. Heat exchange takes place directly from the refrigerant within the copper tubes to the air being drawn across the finned coil by an evaporator fan. The DX type systems offer localized solutions for a building’s heating and cooling needs. These systems are typically appropriate for smaller (singlezone) buildings.
Central plant system uses chilled water recirculation. Compared to a DX system, a central plant HVAC will be able to provide better thermal comfort and flexibility
Direct Expansion Systems or DX Systems
Unitary air conditioners
These are normally used for cooling individual rooms and provide cooling only when needed. Room air conditioners house all the components of an air conditioning system discussed above in one casing. Their efficiency is generally lower than that of central plant systems.
Figure 5.4 Window air conditioner
Split-system air conditioning systems
This consists of an outdoor metal cabinet that contains the condenser and compressor, and an indoor cabinet that contains the evaporator. In many split-system air conditioners, this indoor cabinet also contains a furnace or the indoor part of a heat pump.
Figure 5.5 Split air conditioner
Packaged air conditioners
A packaged air conditioner is a bigger version of the window air conditioner.
Figure 5.6 Packaged unit located on roof top
In a packaged air conditioner, the evaporator, condenser, and compressor are all located in one cabinet, which usually is placed on a roof or on a concrete slab adjacent to the building. This type of air conditioner is typical in small commercial buildings and also in residential buildings. Air supply and return ducts come from indoors through the building’s exterior wall or roof to connect with the packaged air conditioner. The system often includes electric heating coils or a
natural gas furnace. This combination of air conditioner and central heater eliminates the need for a separate furnace indoors.
The packaged system is an all-air system where building is cooled by circulating cool air from the point of generation to the point of supply. Hence it requires extensive duct work for air supply and therefore useful for small to medium sized commercial buildings.
Central Plant Systems
For large buildings, a central plant is better suited for air conditioning. In such systems, chilled water is centrally generated and then piped throughout the building to air handling units serving individual tenant spaces, single floors, or several floors. Ductwork then runs from each air handler to the zones that are served. Chilled water-based systems result in far less ductwork than all-air systems because chilled water piping
is used to convey thermal energy from the point of generation to each point of use.
Chillers
A chiller is essentially a packaged system, which produces chilled water for cooling. A typical chiller is rated between 15 to 1000 tons (53 to 3,500 kW) in cooling power. The chiller rejects heat either to condenser water (in the case of a water-cooled chiller) or to ambient air (in the case of an air-cooled chiller). Water-cooled chillers incorporate the use of cooling towers, which improve heat rejection more efficiently at the condenser than air-cooled chillers. For a water-cooled chiller, the cooling tower rejects heat to the environment through direct heat exchange between the condenser water and cooling air. For an air-cooled chiller, condenser fans move air through a condenser coil. As heat loads increase, water-cooled chillers are more energy-efficient than air-cooled chillers.
Figure 5.7 Different configurations for a central plant
A chiller plant is a system consisting of many components such as chillers, cooling tower, air handling units and pumps. There are several other components such as the chilled water piping, air supply ducts, valves, controls and so on making a central plant more complex to build
and operate compared to a packaged unit. However, it offers many benefits such as greater flexibility, better controllability, longer life and better efficiency.
All the components of a central plant need not be located in one place for it to function as a system. For example, the chillers can be located in a separate plant room outside the main building or in the basement while the cooling towers can be located on the roof top (Figure 5.7).
What are the different types of chillers?
Chillers are classified according to compressor type. Electric chillers for commercial comfort cooling have centrifugal, screw, scroll, or reciprocating compressors. Centrifugal and screw chillers have one or two compressors. Scroll and reciprocating chillers are built with multiple, smaller compressors.
Centrifugal chillers are the quiet, efficient, and reliable workhorses of comfort cooling. Although centrifugal chillers are available as small as 70 tons, most are 300 tons or larger.
Screw chillers are up to 40% smaller and lighter than centrifugal chillers, so are becoming popular as replacement chillers.
Scroll compressors are rotary positivedisplacement machines, also fairly new to the comfort cooling market. These small compressors are efficient, quiet, and reliable. Scroll compressors are made in sizes of 1.5 to 15 tons.
The Code contains mandatory requirements for the following elements of the HVAC system:
• Natural Ventilation
Equipment Efficiency
Controls
• Piping and Ductwork
System Balancing
Condensers
Economizers
Hydronic Systems
Ventilation
Ventilation in a building is essential for occupant comfort. Indoor air pollution is especially gaining attention today since more and more buildings are being designed as a sealed airtight unit due to air conditioning. This is particularly true of large buildings.
The build-up of indoor pollutants such as carbon dioxide and odor need to be flushed out from the interiors to ensure good indoor air quality. Materials used in the interiors such as furniture, furnishing, paints and finishes, cleaning products and others are known to release chemicals called volatile organic compounds (VOC). This process called off-gassing is continuous. Extensive research in this area has established that the concentration of such VOCs increases over time which has adverse effect on the human health, especially in a closed building.
Diluting the concentration of pollutants with outside air is the most common method for controlling indoor air quality. However, eliminating the pollutants by exhausting it from the space is a more effective method.
As per the Code,
(a) All habitable spaces shall be ventilated with outdoor air in accordance with the requirements of §5.2.1 and guidelines specified in National Building Code 2016 (Part 8: Building Services, Section 1: Lighting and Natural Ventilation, Subsection 5: Ventilation).
As per the Code, ventilation in the building can be provided by three methods
i. Natural ventilation
ii. Mechanical ventilation
Natural ventilation is provided by means of building fenestration and hence does not use energy. Mechanical ventilation is provided by means of HVAC system which is usually integrated with the air conditioning system. Mixed mode ventilation is a combination of natural and mechanical ventilation.
5.2.1.1 Natural Ventilation Design Requirements
Naturally ventilated buildings or spaces in a mixed-mode ventilated building shall:
(a) Comply with guidelines provided for natural ventilation in NBC.
(b) Have minimum BEE 3-star rated ceiling fans, if provided with ceiling fans.
(c) Have exhaust fans complying with minimum efficiency requirements of fans in §5.3, if provided.
Design Guidelines for natural ventilation
Naturally ventilated buildings rely on wind that is naturally prevalent at the site. The fenestrations of the building should be designed to capture the breeze for effective ventilation.
Design guidelines from NBC 2016 have been reproduced here in Box 5-1, keeping in view the
philosophy behind this Guide to include ECBC referenced material in the Guide. However, the exact relevance of these general guidelines in the design of commercial buildings need to be critically examined.
Further, ceiling fans are commonly used to force air circulation in a space for occupant comfort. Ceiling fans are largely considered to be a passive cooling strategy since it uses very less energy. However, the Code requires that the ceiling fans, if provided, should be minimum BEE 3-star rated so that it helps reduce the plug loads of the building.
The Star labeling program by the Bureau of Energy Efficiency mandates that certain products and appliances meet the Minimum Energy Performance Standards (MEPS). An informative label listing the energy consumption of the appliance or the equipment is affixed to a product in order to encourage consumer to make informed choices while purchasing. Ceiling fans, tubelights, CFL, split air conditioner, refrigerator and many other appliances are covered in this program. The program ensures that only the energy efficient models are available in the market.
Design guidelines for ceiling fans is given in Box 5-1 as per NBC 2016, Section 5.7
BOX 5-1 : Design guidelines for natural ventilation
Source: National Building Code 2016
By wind action
Building need not necessarily be oriented perpendicular to the prevailing outdoor wind; it may be oriented at any convenient angle between 0° and 30° without losing any beneficial aspect of the breeze. If the prevailing wind is from east or west, building may be oriented at 45° to the incident wind so as to diminish the solar heat without much reduction in air motion indoors.
Inlet openings in the buildings should be well distributed and should be located on the windward side at a low level, and outlet openings should be located on the leeward side. Inlet and outlet openings at high levels may only clear the top air at that level without producing air movement at the level of occupancy.
Maximum air movement at a particular plane is achieved by keeping the sill height of the opening at 85% of the critical height (such as head level) for the following recommended levels of occupancy:
(a) For sitting on chair 0.75 m
(b) For sitting on bed 0.60 m
(c) For sitting on floor 0.40 m
Inlet openings should not, as far as possible, be obstructed by adjoining buildings, trees, sign boards or other obstructions or by partitions inside in the path of air flow.
Greatest flow per unit area of openings is obtained by using inlet and outlet openings of nearby equal areas at the same level.
For a total area of openings (inlet and outlet) of 20% to 30% of floor area, the average indoor wind velocity is around 30% of outdoor velocity. Further increase in window size increases the available velocity but not in the same proportion. In fact, even under most favorable conditions the maximum average indoor wind speed does not exceed 40% of outdoor velocity.
Where the direction of wind is quite constant and dependable, the size of the inlet should be kept within 30 to 50% of the total area of openings and the building should be oriented perpendicular to the incident wind. Where direction of the wind is quite variable, the openings may be arranged so that as far as possible there is approximately equal area on all sides. Thus no matter what the wind direction is, there would be some openings directly exposed to wind pressure and others to air suction and effective air movement through the building would be assured.
Where the direction of wind is quite constant and dependable, the size of the inlet should be kept within 30 to 50% of the total area of openings and the building should be oriented perpendicular to the incident wind. Where direction of the wind is quite variable, the openings may be arranged so that as far as possible there is approximately equal area on all sides. Thus no matter what the wind direction is, there would be some openings directly exposed to wind pressure and others to air suction and effective air movement through the building would be assured.
By Stack Effect
Natural ventilation by stack effect occurs when air inside a building is at a different temperature than air outside. Thus, in heated buildings or in buildings wherein hot processes are carried out and in ordinary buildings during summer nights and during pre-monsoon periods, when the inside temperature is higher than that of outside, cool outside air will tend to enter through openings at low level and warm air will tend to leave through openings at high level. It would, therefore, be advantageous to provide ventilators as close to ceilings as possible. Ventilators can also be provided in roofs as, for example, cowl, ventpipe, covered roof and ridge vent.
Design guidelines for ceiling fans
5.7Energy Conservation in Ventilation System
5.7.1.1 Adequate number of circulating fans should be installed to serve all interior working areas during summer months in the hot dry and warm humid regions to provide necessary air movement at times when ventilation due to wind action alone does not afford sufficient relief.
5.7.1.1.1 The capacity of a ceiling fan to meet the requirement of a room with the longer dimension D metre should be about 55D m3/min.
5.7.1.1.2 The height of fan blades above the floor should be (3H + W)/4, where H is the height of the room, and W is the height of work plane.
5.7.1.1.3 The minimum distance between fan blades and the ceiling should be about 0.3m.
5.7.2 Electronic regulators should be used instead of resistance type regulators for controlling the speed of fans.
5.7.3 When actual ventilated zone does not cover the entire room area, then optimum size of ceiling fan should be chosen based on the actual usable area of room, rather than the total floor area of the room. Thus smaller size of fan can be employed and energy saving could be achieved.
5.7.4 Power consumption by larger fans is obviously higher, but their power consumption per square metre of floor area is less and service value higher. Evidently, improper use of fans irrespective of the rooms’ dimensions is likely to result in higher power consumption. From the point of view of energy consumption, the number of fans and the optimum sizes for rooms of different dimensions are given in Table 5-2-1
Table 5-2-1Optimum Size/Number of Fans for Rooms of Different Sizes
Room width
Room length
m
4m
5m
6m
7m
8m
9m
(1)
(2)
(3)
(4)
(5)
(6)
(7)
3
1200/1
1400/1
1500/1
1050/2
1200/2
1400/2
4
1200/1
1400/1
1200/2
1200/2
1200/2
1400/2
5
1400/1
1400/1
1400/2
1400/2
1400/2
1400/2
6
1200/2
1400/2
900/4
1050/4
1200/4
1400/4
7
1200/2
1400/2
1050/4
1050/4
1200/4
1400/4
8
1200/2
1400/2
1200/4
1200/4
1200/4
1400/4
9
1400/2
1400/2
1400/4
1400/4
1400/4
1400/4
10
1400/2
1400/2
1400/4
1400/4
1400/4
1400/4
11
1500/2
1500/2
1500/4
1500/4
1500/4
1500/4
12
1200/3
1400/3
1200/6
1200/6
1200/6
1400/6
13
1400/3
1400/3
1200/6
1200/6
1200/6
1400/6
14
1400/3
1400/3
1400/6
1400/6
1400/6
1400/6
Room width
Room length
m
10m
11m
12m
14m
16m
(1)
(8)
(9)
(10)
(11)
(12)
3
1400/2
1400/2
1200/3
1400/3
1400/3
4
1400/2
1500/2
1200/3
1400/3
1500/3
5
1400/2
1500/2
1400/3
1400/3
1500/3
6
1400/4
1500/4
1200/6
1400/6
1500/6
7
1400/4
1500/4
1200/6
1400/6
1500/6
8
1400/4
1500/4
1200/6
1400/6
1500/6
9
1400/4
1500/4
1400/6
1400/6
1500/6
10
1400/4
1500/4
1400/6
1400/6
1500/6
11
1500/4
1500/4
1500/6
1500/6
1500/6
12
1400/6
1500/6
1200n
1400/9
1400/9
13
1400/6
1500/6
1400/9
1400/9
1500/9
14
1400/6
1500/6
1400/9
1400/9
1500/9
NOTE: For data on outdoor wind speeds at a place, reference may be made to ‘The Climatic Data Handbook’ prepared by Central Building Research Institute, Roorkee, 1999
5.2.1.2Mechanical Ventilation Air Quantity Design Requirements
Mechanical ventilation is a standard part of air conditioning in large commercial buildings which have a central air conditioning plant. Usually about 10% of the circulated air for cooling will be outdoor air; commonly referred as fresh air. Designers need to size the systems such that there is a balance between the outdoor air supplied and the amount which is removed by exhaust fans.
Smaller buildings that might have split air conditioning systems need to rely on windows for outdoor air. Similar situation exists for smaller leased out spaces within large buildings where the tenant would typically install split air conditioning systems for better indoor air quality.
Whereas in mixed mode buildings, the fresh air intake through natural ventilation is intentional by design. In this case, the HVAC system, with the help of sensors and building automation system will modulate the exterior fenestrations to allow outdoor air directly in the building when the outdoor conditions are comfortable. As per the Code,
Buildings that are ventilated using a mechanical ventilation system or spaces in mixed-mode ventilated buildings that are ventilated with a mechanical system, either completely or in conjunction with natural ventilation systems, shall:
(a) Install mechanical systems that provide outdoor air change rate as per NBC.
(b) Have a ventilation system controlled by CO sensors for basement carpark spaces with total car park space greater than or equal to 600 m2.
Basements in commercial buildings are typically used for vehicle parking and usually poorly ventilated. Carbon monoxide (CO) and nitrous
oxide (NO2) are the two most abundant airborne pollutants found in basement parking structure posing health and safety concerns. Ventilation is essential to prevent the concentration of these pollutants reaching an unsafe level. The CO sensors help keep these levels in check by modulating the exhaust fans or the ventilation system through the building automation system. Further ventilation also helps remove the toxic oil and gasoline fumes given off vehicle exhausts.
Use of CO sensors is an energy conserving strategy where the ventilation fans will supply outdoor air as per the requirement to dilute the carbon monoxide concentrations for keeping it at safe levels. Thus, the fans do not need to be operating at full capacity all the time.
5.2.1.3Demand Control Ventilation
Spaces with variable and high occupant densities such as theatres, meeting rooms, auditorium and others are seldom occupied at full capacity and hence can save energy by providing demandcontrolled ventilation (DCV). Such system modulates the amount of outdoor air as per the number of people present in the space and hence save energy. A common indicator of occupancy is C O 2 concentration which increases with the number of people and also depends on their activity level. The DCV must maintain the outdoor air change rates as per the NBC
Mechanical ventilation systems shall have demand control ventilation if they provide outdoor air greater than 1,500 liters per second, to a space greater than 5 0 m 2 ] , with occupant density exceeding 40 people per 100 m 2 of the space, and are served by one or more of the following systems:
(a) An air side economizer
(b) Automatic outdoor modulating control of the outdoor air damper
It is important to locate the C O 2 sensors properly to get the maximum benefit. Few design guidelines are given below:
The sensors should be installed in all the densely occupied spaces
It should be installed at a height of 1.5m from the floor which is considered as the breathing zone
The C O 2 monitoring system should be configured to generate an audible or visual alarm to the system operator if the differential C O 2 concentration exceeds the setpoint by more than 10%.
Exceptions to § 5.2.1.3: Following shall be exempt from installing demand control ventilation systems:
(a) Classrooms in Schools, call centers category under Business
(b) Spaces that have processes or operations that generate dust, fumes, mists, vapors, or gases and are provided with exhaust ventilation, such as indoor operation of internal combustion engines or areas designated for unvented food service preparation, or beauty salons
(c) Systems with exhaust air energy recovering system
Minimum Space Conditioning Equipment Efficiencies
Today air conditioning is a common sight in commercial buildings. In a hot climate like India, space cooling is required for most of the year. In addition to providing cooling, the HVAC systems control humidity and ventilation. There are many different types of HVAC systems suited for different purposes. After deciding the right type of system for the project, it is important to select high efficient model also. There are many terms used to communicate the efficiency of systems as explained below.
Energy Efficiency Terms
Coefficient of Performance (COP) – Cooling
The ratio of the rate of heat removal to the rate of energy input, in consistent units, for a complete refrigerating system or some specific portion of that system under designated operating conditions.
Coefficient of Performance (COP) – Heating
The ratio of the rate of heat delivered to the rate of energy input, in consistent units, for a complete heat pump system, including the compressor and, if applicable, auxiliary heat, under designated operating conditions.
Energy Efficiency Ratio (EER)
The ratio of net cooling capacity in BTU/hr to total rate of electric input in watts under designated operating conditions.
Integrated Part-Load Value (IPLV)
A single number figure of merit based on partload EER, COP, or KW/ton expressing part-load efficiency for air-conditioning and heat pump equipment on the basis of weighted operation at various capacities for the equipment
Selection of individual equipment efficiency should be considered in the context of the whole HVAC system. In a chilled-water system, for example, although the chiller is at the core of the system and typically is the single largest energy user, simply selecting a high-efficiency chiller does not guarantee high performance. Auxiliary equipment (such as fans and blowers) and design decisions (such as “approach temperatures”) can have substantial effects on overall efficiency. Thus, attention to overall system design and auxiliary components is critical to achieving optimal performance and comfort. Even in packaged air-conditioning systems, leaky
ductwork, improper sizing, refrigerant charge, and air flow rates can considerably affect energy performance.
5.2.2.1Chillers
Chillers shall meet or exceed the minimum efficiency requirements presented in Table 5-1 through Table 5-2 under ANSI/ AHRI 550/ 590 conditions.
(b) The application of air-cooled chiller is allowed in all buildings with cooling load less than 530 kW. For buildings with cooling load equal to or greater than 530 kW, the number of air-cooled chiller shall be restricted to 33% of the total installed chilled water capacity unless the authority having jurisdiction mandates the application of air cooled chillers.
(c) Minimum efficiency requirements under BEE Standards and Labeling Program for chillers shall take precedence over the minimum requirements presented Table 5-1 through Table 5-2.
(d) To show compliance to ECBC, minimum requirement of both COP and IPLV requirement of ECBC Building shall be met. To show compliance with ECBC+ Building and SuperECBC Building, minimum requirement of either COP or IPLV of respective efficiency level shall be met.
Table 5-1Minimum Energy Efficiency Requirements for water cooled Chillers
ECBC Bui
lding
Chiller Capacity (kWr)
COP
IPLV
<260
4.7
5.8
≥260 & <530
4.9
5.9
≥530 &<1,050
5.4
6.5
≥1,050 &<1,580
5.8
6.8
≥1,580
6.3
7.0
Table 5-2Minimum Energy Efficiency Requirements for air cooled Chillers
ECBC Bui
lding
Chiller Capacity (kWr)
COP
IPLV
<260
2.8
3.5
≥260
3.0
3.7
5.2.2.2 Unitary, Split, Packaged Air-Conditioners
Unitary air-conditioners shall meet or exceed the efficiency requirements given in Table 5-3 through Error! Reference source not found.. Window and split air conditioners shall be certified under BEE’s Star Labeling Program. EER shall be as per IS 8148 for all unitary, split, packaged air conditioners greater than 10 kWr.
Table 5-3Minimum Requirements for Unitary, Split, Packaged Air Conditioners in ECBC Building
Cooling Capacity (kWr)
Water Cooled
Air Cooled
≤ 10.5
NA
BEE 3 Star
> 10.5
3.3 EER
2.8 EER
5.2.2.3Variable Refrigerant Flow
Variable Refrigerant Flow (VRF) systems shall meet or exceed the efficiency requirements specified in
Table 5-4 as per the ANSI/AHRI Standard 1230 while the Indian Standard on VRF is being developed. BEE Standards and Labeling requirements for VRF shall take precedence over the current minimum requirement
Table 5-4Minimum Efficiency Requirements for VRF Air conditioners for ECBC Building*
For Hea
ting or cooling or both
Type
Size category (kWr)
EER
IEER
VRF Air Conditioners,
< 40
3.28
4.36
Air cooled
>= 40 and < 70>= 70
3.263.02
4.344.07
* The revised EER and IEER values as per Indian Standard for VRF corresponding to values in this table will supersede as and when the revised standards are published.
5.2.2.4Air Conditioning and Condensing Units Serving Computer Rooms
Computer rooms or server rooms in commercial buildings tend to have a dedicated air conditioning system with different temperature control requirements for the equipment operation rather than occupant comfort. These
systems are typically operational for 24 hours and hence us significant amount of energy. As per the Code,
Air conditioning and condensing units serving computer rooms shall meet or exceed the energy efficiency requirements listed in Table 5-5.
Table 5-5Minimum Efficiency Requirements for Computer Room Air Conditioners
Equipment type
Net Sensible Cooling Capacitya
Minimum SCOP-127b
Downflow
Upflow
All types of computer room ACsAir/ Water/ Glycol
All capacity
2.5
2.5
a. Net Sensible cooling capacity = Total gross cooling capacity - latent cooling capacity – Fan powerb. Sensible Coefficient of Performance (SCOP-127): A ratio calculated by dividing the net sensible cooling capacity in watts by the total power input in watts (excluding reheater and dehumidifier) at conditions defined in ASHRAE Standard 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners)
5.2.2.5Boilers
Boilers are used for heating water to supply hot water or heat to a building. The heat is supplied by the combustion of a fuel; usually oil or gas. Major heat loss in a boiler occurs because of the creation of water vapour from burning hydrogen content of fuel. This enthalpy – or heat content in the form of latent heat of vaporization escapes the system resulting in loss of energy.
A condensing boiler recovers heat from the waste gas by condensing water vapour to liquid water thereby achieving higher energy efficiency. The condensed vapor leaves the system in a liquid form via a drain.
The Fuel Utilization Efficiency (FUE) is a unit that measures boiler’s efficiency of converting fuel to energy. A higher FUE means higher energy efficiency.
As per the Code,
Gas and oil-fired boilers shall meet or exceed the minimum efficiency requirements specified in
Table 5-6.Error! Reference source not found.
Table 5-6Minimum Efficiency Requirements for Oil and Gas Fired Boilers for ECBC building
Equipment Type
Sub Category
Size Category
Minimum FUE
Boilers, Hot Water
Gas or oil fired
All capacity
80%
FUE - fuel utilization efficiency
Controls
Controls are one of the most critical elements for improving efficiency of any HVAC system. Controls determine how HVAC systems should operate to meet the design goals of comfort, efficiency, and cost-effective operation. In this context, the Code specifies the use of time clocks, temperature controls/thermostats, and two-speed or variable speed drives for fans.
5.2.3.1Time clock
Mechanical cooling and heating systems in Universities and Training Institutions of all sizes and all Shopping Complexes with built up area greater than 20,000 m2 shall be controlled by timeclocks that:
(a) Can start and stop the system under different schedules for three different daytypes per week,
(b) Are capable of retaining programming and time setting during loss of power for a period of at least 10 hours, and
(c) Include an accessible manual override that allows temporary operation of the system for up to 2 hours.
Exceptions to §5.2.3.5:
(a) Cooling systems less than 17.5 kWr
(b) Heating systems less than 5.0 kWr
(c) Unitary systems of all capacities
5.2.3.2Temperature Controls
Mechanical heating and cooling equipment in all buildings shall be installed with controls to manage the temperature inside the conditioned zones. Each floor or a building block shall be installed with at least one control to manage the temperature. These controls should meet the following requirements:
(a) Where a unit provides both heating and cooling, controls shall be capable of providing a temperature dead band of 3 . 0 ° C within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
(b) Where separate heating and cooling equipment serve the same temperature zone, temperature controls shall be interlocked to prevent simultaneous heating and cooling.
(c) Separate thermostat control shall be installed in each
i. guest room of Resort and Star Hotel,
ii. room less than 30 m2in Business,
iii. air-conditioned class room, lecture room, and computer room of Educational,
iv. in-patient and out-patient room of Healthcare
5.2.3.3 Occupancy Controls
Occupancy controls shall be installed to deenergize or to throttle to minimum the ventilation and/or air conditioning systems when there are no occupants in:
(a) Each guest room in a Resort and Star Hotel
(b) Each public toilet in a Star Hotel or Business with built up area more than 20,000 m2
(c) Each conference and meeting room in a Star Hotel or Business
(d) Each room of size more than 30 m 2 in Educational buildings
5.2.3.4Fan Controls
Through the application of variable speed drive (VSD) on the cooling tower fan, the fan speed can be reduced during lower ambient conditions for reducing energy consumption.
Variable Speed Drive
A variable speed drive (VSD) is an electronic device that controls the rotational speed of a piece of motor-driven equipment (e.g. a blower, compressor, fan, or pump). Speed control is obtained by adjusting the frequency of the voltage applied to the motor. This approach usually saves energy for varying-load applications.
However condenser water reset strategy may require condenser fan speeds to be maintained to improve chiller efficiency by lowering condenser water temperature. At lower loads the overall system efficiency should be the driver as pumping and tower fan energy form significant proportion of overall chiller plant energy.
Cooling towers in buildings with built up area greater than 20,000 m2, shall have fan controls based on wet bulb logic, with either:
(a) Two speed motors, pony motors, or variable speed drives controlling the fans, or
(b) Controls capable of reducing the fan speed to at least two third of installed fan power
5.2.3.5Dampers
Dampers are devices that regulate the air flow in a air handling system. The unwanted hot or cold air from outside can be prevented from entering the building by controlling the dampers.
All air supply and exhaust equipment, having a Variable Frequency Drive (VFD), shall have dampers that automatically close upon:
(a) Fan shutdown, or,
(b) When spaces served are not in use
(c) Backdraft gravity damper is acceptable in the system with design outdoor air of the system is less than 150 liters per second in all climatic zones except cold climate, provided backdraft dampers for ventilation air intakes are protected from direct exposure to wind.
(d) Dampers are not required in ventilation or exhaust systems serving naturally conditioned spaces.
Dampers are not required in exhaust systems serving kitchen exhaust hoods.
Piping and Ductwork
5.2.4.1Piping Insulation
Chilled water and hot water are carried through a network of pipes to various components of the heating, cooling and service hot water equipment in the building. During this transport, heat loss should be minimized to conserve energy. Hence the Code requires insulation for piping as per Table 5-7 through
Table 5-9. Since the rate of heat transfer also depends on the temperature of water in the pipes, the Code specifies higher insulation levels for water at higher temperatures. In the case of a ductless system, Code specifies insulation values for the refrigerant piping.
Figure 5.8 Chilled water pipe insulation installation
Further, insulation that is exposed to weather and subject to damage must be protected. For example, insulation located outdoors may be subject to damage from sunlight, rain, moisture, wind.
Piping for heating, space conditioning, and service hot water systems shall meet the insulation requirements listed in Table 5-7 through Table 5-9. Insulation exposed to weather shall be protected by aluminum sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above, or be painted with water retardant paint.
Exceptions to § 5.2.4.1:
(a) Reduction in insulation R value by 0.2 (compared to values in Table 5-7, Table 5-8 and Table 5-9) to a minimum insulation level of R-0.4 shall be permitted for any pipe located in partition within a conditioned space or buried.
(b) Insulation R value shall be increased by 0.2 over and above the requirement stated in Table 5-7 through Table 5-9 for any pipe
located in a partition outside a building with direct exposure to weather.
(c) Reduction in insulation R value by 0.2 (compared to values in Table 5-7, Table 5-8 and Table 5-9) to a minimum insulation level of R-0.4 shall be permitted for buildings in Temperate climate zone.
Table 5-7Insulation Requirements for Pipes in ECBC Building
Operating Temperature (ºC)
Pipe size (mm<40Insulation R v
)>=40alue (m<sup>2</sup>.K/W)
Heating System
>94°Cand <=121°C
0.9
1.2
>60°Cand <=94°C
0.7
0.7
>40°Cand <=60°C
0.4
0.7
Cooling System
>4.5°Cand <=15°C
0.4
0.7
< 4.5°C
0.9
1.2
Refrigerant Piping (Split systems)
>4.5°Cand <=15°C
0.4
0.7
< 4.5°C
0.9
1.2
Minimizing heat loss is important for energy conservation. For piping that can easily run into several metres in buildings, insulation requirements are progressively stringent for ECBC+ and Super ECBC buildings.
Table 5-8Insulation Requirements for Pipes in ECBC+ Building
Operating Temperature (°C)
Pipe size (mm)
< 40
>=40
Insulation R value ( m².K/W )
Heating System
>94°C and <=121°C
1.1
1.3
>60°C and <=94°C
0.8
0.8
>40°C and <=60°C
0.5
0.9
Cooling System
>4.5°C and <=15°C
0.5
0.9
< 4.5°C
1.1
1.3
Refrigerant Piping (Split systems)
>4.5°C and <=15°C
0.5
0.9
< 4.5°C
1.1
1.3
Table 5-9Insulation Requirements for Pipes in SuperECBC Buildings
Operating Temperature (ºC)
Pipe size (mm)
< 40
>=40
Insulation R value (m2.K/W)
Heating System
>94°C to <=121°C
1.5
1.5
>60°C to <=94°C
1.0
1.3
>40°C to <=60°C
0.7
1.1
Cooling System
>4.5°C to <=15°C
0.7
1.2
< 4.5°C
1.5
1.5
Refrigerant Piping (Split Systems)
>4.5°C to <=15°C
0.7
1.1
< 4.5°C
1.5
1.5
5.2.4.2Ductwork and Plenum Insulation
Air is supplied to rooms/spaces by means of round or rectangular ducts. Supply ducts carry the conditioned air to be supplied to the space and return ducts carry the air from the space back to the air conditioning system. Ducts are constructed out of thin sheet metal which are highly conductive.
Figure 5.9 Ductwork in a mechanical room
Typically supply ducts carry cool air and hence it is critical to thermally insulate the ducts to prevent heat loss. Whereas the return ducts
carry relatively warm air and hence heat loss is not a great concern as long as the duct is installed inside the building. The Code requires return ducts to be insulated only when exposed to outdoor air.
Figure 5.10 Insulated ducts
Sometimes, the empty space above the dropped ceiling can be used carry the return air instead of installing a separate return duct. This is called a plenum. As per the Code, the requirements for return ducts is applicable to the plenum space. Table 5-10 shows the Code requirement for applicable insulation.
Table 5-10Ductwork Insulation (R value in m2. K/W) Requirements
Duct Location
Supply ducts
Return ducts
Exterior
R -1.4
R -0.6
Unconditioned Space
R -0.6
None
Buried
R -0.6
None
Table 5 A provides R-value (h. oF .ft2)/Btu of a few insulating materials.
Table 5A Sample R-values for Duct Insulation Materials
Installed R-value1 (m2·K/W)
Typical Material Meeting or Exceeding the Given R-value2
1.9
½ in. Mineral fiber duct liner per ASTM C 1071, Type 1 1 in. Mineral fiber duct wrap per ASTM C 1290
3.5
1 in. Mineral fiber duct liner per ASTM C 1071, Types I & II 1 in. Mineral fiber board per ASTM C 612, Types IA & IB 1 in. Mineral fiber duct board per UL 181 1 ½ in. Mineral fiber duct wrap per ASTM C 1290 1 in. Insulated flex duct per UL 181
6.0
1 ½ in. Mineral fiber duct liner per ASTM C1071, Types I & II 1 ½ in. Mineral fiber duct board per UL 181 1 ½ in. Mineral fiber board per ASTM C 612, Types IA & IB 2 in.. 2 lb/ft3 Mineral fiber duct wrap per ASTM C 1290 2 ½ in. 0.6 to 1 lb./ft3 Mineral fiber duct wrap per ASTM C 1290 2 ½ in. Insulated flex duct per UL 181
8.0
2 in. Mineral fiber duct liner per ASTM C 1071, Types I & II 2 in. Mineral fiber duct board per UL 181 2 in. Mineral fiber board per ASTM C 612, Types IA & IB 3 in. ¾ lb/ft3 Mineral fiber duct wrap insulation per ASTM C 1290 3 in. Insulated flex duct per UL 181
10.0
2 ½ in. Mineral fiber board per ASTM C 612, Types IA & IB
1) Listed R-values are for the insulation only as determined in accordance with ASTM C 518 at a mean temperature of 24°C at the installed thickness and do not include air film resistance. 2) Consult with manufacturers for other materials or combinations of insulation thickness or density meeting the required R-value.
Source: ASHRAE 90.1 User Manual (2007), Table 6-D
Duct sealing
Ensuring proper design, construction and sealing of duct joints is an essential aspect of energy conservation. Ductwork should be properly air sealed and also be protected from moisture absorption. Condensing moisture can cause many types of insulation, such as fiberglass, to lose their insulating properties or degrade. Duct sealing is critical to avoid air leaks that prevent the HVAC system from functioning as designed and operated. The Code currently does not
provide any guidance on ductwork sealing. The ASHRAE 90.1 energy code can be referred to for appropriate seal levels for all ductwork in order to minimize energy losses from the HVAC system. ASHRAE 90.1 (tables 6.2.4.3 A and 6.2.4.3 B) specify sealing requirements based on the duct location, static pressure classification, and type of the duct (exhaust or return) as given below in Table 5 B.
Minimum Duct Seal Level
Table 5B Requirements for duct sealing
Duct Location
Duct Type Supply
Exhaust
Return
≤498.2 Pa
≥498.2 Pa
Outdoors
A
A
C
A
Unconditioned Spaces
B
A
C
B
C
B
B
C
Source: ASHRAE 90.1 Table 6.2.4.3 A
Duct Seal Levels
Seal Level
Sealing Requirements
A
All transverse joints and longitudinal seams, and duct wall penetrations. Pressure-sensitive tape shall not be used as the primary sealant.
B
All transverse joints and longitudinal seams. Pressure-sensitive tape shall not be used as the primary sealant
C
Transverse joints only.
Source: ASHRAE 90.1 Table 6.2.4.3 B
Guidelines for good duct design and construction is given in the Box 5-2 below.
BOX 5-2 Design guidelines for good ductwork
• Design a compact duct layout with short straight runs and minimal bends.
Include ducts within conditioned space if possible. This makes the ducts easy to access for maintenance. It also protects the duct from being exposed to high temperatures and humidity (in some cases) in unconditioned spaces.
5.2.5.1General
System balancing is a process for maintaining the performance of an HVAC system, and for providing the occupants with a comfortable conditioned space and reducing the cost of operation. Balancing is achieved by optimizing the air/water distribution rates for the HVAC system.
System balancing shall be done for systems serving zones with a total conditioned area exceeding 500 m2.
Construction documents provide vital information to the building owners on how to properly operate and maintain a system that has been properly balanced. Verify during final inspection that an operations manual has been passed on to the building owner and that it contains the followingi i information at a
Figure 5.11 Air distribution scheme
HVAC equipment capacity
Equipment operation and maintenance manuals
HVAC system control maintenance and calibration information, including wiring diagrams, schedules, and control sequence descriptions.
A complete written narrative of how each system is intended to operate.
5.2.5.2Air System Balancing
Air System Balancing refers to the adjustment of airflow rates through air distribution system devices, such as fans and diffusers. In a central plant system, the chilled water is supplied to the Air Handling Unit (AHU) from where the cool air supplied to all the spaces in the building. Depending on the scale and zoning, there can be several AHUs in a building. A large AHU can be located on the roof top which supplied cool air to all the zones in the building. This could work in the case of a single zone system. However, most buildings have multiple zones in which case AHUs can be installed on each floor.
High-efficiency air distribution systems can substantially reduce fan power required by an HVAC system, resulting in dramatic energy savings. The largest gains in efficiency for air distribution systems are realized in the system design phase for new constructions or major retrofit projects. Passive or natural air transport systems have the highest efficiency, and successful, modern examples of this approach are steadily accumulating. For buildings that require mechanical ventilation, innovative design approaches and a methodical examination of the entire air system can greatly improve efficiency and effectiveness.
Design options for improving air distribution efficiency include:
Variable-air-volume systems
VAV diffusers
• Low-pressure-drop duct design
• Low-face-velocity air handlers
Fan sizing and variable-frequencydrive motors
Displacement ventilation systems.
Air balancing is done by adjusting the position of dampers, splitter vanes, extractors, etc., manually or by using automatic control devices, such as constant air volume or variable air volume boxes.
Balancing is necessary to verify that each space served by a system receives the air volume designed for that space. Proper means for air balancing should be installed at each supply air outlet and zone terminal device. These include balancing dampers or other means of supplyair adjustment provided in the branch ducts or at each individual duct register, grille, or diffuser. Installation in the duct system of all devices used for balancing, shown on the
approved mechanical plans, typically, on the ductwork layout, should be verified.
As per the Code,
Air systems shall be balanced in a manner to first minimize throttling losses; then, for fans with fan system power greater than 0.75 kW, fan speed shall be adjusted to meet design flow conditions.
5.2.5.3Hydronic System Balancing
Hydronic System Balancing refers to the adjustment of water flow rates through distribution system devices, such as pumps and coils, by manually adjusting the position of valves, or by using automatic control devices, such as flow control valves.
When something is balanced, it is even on both sides. Therefore, a balanced hydronic system is one that delivers even flow to all of the devices on that piping system. Each component has an effective equal length of pipe on the supply and return. And when a system is balanced, all of the pressure drops are correct for the devices. When that happens, the highest efficiencies are possible in the system. One need not have to change system supply temperatures to accommodate one zone only. The system has the least amount of pressure drop possible, which translates into reduced pumping costs.
A balanced hydronic system is one that is efficient. If a system that is not delivering the water to the right devices in the right amounts, then the system is out of balance.
As per the Code,
Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions
Condensers
5.2.6.1Condenser location
A condenser is a heat exchanger that liquefies refrigerant vapor through heat removal. The typical condensing unit houses a compressor, a condenser fan motor, and coils, along with controls which make all the components work sequentially.
Condensers shall be located such that the heat sink is free of interference from heat discharge by devices located in adjoining spaces, and do not interfere with other such systems installed nearby.
Condensers should be located in such a manner that there is no restriction to the air flow around the condenser coils, there is no short-circuiting of discharge air to the intake side, and the heat discharge of other adjacent equipment is not anywhere the air intake of the condenser.
Condenser water treatment is important to eliminate mineral buildup in condensers and chilled water systems. Mineral deposits create poor heat transfer situations there by reducing the efficiency of the unit.
Service Hot Water Heating
For some building types such as large hotels and hospitals service water heating can be major energy consumer. Inefficiency in water heating is caused primarily by inefficiency of the heating equipment, and by heat loss from hot water storage tanks and distribution piping network.
ECBC through mandatory requirements seeks to minimize energy usage in water heating systems by:
Utilizing solar water heating
Specifying heating equipment efficiency
Maximizing heat recovery and minimizing electric heating
Insulating hot water storage tanks and pipelines
• Reducing standby losses
Reducing heat and evaporation losses in heated swimming pools
5.2.7.4Piping Insulation
As per the Code,
Piping insulation shall comply with § 5.2.4.1. The entire hot water system including the storage tanks, pipelines shall be insulated conforming to the relevant IS standards on materials and applications.
Box 5-3 provides guidelines for hot water temperature controls and measures for improving heating efficiency.
BOX 5-3 Guidelines for temperature controls
Water-heating systems are required to have controls that are adjustable down to a 4 9 ° C setpoint or lower. An exception is made where a higher setting is recommended by the manufacturer to prevent condensation and possible corrosion. To comply with this requirement, the water heater must have thermostatic control with an accessible setpoint. This setpoint must be adjustable down to whichever is lower: 4 9 ° C or the minimum manufacturer’s recommended setting to prevent condensation.
Both standby and distribution losses will be minimized by designing a system to provide hot water at the minimum temperature required. In addition to the potential energy savings, maintaining water temperature as low as possible reduces corrosion and scaling of water heaters and components.
Another important benefit is improved safety with respect to scalding. Accidental scalding from temperatures as low as 6 0 ° C is responsible for numerous deaths each year. Designers should be aware that the bacteria that cause Legionnaire’s Disease has been found in service water heating systems and can colonize in hot water systems maintained below 4 6 ° C ,
BOX 5-2 Guidelines for temperature controls (contd)
Careful maintenance practices can reduce the risk of contamination. In health-care facilities or service-water systems maintained below 60°C, periodic flushing of the fixtures with high temperature water or other biological controls may be appropriate.
Guidelines for improving water heating system efficiency temperature controls
Reduce standby losses from storage tank and pipes.
Lower Water Heating Temperature: Use a hot water system with a thermostat. Service water heating energy use and operating costs can be reduced by simply lowering the thermostat setting on your water heater.
For each 5.5ºC (10ºF) reduction in water temperature, can save between 3%–5% in energy costs.
Insulate pipes and use heat traps: Insulate all exposed pipes. The R-value of pipe insulation is dependent on wall thickness; thicker is better. A 5/8” wall thickness should be considered minimum for foam insulation, while 3” is the minimum for fiberglass wrap. Heat trap nipples work best to eliminate convective losses from the tank into the plumbing, but pipe loops also work if the drop is at least 6”.
5.2.7.2Heating Equipment Efficiency
As per the Code,
Service water heating equipment shall meet or exceed the performance and minimum efficiency requirements presented in available Indian Standards
(a) Solar water heater shall meet the performance/ minimum efficiency level mentioned in IS 13129 Part (1&2)
(b) Gas Instantaneous water heaters shall meet the performance/minimum efficiency level mentioned in IS 15558 with above 80% Fuel utilization efficiency.
(c) Electric water heater shall meet the performance/ minimum efficiency level mentioned in IS 2082.
The mandatory requirements for the Code include minimum efficiencies presented in relevant Indian Standards for various water heating equipment such as electric and gas heaters, instantaneous heaters, boilers and pool heaters.
For Solar water heating systems, IS 13129 (Part 1) provides information on the ‘Performance Rating Procedure Using Indoor Test Methods’, and IS 13129 (Part 2) provides the information on the ‘Procedure for System Performance Characterization and Yearly Performance Prediction’. These standards however, do not provide any performance/minimum efficiency levels.
For Gas Instantaneous Water Heaters, IS 15558 describes the information and procedure for the measurement of thermal efficiency of the heaters.
As per this Standard, thermal efficiency of the water heaters (under test conditions) shall not be less than:
84% for water heaters with a nominal heat input exceeding 10 kW
82% for water heaters with a nominal heat input not exceeding 10 kW
However, the Code specifies thermal efficiency of 80% or more.
For Electric Water Heaters, IS 2082 (Part 1) covers the safety and performance requirements of heaters with rated capacities in the range of 6 liters to 200 liters. In these heaters, certain amount of energy is consumed to keep the water hot while it is not being used. This consumption of electricity is called as standing loss (or standby loss). Standby loss depends on the design and insulation of the water heater, as well as the difference between the temperature of the water and that of the air around the tank. Water heating energy can be reduced by decreasing standby losses.
The following table of IS 2082 (Part 1) specifies the standing loss in the heaters. For hot water temperature difference of 45°C, in no case the standing loss should exceed the values specified in Table 5 C.
5.2.7.5Heat Traps
Heat traps are valves or loops of pipe that allow water to flow into the water heater tank but prevent unwanted hot-water flow out of the tank. The valves have balls inside that either float or sink into a seat, which stop natural water circulation loop. Heat traps can help save energy and cost on the water heating bill by preventing convective heat losses through the inlet and outlet pipes. These specially designed valves come in pairs. The valves are designed differently for use in either the hot or cold water line.
Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a non-recirculating system shall have heat traps on both the inlet and outlet piping.
Heat traps may either be installed internally by the manufacturer, installed as an after-market add-on, or site fabricated. Site fabricated heat traps may be constructed by creating a loop or inverted U-shaped arrangement to the inlet and outlet pipes.
Figure 5.15 Heat trap elements
5.3Prescriptive Requirements
As per the Code,
Compliance shall be demonstrated with the prescriptive requirements in this section. Supply, exhaust, and return or relief fans with motor power exceeding 0.37 kW shall meet or exceed the minimum energy efficiency requirements specified in
Table 5-11 through Table 5-13 except the following need not comply with the requirement
(a) Fans in un-ducted air conditioning unit where fan efficiency has already been taken in account to calculate the efficiency standard of the comfort system.
(b) Fans in Health Care buildings having HEPA filters.
(c) Fans inbuilt in energy recovery systems that pre-conditions the outdoor air.
Table 5-11Mechanical and Motor Efficiency Requirements for Fans in ECBC Buildings
System type
Fan Type
Mechanical Efficiency
Motor Efficiency(As per IS 12615)
Air-handling unit
Supply, return and exhaust
60%
IE 2
Table 5-12Mechanical and Motor Efficiency Requirements for Fans in ECBC+ Buildings
System type
Fan Type
Mechanical Efficiency
Motor Efficiency(As per IS 12615)
Air-handling unit
Supply, return and exhaust
65%
IE 3
Table 5-13Mechanical and Motor Efficiency Requirements for Fans in SuperECBC Buildings
System Type
Fan Type
Mechanical Efficiency
Motor Efficiency(As per IS 12615)
Air-handling unit
Supply, exhaust
return
and
70%
IE 4
Chillers
Chillers shall meet or exceed the minimum efficiency requirements for ECBC+ and SuperECBC Buildings are presented in Table 5-14 and Table 5-15 under ANSI/ AHRI 550/ 590 conditions.
Table 5-14Minimum Energy Efficiency Requirements for water cooled Chillers
ECBC+
Building
Super Buildi
ECBC ng
Chiller
COP
IPLV
COP
IPLV
Capacity
(kWr)
<260
5.2
6.9
5.8
7.1
≥260 & <530
5.8
7.1
6.0
7.9
≥530
5.8
7.5
6.3
8.4
&<1,050
≥1,050
6.2
8.1
6.5
8.8
&<1,580
≥1,580
6.5
8.9
6.7
9.1
Table 5-15Minimum Energy Efficiency Requirements for air cooled Chillers
ECBC+
Building
SuperECBC Building
Chiller
COP
IPLV
COP/ IPLV
Capacity
(kWr)
<260
3.0
4.0
NA
≥260
3.2
5.0
NA
Pumps
Chilled and condenser water pumps shall meet or exceed the minimum energy efficiency requirements specified in Table 5-16 Pump Efficiency Requirements for ECBC BuildingTable 5-16 through Table 5-17. Requirements for pumps in district chiller systems and hot water pumps for space heating are limited to the installed efficiency requirement of individual pump equipment only. To show compliance, calculate the total installed pump capacity in kilo watt and achieve the prescribed limits per kilo watt of refrigeration installed in the building.
Exceptions to §5.3.1: Pumps used in processes e.g. service hot water, chilled water used for refrigeration etc.
Table 5-16Pump Efficiency Requirements for ECBC Building
Equipment
ECBC
Chilled Water Pump (Primary and Secondary)
18.2 W/ kW<sub>r</sub> with VFD on secondary pump
Condenser Water Pump
17.7 W/ kW<sub>r</sub>
Pump Efficiency (minimum)
70%
Table 5-17Pump Efficiency Requirements for ECBC+ Building
Equipment
ECBC+ Building
Chilled Water Pump (Primary and Secondary)
16.9 W/ kW<sub>r</sub> with VFD on secondary pump
Condenser Water Pump
16.5 W/ kW<sub>r</sub>
Pump Efficiency (minimum)
75%
Table 5-18Pump Efficiency Requirements for SuperECBC Building
Equipment
SuperECBC Building
Chilled Water Pump (Primary and Secondary)
14.9 W/ kW<sub>r</sub> with VFD on secondary pump
Condenser Water Pump
14.6 W/ kW<sub>r</sub>
Pump Efficiency (minimum)
85%
Cooling Towers
Water-based HVAC systems offer significant energy savings due to the ability of water to transport large quantities of heat over relatively long distances, more efficiently than air-based systems. Additionally, they offer advantages such as smaller equipment size and cost, along with reduced maintenance and extended life of mechanical equipment. However, for water scarce urban centers in India, the viable installation and operation of cooling towers will require balancing needs for energy efficiency and water conservation simultaneously. Air cooled chillers are a good option to conserve water, however the trade-off is that these chillers consume more energy to provide the same amount of cooling when compared to water cooled chillers with cooling towers. Some guidelines for improving energy and water
efficiency in cooling towers is discussed in Box 5-4
As per the Code,
Cooling towers shall meet or exceed the minimum efficiency requirements specified in Table 5-19. ECBC+ and SuperECBC Buildings shall have additional VFD installed in the cooling towers
Table 5-19Cooling Tower Efficiency Requirements for ECBC, ECBC+, and SuperECBC Buildings
Equipment type
Rating Condition
Efficiency
Open circuit cooling tower Fans
35°C
entering
water 0.017 kW/kWr
29°C
leaving
water 0.31 kW/L/s
24°C WB outdoor air
BOX 5-4 – Design guidelines for water and energy efficiency in cooling towers Energy Efficiency Measures:
Proper site selection and sizing of the tower can reduce fan speed, capacity, and sound and help to conserve energy
Centrifugal fans in favor of lower energy axial fans can reduce horsepower by 50% or more for the same capacity
Fan control through two-speed motors, pony motors, or variable speed motors can save energy as well
Water Efficiency Measures:
An optimized bleed rate for the tower should be maintained to regulate water consumption. The evaporation rate is dependent on the load, which can vary widely and a constant bleed rate usually discharges more water than required. A properly operating conductivity meter can automatically control bleed to the proper amount required to maintain the desired tower chemistry in the system at all times.
Contaminant induction should be minimized and a proper blow down rate should be maintained. Water treatment regimens are effective for water conservation, keeping the cooling loop cleaner, saving energy, reducing maintenance, and improving reliability of the entire cooling system.
New technological solutions like hybrid wet-dry cooling tower designs, which combine wet and dry cooling can be adopted to reduce water use, some as much as 70% compared to conventional towers. Typically, a dry finned coil section is combined in series with an evaporative section in these units. The dry finned section handles as much of the load as possible, with the unit able to operate completely dry at reduced ambient. Both open and closed-circuit versions are available.
Source: Morrison F.: What’s up with Cooling Tower (2004). ASHRAE Journal 46 (7)
Boilers
Gas and oil-fired boilers shall meet or exceed the minimum efficiency requirements specified in Table
Table 5-20Minimum Efficiency Requirements for Oil and Gas Fired Boilers for ECBC+ and SuperECBC Buildings
Equipment Type
Sub Category
Size Category
Minimum FUE
Boilers, Hot Water
Gas or oil fired
All capacity
85%
FUE - fuel utilization efficiency
Economizers
Economizers allow the use of outdoor air to cool the building when the outside temperature is cooler than that inside. An economizer consists of dampers, sensors, actuators, and logic devices that together decide how much outside air to bring into a building. Under the right conditions, sensors and controls shut down the compressor and bring in the outside air through the economizer louvers. A properly operating economizer can cut energy costs by as much as 10% of a building’s total energy consumption, depending mostly on local climate and internal cooling loads.
Figure 5.16 Economizer
There are primarily two types of Economizers as explained below.
Air Economizer
An air economizer is duct and damper arrangement and automatic control system that together allow a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather.
Water Economizer
A water economizer is a system by which the supply air of a cooling system is cooled indirectly with water that is itself cooled by heat or mass transfer to the environment without the use of mechanical cooling.
5.3.5.1 Economizer for ECBC, ECBC+ and SuperECBC building
As per the Code,
Each cooling fan system in buildings with built up area greater than 20,000 m2, shall include at least one of the following:
(a) An air economizer capable of modulating outside-air and return-air dampers to supply 50% of the design supply air quantity as outside-air.
(b) A water economizer capable of providing 50% of the expected system cooling load at outside air temperatures of 10°C drybulb/7.2°C wet-bulb and below.
Exception to § 5.3.5.1:
(a) Projects in warm-humid climate zones are exempt.
(b) Projects with only daytime occupancy in the hot-dry are exempt.
(c) Individual ceiling mounted fan systems is less than 3,200 liters per second exempt
5.3.5.2Partial Cooling
One can use the building’s intrinsic thermal mass to reduce peak cooling loads by circulating cool night-time air to pre-cool the building prior to daily occupancy in the cooling season. The building control system can operate ventilation fans in the economizer mode on a scheduled basis. Care should be taken to prevent excessive fan operation that would offset cooling energy savings. It is also ensured that night humidity does not preclude the use of this strategy.
Where required by §5.3.5.1 economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the cooling load.
5.3.5.3 Economizer Controls
Air economizer shall be equipped with controls
(a) That allows dampers to be sequenced with the mechanical cooling equipment and not be controlled by only mixed air temperature.
(b) Capable of automatically reducing outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage.
(c) Capable of high-limit shutoff at 24 °C dry bulb temperature.
5.3.5.4Testing
As per the Code,
Air-side economizers shall be tested in the field following the requirements in §12 Appendix C 12to ensure proper operation.
Exception to §5.3.5.4: Air economizers installed by the HVAC system equipment manufacturer and certified to the building department as being factory calibrated and tested per the procedures in §12.
Variable Flow Hydronic Systems
Fluid from the heating or cooling source is supplied to heat transfer devices, such as coils and heat exchangers, and back through the hydronic system. The Code specifies the type of equipment and capabilities in such a way as to reduce pump energy. Variable fluid flow, automatic isolation valves, and variable speed drives enable the system to operate below design flow when needed.
5.3.6.1 Variable Fluid Flow
As per the Code,
HVAC pumping systems having a total pump system power exceeding 7.5 kW shall be designed for variable fluid flow and shall be capable of reducing pump flow rates to an extent which is lesser or equal to the limit, where the limit is set by the larger of:
(a) 50% of the design flow rate, or
(b) the minimum flow required by the equipment manufacturer for proper operation of the chillers or boilers.
5.3.6.2 Isolation Valves
Two-way automatic isolation valves serve as a means of varying flow rate in a hydronic system.
As per the Code,
Water cooled air-conditioning or heat pump units with a circulation pump motor greater than or equal to 3.7 kW shall have two-way automatic isolation valves on each water cooled airconditioning or heat pump unit that are interlocked with the compressor to shut off condenser water flow when the compressor is not operating.
5.3.6.3Variable Speed Drives
Variable speed drives are required to control chilled water and condenser water systems for energy efficiency.
As per the Code,
Chilled water or condenser water systems that must comply with either §5.3.6.1 or §5.3.6.2 and that have pump motors greater than or equal to 3.7 kW shall be controlled by variable speed drives.
Unitary, Split and Packaged Air-Conditioners
Unitary air-conditioners shall meet or exceed the efficiency requirements given in Table 5-21 and Table 5-22. Window and split air conditioners shall be certified under BEE’s Star Labeling Program. EER shall be as per IS 8148 for all unitary, split, packaged air conditioners greater than 10 kWr.
Table 5-21Minimum Requirements for Unitary, Split, Packaged Air Conditioners in ECBC+ Building
Cooling Capacity (kWr)
Water Cooled
Air Cooled
≤10.5
NA
BEE 4 Star
>10.5
3.7 EER
3.2 EER
Table 5-22Minimum Requirements for Unitary, Split, Packaged Air Conditioners in SuperECBC Building
Cooling Capacity (kWr)
Water Cooled
Air Cooled
≤10.5
NA
BEE 5 Star
>10.5
3.9 EER
3.4 EER
Controls for ECBC+ and SuperECBC buildings
ECBC+ and SuperECBC buildings shall comply with requirements of §0 in addition to complying with requirements of §5.2.3.
5.3.8.1Centralized Demand Shed Controls
ECBC+ and SuperECBC Buildings with built up area greater than 20,000 m2 shall have a building management system. All mechanical cooling and heating systems in ECBC+ and SuperECBC Buildings with any programmable logic controller (PLC) to the zone level shall have the following control capabilities to manage centralized demand shed in noncritical zones:
(a) Automatic demand shed controls that can implement a centralized demand shed in non-critical zones during the demand response period on a demand response signal.
(b) Controls that can remotely decrease or increase the operating temperature set points by four degrees or more in all noncritical zones on signal from a centralized control point
(c) Controls that can provide an adjustable rate of change for the temperature setup and reset
The centralized demand shed controls shall have additional capabilities to
(a) Be disabled by facility operators
(b) Be manually controlled from a central point by facility operators to manage heating and cooling set points
5.2.7.1Solar Water Heating
Solar Water heaters use energy from the sun’s rays to heat water for domestic & commercial purpose. This appliance consists of a collector which collects solar energy and an insulated water tank to store hot water.
The collector on receiving solar energy transfers heat to the underlying pipes containing water which in turn goes to the insulated storage tank. This water is recirculated to increase the temperature of the water.
The lifespan of a solar water heater designed as per BIS specification is between 15-20 years but a lot depends on the maintenance of the heater.
Types of solar water heaters
There are two categories of solar water heaters, namely closed loop and open loop. The closed loop system has heat exchangers for protection against hard water obtained from borewells. In the open loop system, the water is open to the atmosphere at some point in the cycle. The open loop systems are suitable for domestic as well as small industrial purposes.
Solar collectors
There are two types of solar collectors in a solar hot water system as explained below.
Flat plate collectors
It consists of a large heat absorbing plate that is dark colored to absorb solar radiation to its maximum potential. Series of thin copper tubes called risers are attached to this plate that has water circulating inside them. This assembly is enclosed in an insulated glass box.
Figure 5.12 Flat plate collector
The metal plate absorbs heat and transfers it to the copper tubes to heat the water. The glass box prevents the absorbed heat from escaping.
Evacuated tube collectors
This system consists of rows of transparent glass tubes connected to a header pipe. Since the pipes are cylindrical, the angle of sunlight is always perpendicular to the tubes which enables the collector to perform well even in low sunlight.
5.2.7.6Swimming Pools
Heated swimming pools can be a source of considerable heat and water loss due to
evaporation. Also, the cost of the energy required to maintain the temperature of the water in the pool at a level comfortable for swimming is a strong incentive to adopt measures which promote retention of heat in the pool and reduction in heat loss.
As per the Code,
All heated pools shall be provided with a vapor retardant pool cover on or at the water surface. Pools heated to more than 32°C shall have a pool cover with a minimum insulation value of R-4.1.
Exception to § 5.2.7.6: Pools deriving over 60% of their energy from site-recovered energy or solar energy source.
5.3.8.3Chilled Water Temperature Reset
Chilled-water reset adjusts the chilled-water set point to improve the efficiency of the chiller, reducing the energy consumption of the chiller. Usually, a chilled-water-reset strategy raises the set-point temperature when the building load is at less-than-design conditions. Producing warmer chilled water reduces the burden on the compressor, which means that the chiller consumes less energy.
Chilled water systems with a design capacity exceeding 350 kWr supplying chilled water to comfort conditioning systems in ECBC+ and SuperECBC Buildings shall have controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature.
Exceptions to §5.3.8.2: Controls to automatically reset chilled water temperature shall not be required where the supply temperature reset
controls causes improper operation of equipment.
Controls for SuperECBC Buildings
SuperECBC Buildings shall comply with requirements of §5.3.9 in addition to complying with requirements of §5.2.3 and §0.
In rooms of normal size having identical windows on opposite walls the average indoor air speed increases rapidly by increasing the width of the window up to two-thirds of the wall width; beyond that the increase is in much smaller proportion than the increase of the window width. The air motion in the working zone is maximum when window height is 1.1 m. Further increase in window height promotes air motion at higher level of window, but does not contribute additional benefits as regards air motion in the occupancy zones in buildings.
Windows of living rooms should open directly to an open space. In places where building sites are restricted, open space may have to be created in the buildings by providing adequate courtyards.
In the case of rooms with only one wall exposed to outside, provision of two windows on that wall is preferred to that of a single window.
Windows located diagonally opposite to each other with the windward window near the upstream comer give better performance than other window arrangements for most of the building orientations.
Horizontal louvers, that is a sunshade, atop a window deflects the incident wind upward and reduces air motion in the zone of occupancy. A horizontal slot between the wall and horizontal louver prevents upward deflection of air in the interior of rooms. Provision of inverted L type (r) louver increases the room air motion provided that the vertical projection does not obstruct the incident wind.
Provision of horizontal sashes inclined at an angle of 45° in appropriate direction helps to promote the indoor air motion. Sashes projecting outward are more effective than projecting inward.
Air motion at working plane 0.4 m above the floor can be enhanced by 30% using a pelmet type wind deflector.
Roof overhangs help by promoting air motion in the working zone inside buildings.
In case of room with windows on one wall, with single window, the room wind velocity inside the room on the windward side is 10% of outdoor velocity at points up to a distance of one-sixth of room width from the window and then decreases rapidly and hardly any air movement is produced in the leeward half portion of the room. The average indoor wind velocity is generally less than 10% of outdoor velocity. When two windows are provided and wind impinges obliquely on them, the inside velocity increases up to 15% of the outdoor velocity.
Cross ventilation can be obtained through one side of the building to the other, in case of narrow buildings with the width common in the multi-storeyed type by the provision of large and suitably placed windows or combination of windows and wall ventilators for the inflow and outflow of air.
Verandah open on three sides is to be preferred since it causes an increase in the room air motion for most of the orientations of the building with respect to the outdoor wind.
A partition placed parallel to the incident wind has little influence on the pattern of the air flow, but when located perpendicular to the main flow, the same partition creates a wind shadow. Provision of a partition with spacing of 0.3 m underneath helps by augmenting air motion near floor level in the leeward compartment of wide span buildings.
Air motion in a building unit having windows tangential to the incident wind is accelerated when unit is located at end-on position on downstream side.
Air motion in two wings oriented parallel to the prevailing breeze is promoted by connecting them with a block on downstream side.
Air motion in a building is not affected by constructing another building of equal or smaller height on the leeward side; but it is slightly reduced if the leeward building is taller than the windward block.
Air motion in a shielded building is less than that in an unobstructed building. To minimize the shielding effect, the distances between two rows should be 8H for semi-detached houses and 10H for long rows houses. However, for smaller spacing the shielding effect is also diminished by raising the height of the shielded building.
Hedges and shrubs deflect the air away from the inlet openings and cause a reduction in indoor air motion. These elements should not be planted at a distance of about 8m from the building because the induced air motion is reduced to minimum in that case. However, air motion in the leeward part of the building can be enhanced by planting a low hedge at a distance of 2m from the building.
Trees with large foliage mass having trunk bare of branches up to the top level of window, deflect the outdoor wind downwards and promotes air motion in the leeward portion of buildings.
Ventilation conditions indoors can be ameliorated by constructing buildings on earth mound having a slant surface with a slope of 10° on the upstream side.
In case of industrial buildings, the window height should be about 1.6m and the width about two thirds of wall width. These should be located at a height of 1.1m above the floor. In addition, openings around 0.9m high should be provided over two-thirds of the length of the glazed area in the roof lights.
Height of industrial buildings, although determined by the requirements of industrial processes involved, generally kept large enough to protect the workers against hot stagnant air below the ceiling as also to dilute the concentration of contaminant inside. However, if high level openings in roof or walls are provided, building height can be reduced to 4m without in any way impairing the ventilation performance.
The maximum width up to which buildings of height usually found in factories, being effectively ventilated by natural means by wind action, is 30m, beyond which sufficient reliance cannot be placed on prevailing winds. Approximately half the ventilating area of openings should be between floor level and a height of 2.25m from the floor.
Use screws to secure connections in the metal ducts. Wipe ducts to ensure they are clean and dry especially at seams and joints.
Seal all seams and joints in the ducts with mastic. Cover all seams that are wider than 1/8 inch with fiberglass mesh tape then apply mastic.
• Use putty around all conduit and wiring holes.
Consider insulating all metal ductwork located in conditioned space, including supply and return ducts, duct boots, and exhaust ducts, to minimize condensation.
Ensure that all duct connections and seams are air sealed for the following, regardless of whether they are located in conditioned or unconditioned space:
Ensure that insulation completely covers ducts and connections without gaps, voids, or compressions.
Insulate the storage tank: Install a water heater insulation blanket; the higher the R-value, the better. Use wire or twine or straps to insure that the blanket stays in place. Some new highefficiency heaters should not be insulated; consult the equipment manual provided by the manufacturer.
Gas water heaters should not be insulated on top or within about 8” of the bottom of the water tank. Set an electric water heater on a rigid foam insulation board. This step is most critical when the heater sits on a concrete slab, but it’s always a good idea. Install the water heater in a heated location. The colder the air surrounding the heater, the more the standby loss. Indoor gas heaters should be sealed combustion or fan-forced draft.
Table 5C Standing Loss in Storage Type Electric Water Heaters
Rated Capacity in
Loss in kWh/day for 45º
Liters
Difference
6
0.792
10
0.990
15
1.138
25
1.386
35
1.584
50
1.832
70
2.079
100
2.376
140
2.673
200
2.970
Source: IS 2082 (Part 1): 1993 (Reaffirmed 2004) Edition 5.4 (2002-05) Stationary Storage Type Electric Water Heaters-Specification (Fourth Revision)
5.2.7.3 Other Water Heating System
As per the Code,
Supplementary heating system shall be designed to maximize the energy efficiency of
the system and shall incorporate the following design features in cascade:
(a) Maximum heat recovery from hot discharge system like condensers of air conditioning units,
(b) Use of gas fired heaters wherever gas is available, and
(c) Electric heater as last resort.
Figure 5.13 Evacuated tube collector
Each tube consists of a thick outer glass and a thin inner glass tube with a special coating that absorbs solar energy (high absorptance) but inhibits loss (low emittance). Unlike flat panel collectors, evacuated tube collectors do not heat the water directly within the tubes. Instead, air is removed or evacuated from the space between the two tubes, forming a vacuum (hence the name evacuated tubes).
Figure 5.14 Cross section of an evacuated tube
With the assistance of this vacuum, evacuated tube collectors generally produce higher fluid temperatures than the flat plate counterparts and hence may become very hot in summer.
As per the Code,
Hotels and Hospitals in all climatic zones and all buildings in cold climate zone with a hot water system, shall have solar water heating equipment installed to provide for:
(a) at least 20% of the total hot water design capacity if above grade floor area of the building is less than 20,000 m2
(b) at least 40% of the total hot water design capacity if above grade floor area of the building is greater than or equal to 20,000 m 2
For compliance with ECBC+ and SuperECBC, Hotels and Hospitals in all climatic zones and all buildings in cold climate zone with a hot water system, shall have solar water heating
equipment installed to provide at least 40% and 60% respectively of the total hot water design capacity.
Exception to § 5.2.7.1: Systems that use heat recovery to provide the hot water capacity required as per the efficiency level or building size.
5.3.9.1Variable Air Volume Fan Control
Fans in Variable Air Volume (VAV) systems in SuperECBC buildings shall have controls or devices that will result in fan motor demand of no more than 30% of their design wattage at 50% of design airflow based on manufacturer’s certified fan data.
Energy Recovery
Energy recovery system help exchange/recover heat from the outgoing stale air so that the incoming air can be pre-cooled before reaching the air conditioning system.
The exhaust air exiting a building is warmer than the conditioned supply air but cooler than the outdoor air when the building is operating in cooling mode. Hence the heat exchange can provide additional benefit by reducing the load on the air conditioning system.
The system consists of a unit with fans or blowers and a rotating thermal wheel that transfers heat between two isolated airstreams. The wheel is made of material with high thermal conductivity to enable an efficient heat exchange. The two streams of air are kept isolated from each other. The thermal wheel can help exchange only the sensible heat in which case it is commonly referred to sensible wheel. Or it can also help recover moisture in addition to sensible heat, in which case it is referred to as enthalpy wheel.
As per the Code,
All Hospitality and Healthcare, with systems of capacity greater than 2,100 liters per second and minimum outdoor air supply of 70% shall have air-to-air heat recovery equipment with minimum 50% recovery effectiveness
Hospitality and healthcare buildings can have a dedicated 100% outdoor air supply system and various spaces that have a high minimum requirement for ventilation air. In such cases, energy recovery is beneficial.
The same concept that be applied to recover heat from exhaust gases of a generator set. As per the Code,
At least 50% of heat shall be recovered from diesel and gas fired generator sets installed in Hospitality, Healthcare, and Business buildings with built up area greater than 20,000 m2.
Service Water Heating
For compliance with ECBC+ and SuperECBC,
(a) Hospitality and Healthcare in all climatic zones shall have solar water heating equipment installed to provide atleast 40% of the total hot water design capacity.
(b) All buildings in cold climate zone with a hot water system, shall have solar water heating equipment installed to provide atleast 60% of the total hot water design capacity.
Exception to §5.3.11: Systems that use heat recovery to provide the hot water capacity required as per the building type, size and efficiency level.
Total System Efficiency – Alternate Compliance Approach
A chilled water plant is a complex collection of individual components (chiller, pumps, cooling tower etc.) that have been designed to work together as a system (Error! Reference source
not found.). Energy efficiency requirements for each component of this system have been specified in this Code under various sections. However, Chillers, Pumps and Cooling towers shall be efficient not just individually but also when working together under various operating conditions. Therefore, the Chilled water plant efficiency as a whole is an important parameter to consider before Chilled water plant equipment selection.
Just like the Building Envelope Trade-off method, this alternative compliance method gives engineers the flexibility to show compliance for the entire Chilled water plant as one instead of meeting the individual equipment prescriptive requirements mentioned under §5.3.1 to §5.3.11.
Figure 5.17 Chiller plant schematic
Compliance for this alternative path is to be demonstrated by hourly energy simulation using a BEE approved energy simulation software.
As per the Code,
This alternate compliance approach is applicable for central chilled water plant side system in all building types. The total installed capacity per kilo-watt refrigeration load shall be less than or
equal to maximum threshold requirements as specified in Error! Reference source not found.. Equipment that can be included in central chilled water plant side system for this alternate approach are chillers, chilled water pumps, condenser water pumps, and cooling tower fan. Compliance check will be based on annual hourly simulation.
Table 5-23Minimum System Efficiency Requirement for ECBC, ECBC+, and SuperECBC Buildings
Water Cooled Chilled
Maximum Threshold
Water Plant
(kW/kWr)
ECBC
0.26
ECBC+
0.23
SuperECBC
0.20
5.3.8.2Supply Air Temperature Reset
Cooling hot outside air takes energy. The colder the supply air, more energy it takes. A reset strategy saves energy by reducing the need to produce very cold air. For example, when a space
is not fully occupied, the supply air temperature can be increased to meet the lower demand. Reset strategy allows the building energy management system to adjust the supply of cold air to meet demand, balancing comfort versus energy cost.
As per the Code,
Multi zone mechanical cooling and heating systems in ECBC+ and SuperECBC Buildings shall have controls that automatically reset the supply-air temperature in response to building loads or to outdoor air temperature. Controls shall reset the supply air temperature to at least 25% of the difference between the design supply air temperature and the design room air temperature.
Exception to § 5.3.8.2 : ECBC+ and SuperECBC Buildings in warm humid climate zone.