but the ratios of areas as maintained in the table for different occupancies and types of construction shall be adhered to.
Advantage has been taken of the developments, particularly in fire resistance rating of materials, designating types of construction in a rational manner and relating the area limitations of different occupancies to different types of construction.
Halons (halogenated hydrocarbons) which exhibit exceptional fire fighting and explosion prevention/suppression characteristics have been found to possess high ozone depleting potential. They come under Group II of Annex A of the Montreal Protocol on Substances that Deplete the Ozone Layer, the international environmental agreement for phasing out ozone depleting substances. Due to increasing evidence that the ozone layer is getting depleted at a faster rate than thought earlier, the developed countries accelerated their phase-out schedule with a view to achieving 100 percent phase-out of halons by 1 January 1994, instead of the earlier target date of 1 January 2000 after which only essential use of halon was allowed. For developing countries like India, the total phase-out of halons is to be achieved by 1 January 2010, as per Montreal Protocol, unless a decision is taken in between to hasten up the phase-out of ozone depleting substances. India, having become a signatory to the Protocol in June 1992, is committed to abide by the Montreal Protocol decisions. In accordance with Ministry of Environment and Forests, Government of India, Ozone Depleting Substances (Regulations), Rules, 2000, the manufacture of halon based fire extinguishers and extinguishing systems has been phased out by 1 January 2001. Meanwhile, the practical implications of the phasing out of the halons cover, by and large, the following aspects:
a) Availability of halons will be restricted;
b) Non-standard halon extinguishers, like aerosol type, shall not be permitted;
c) Discharge of halons for training/testing, etc shall not be permitted;
d) All efforts shall be made for avoiding/minimizing halon emissions at various levels such as production, fire equipment manufacture, use, service and maintenance;
e) Since ‘drop-in’ substitutes for halons are not likely to be available on a commercial scale in the near future, wherever possible, instead of halon, use of suitable alternative extinguishing media/methods will be resorted to, even accepting some trade-offs, if necessary; and
Halons shall be restricted for ‘essential uses’ only, for protection of critical fire explosion risk areas which would otherwise result in serious impairment of an essential service to society, or pose an unacceptable threat to life, the environment, or national security.
NOTE — Detailed instructions which will be issued by the Government of India from time-to-time for implementation of the Country Programme for the phasing out of ozone depleting substance (ODS) and regarding permitting use of halons for applications till the availability of proper substitutes, shall have to be complied with.
The first version of this Part was formulated in 1970 and first revision was brought out in 1983. Subsequently the first revision of this Part was modified in 1997 through Amendment No. 3 to 1983 version of the Code. This modified version of this part included few tables for the fire resistance ratings of various building components, such as walls, columns, beams and floors. The requirements for wet riser, down-comer, automatic sprinkler installation, high velocity (10-15 m/s) water spray or foam generating system, etc, for buildings were modified. Annex giving guidelines for selection of fire detectors had been deleted and relevant Indian Standards on fire alarm system and smoke detectors had been referred. Also, Annex for determination of fire loads and fire load density for arriving at the classification of occupancy hazard and calorific values of some common materials were included. Annex for broad classification of industrial and non-industrial occupancies into low, moderate and high hazard had also been included.
As a result of implementation of this Part, some useful suggestions have emerged. This revision has, therefore, been prepared to take care of the same. The significant modifications incorporated include:
a) The text has now been divided into the following broad clauses:
Fire Prevention — Covering aspects of fire prevention pertaining to design and construction of buildings on passive fire protection measures, also describing the various types of building materials and their fire rating.
Life Safety — Covering life safety provisions in the event of fire and similar emergencies, also addressing construction and occupancy features that are necessary to minimize danger to life from fire, smoke, fumes or panic.
Fire Protection — covering the significant appurtenances and their related components and guidelines for selecting the correct type of equipment and installation meant for fire protection of the building, depending upon the classification and type of the building.
b) The classification of building based on occupancy has been elaborated, with:
Starred hotels now covered as a new sub-division A-6 under occupancy Group A Residential.
Heritage structures and archeological monuments now covered under sub-division D-3 occupancy Group D Assembly buildings.
Mixed assembly occupancies now covered as a new sub-division D-6 and under ground elevated railways have been covered as a new sub-division D-7 under occupancy Group D Assembly buildings.
TV stations now covered under sub-division E-5 of occupancy Group E Business buildings.
c) The minimum capacity of smoke exhaust equipment has been increased to 12 air changes per hour.
d) For the external stairs for exit requirements, the width and treads have been increased to 1 250 mm and 250 mm respectively.
e) Under the requirements for institutional buildings the clear width of all required exits which serve as egress from hospital or infirmary section has been increased from 1.5 m to 2 m. Also, provision of patient-lift has been included.
f) Due cognizance of halon phase out programme has been taken, while specifying provisions in this Part with respect to fire protection using fire extinguishers/systems.
All standards cross-referred to in the main text of this section, are subject to the revision. The parties to agreement based on this Part are encouraged to investigate the possibility of applying the most recent editions of the standards.
1Scope
This Part covers the requirements for fire prevention, life safety in relation to fire and fire protection of buildings. The Code specifies construction, occupancy and protection features that are necessary to minimize danger to life and property from fire.
3Fire Prevention
3.1 Classification of Building Based on Occupancy
3.1.1 General Classification
All buildings, whether existing or hereafter erected shall be classified according to the use or the character of occupancy in one of the following groups:
Group A Residential
Group B Educational
Group C Institutional
Group D Assembly
Group E Business
Group F Mercantile
Group G Industrial
Group H Storage
Group J Hazardous
3.1.1.1 Minor occupancy incidental to operations in another type of occupancy shall be considered as part of the main occupancy and shall be classified under the relevant group for the main occupancy.
Examples of buildings in each group are given in 3.1.2 to 3.1.10.
3.1.2 Group A Residential Buildings
These shall include any building in which sleeping accommodation is provided for normal residential purposes with or without cooking or dining or both facilities, except any building classified under Group C.
Buildings and structures under Group A shall be further sub-divided as follows:
Sub-division A-1 Lodging or rooming houses
Sub-division A-2 One or two-family private dwellings
Sub-division A-3 Dormitories
Sub-division A-4 Apartment houses (flats)
Sub-division A-5 Hotels
Sub-division A-6 Hotels (Starred)
a) Sub-division A-1 Lodging or rooming houses — These shall include any building or group of buildings under the same management, in which separate sleeping accommodation for a total of not more than 40 persons (beds), on transient or permanent basis, with or without dining facilities but without cooking facilities for individuals is provided. This includes inns, clubs, motels and guest houses.
A lodging or rooming house shall be classified as a dwelling in sub-division A-2 if no room in any of its private dwelling units is rented to more than three persons.
b) Sub-division A-2 One or two-family private dwellings — These shall include any private dwelling which is occupied by members of one or two families and has a total sleeping accommodation for not more than 20 persons. If rooms in a private dwelling are rented to outsiders, these shall be for accommodating not more than three persons per room.
If sleeping accommodation for more than 20 persons is provided in any one residential building, it shall be classified as a building in sub-division A-1, A-3 or A-4 as the case may be.
2Terminology
2.0 For the purpose of this Part, the following definitions shall apply.
2.1 Automatic Fire Detection and Alarm System — Fire alarm system comprising components for automatically detecting a fire, initiating an alarm of fire and initiating other actions as appropriate.
NOTE — The system may also include manual fire alarm call points.
2.2 Automatic Sprinkler System — A system of water pipes fitted with sprinkler heads at suitable intervals and heights and designed to actuate automatically, control and extinguish a fire by the discharge of water.
2.3 Building — Any structure for whatsoever purpose and of whatsoever materials constructed and every part thereof whether used as human habitation or not and includes foundation, plinth, walls, floors, roofs, chimneys, plumbing and building services, fixed platforms, VERANDAH, balcony, cornice or projection, part of a building or anything affixed thereto or any wall enclosing or intended to enclose any land or space and signs and outdoor display structures. Tents, SHAMIANAHS, tarpaulin shelters, etc, erected for temporary and ceremonial occasions with the permission of the Authority shall not be considered as building.
2.4 Building, Height of — The vertical distance measured in the case of flat roofs, from the average level of the ground around and contiguous to the building or as decided by the Authority to the terrace of the last livable floor of the building adjacent to the external wall; and in the case of pitched roofs, up to the point where the external surface of the outer wall intersects the finished surface of the sloping roof; and in the case of gables facing the road, the mid-point between the eaves level and the ridge. Architectural features serving no other function except that of decoration, shall be excluded for the purpose of measuring heights.
2.5 Combustible Material — The material which either burns itself or adds heat to a fire, when tested for non-combustibility in accordance with accepted standard [4(1)].
2.6 Covered Area — Ground area covered by the
building immediately above the plinth level. The area covered by the following in the open spaces is excluded from covered area (see Table 19):
a) garden, rockery, well and well structures, plant nursery, waterpool, swimming pool (if uncovered), platform round a tree, tank, fountain, bench, CHABUTARA with open top and unenclosed on sides by walls and the like;
b) drainage culvert, conduit, catch-pit, gully pit, chamber, gutter and the like;
c) compound wall, gate, unstoreyed porch and portico, slide, swing, uncovered staircases, ramp areas covered by CHHAJJA and the like; and
3.2Fire Zones
3.2.1 Demarcation
The city or area under the jurisdiction of the Authority shall for the purpose of the Code, be demarcated into distinct zones, based on fire hazard inherent in the buildings and structures according to occupancy (see 3.1), which shall be called as ‘Fire Zones’.
3.2.2 Number and Designation of Fire Zones
3.2.2.1 The number of fire zones in a city or area under the jurisdiction of the Authority depends upon the existing layout, types of building construction (see 3.3), classification of existing buildings based on occupancy (see 3.1) and expected future development of the city or area. In large cities or areas, three fire zones may be necessary, while in smaller ones, one or two may be adequate.
3.2.2.2 The fire zones shall be made use of in land use development plan and shall be designated as follows:
a) Fire Zone No. 1 — This shall comprise areas having residential (Group A), educational (Group B), institutional (Group C), and assembly (Group D), small business (Subdivisions E-1) and retail mercantile (Group F) buildings, or areas which are under development for such occupancies.
b) Fire Zone No. 2 — This shall comprise business (Sub-divisions E-2 to E-5) and industrial buildings (Sub-division G-1 and G-2), except high hazard industrial buildings (Sub-division G-3) or areas which are under development for such occupancies.
c) Fire Zone No. 3 — This shall comprise areas having high hazard industrial buildings (Subdivision G-3), storage buildings (Group H) and buildings for hazardous used (Group J)
or areas which are under development for such occupancies.
3.2.3 Change in the Fire Zone Boundaries
When the boundaries of any fire zone are changed, or when it is intended to include other areas or types of occupancies in any fire zone, it shall be done by following the same procedure as for promulgating new rules or ordinances or both.
3.2.4 Overlapping Fire Zones
3.2.4.1 When any building is so situated that it extends to more than one fire zone, it shall be deemed to be in the fire zone in which the major portion of the building or structure is situated.
3.2.4.2 When any building is so situated that it extends equally to more than one fire zone, it shall be deemed to be in the fire zone having more hazardous occupancy buildings.
3.2.5 Temporary Buildings or Structures
3.3Types of Construction
3.3.1 General
The design of any building and the type of materials used in its construction are important factors in making the building resistant to a complete burn-out and in preventing the rapid spread of fire, smoke or fumes, which may otherwise contribute to the loss of lives and property.
The fire resistance of a building or its structural and non-structural elements is expressed in hours against a specified fire load which is expressed in kcal/m2, and against a certain intensity of fire. The fire-resistance test for structural element shall be done in accordance with good practice [4(5)]. For the purpose of the Code, the types of construction according to fire resistance shall be classified into four categories, namely,
Type 1 Construction, Type 2 Construction, Type 3 Construction and Type 4 ‘Construction’. The fire resistance ratings for various types of construction for structural and non-structural members shall be as given in Table 1.
For buildings 15 m in height or above non-combustible materials should be used for construction and the internal walls of staircase enclosures should be of brick work or reinforced concrete or any other material of construction with minimum of 2 h rating. The walls for the chimney shall be of Type 1 and Type 2 Construction depending on whether the gas temperature is above 200°C or less.
3.3.2 It is required that an element/component shall have the requisite fire resistance rating when tested in acco”rdance with the accepted standard [4(1)]. Tables 2 to 18 provide available data regarding fire resistance ratings of various building components such as walls, columns, beams and floors. Fire damage assessment, post fire structural safety assessment of various structural elements of the building and adequacy of the structural repairs can be done by the fire resistance ratings mentioned in Tables 2 to 18.
Table 1Fire Resistance Ratings of Structural and Non-Structural Elements (Hours) (Clause 3.3.1)
Sl No.
Structural Element
Type of Construction
Type 1(3)
Type 2(4)
Type 3(5)
Type 4(6)
(1)
(2)
3.4General Requirements of All Individual Occupancies
3.4.1 General
All buildings shall satisfy certain requirements which contribute, individually and collectively, to the safety of life from fire, smoke, fumes and panic arising from these or similar causes. There are, however, certain general principles and common requirements which are applicable to all or most of the occupancies.
3.4.2 Exceptions and Deviations
Exceptions and deviations to the general provisions of requirements of individual occupancies are given as applicable to each type of occupancy in 6.1 to 6.9. In case of practical difficulty or to avoid unnecessary hardship, without sacrificing reasonable safety, the Authority may grant exemptions from the Code.
3.4.3 Occupation of Buildings under Construction
3.4.3.1 A building or portion of the building may be occupied during construction, repairs, alterations or additions only if all means of exit and fire protection measures are in place and continuously maintained for the occupied part of the building.
3.4.3.2 A high rise building during construction shall be provided with the following fire protection measures, which shall be maintained in good working condition at all the times:
a) Dry riser of minimum 100 mm diameter pipe with hydrant outlets on the floors constructed with a fire service inlet to boost the water in the dry riser and maintenance should be as per the requirements laid down in good practice [4(6)].
b) Drums filled with water of 2 000 litres capacity with two fire buckets on each floor; and
c) A water storage tank of minimum 20 000 litres capacity, which may be used for other construction purposes also.
3.4.4 Maximum Height
Every building shall be restricted in its height above the ground level and the number of storeys, depending upon its occupancy and the type of construction. The height shall be measured as specified in Part 3 ‘Development Control Rules and General Building Requirements’. The maximum permissible height for any combination of occupancy and types of construction should necessarily be related to the width of street fronting the building, or floor area ratios and the local fire fighting facilities available.
3.4.5 Floor Area Ratio
4Life Safety
4.1 General
Every building shall be so constructed, equipped, maintained and operated as to avoid undue danger to the life and safety of the occupants from fire, smoke, fumes or panic during the time period necessary for escape.
4.2General Exit Requirements
4.2.1 An exit may be a doorway; corridor; passageway(s) to an internal staircase, or external staircase, or to a VERANDAH or terrace(s), which have access to the street, or to the roof of a building or a refuge area. An exit may also include a horizontal exit leading to an adjoining building at the same level.
4.2.2 Lifts and escalators shall not be considered as exits.
4.2.3 Every exit, exit access or exit discharge shall be continuously maintained free of all obstructions or impediments to full use in the case of fire or other emergency.
4.2.4 Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants, in case of fire or other emergency.
4.2.5 In every building or structure, exits shall comply with the minimum requirements of this part, except those not accessible for general public use.
4.2.6 No building shall be so altered as to reduce the number, width or protection of exits to less than that required.
4.2.7 Exits shall be clearly visible and the route to reach the exits shall be clearly marked and signs posted to guide the occupants of the floor concerned. Signs shall be illuminated and wired to an independent electrical circuit on an alternative source of supply. The sizes and colours of the exit signs shall be in accordance with good practice [4(16)]. The colour of the exit signs shall be green.
NOTE — This provision shall not apply to A-2 and A-4 occupancies less than 15 m in height.
4.2.8 The floors of areas covered for the means of exit shall be illuminated to values not less than 1 ft candle (10 lux) at floor level. In auditoriums, theatres, concert halls and such other places of assembly, the illumination of floor exit/access may be reduced during period of performances to values not less than 1/5 ft candle (2 lux).
4.2.9 Fire doors with 2 h fire resistance shall be provided at appropriate places along the escape route and particularly at the entrance to lift lobby and stair well where a ‘funnel or flue effect’ may be created, inducing an upward spread of fire to prevent spread of fire and smoke.
4.2.10 All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street.
4.2.11 Exits shall be so arranged that they may be reached without passing through another occupied unit.
4.3 Occupant Load
For determining the exits required, the number of persons within any floor area or the occupant load shall be based on the actual number of occupants, but in no case less than that specified in Table 20.
4.5Arrangement of Exits
4.5.1 Exits shall be so located that the travel distance on the floor shall not exceed the distance given in Table 22.
4.5.2 The travel distance to an exit from the dead end of a corridor shall not exceed half the distance specified
in Table 22, except in assembly and institutional occupancies in which case it shall not exceed 6 m.
4.5.3 Whenever more than one exit is required for any room space or floor of a building, exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any point in the area served.
Table 22Travel Distance for Occupancy and Type of Construction (Clauses 4.4.1, 4.5.1 and 4.5.2)
Sl No.
Group of Occupancy
Maximum Travel Distance Construction
Types 1 & 2 m
Types 3 & 4 m
(1)
(2)
(3)
(4)
i)
Residential (A)
30.0
22.5
ii)
Educational (B)
30.0
22.5
iii)
Institutional (C)
30.0
22.5
iv)
Assembly (D)
30.0
30.0
v)
Business (E)
30.0
30.0
vi)
Mercantile (F)
30.0
30.0
vii)
Industrial (G)
45.0
¹⁾
viii)
Storage (H)
30.0
¹⁾
ix)
Hazardous (J)
22.5
¹⁾
NOTES
1 For fully sprinklered building, the travel distance may be increased by 50 percent of the values specified.
2 Ramps shall be protected with automatic sprinkler system and shall be counted as one of the means of escape. ¹⁾ Construction of type 3 or 4 is not permitted.
4.6Number of Exits
4.6.1 General
The general requirements of number of exits shall supplement the requirement of different occupancies in 6.1 to 6.9.
4.6.2 All buildings, which are 15 m in height or above, and all buildings used as educational, assembly, institutional, industrial, storage, and hazardous occupancies and mixed occupancies with any of the aforesaid occupancies, having area more than 500 m2 on each floor shall have a minimum of two staircases. They shall be of enclosed type; at least one of them shall be on external walls of buildings and shall open directly to the exterior, interior open space or to an open place of safety. Further, the provision or otherwise of alternative staircases shall be subject to the requirements of travel distance being complied with.
4.7Doorways
4.7.1 Every exit doorway shall open into an enclosed stairway or a horizontal exit of a corridor or passageway providing continuous and protected means of egress.
4.7.2 No exit doorway shall be less than 1 000 mm in width except assembly buildings where door width shall be not less than 2 000 mm. Doorways shall be not less than 2 000 mm in height.
4.7.3 Exit doorways shall open outwards, that is, away from the room, but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 900 mm; overhead or sliding doors shall not be installed.
NOTE — In the case of buildings where there is a central corridor, the doors of rooms shall open inwards to permit smooth flow of traffic in the corridor.
4.7.4 Exit door shall not open immediately upon a flight of stairs; a landing equal to at least the width of the door shall be provided in the stairway at each doorway; the level of landing shall be the same as that of the floor which it serves.
4.7.5 Exit doorways shall be openable from the side which they serve without the use of a key.
4.7.6 Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
4.8 Corridors and Passageways
4.8.1 Exit corridors and passageways shall be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.
4.8.2 Where stairways discharge through corridors and passageways, the height of corridors and passageways shall be not less than 2.4 m.
4.8.3 All means of exit including staircases lifts lobbies and corridors shall be adequately ventilated.
4.9Internal Staircases
4.9.1 Internal stairs shall be constructed of non-combustible materials throughout.
4.9.2 Internal stairs shall be constructed as a self-contained unit with an external wall of the building constituting at least one of its sides and shall be completely enclosed.
4.9.3 A staircase shall not be arranged round a lift shaft.
4.9.4 Hollow combustible construction shall not be permitted.
4.9.5 No gas piping or electrical panels shall be allowed in the stairway. Ducting in stairway may be permitted if it is of 1 h fire resistance rating.
4.9.6 Notwithstanding the detailed provision for exits in accordance with 4.3, 4.4 and 4.5, the following minimum width shall be provided for staircases:
a) Residential buildings (dwellings) 1.0 m
b) Residential hotel buildings 1.5 m
c) Assembly buildings like auditorium, 2.0 m theatres and cinemas
d) Educational buildings up to 30 m in 1.5 m height
e) Institutional buildings like hospitals 2.0 m
f) All other buildings 1.5 m
4.9.7 The minimum width of tread without nosing shall be 250 mm for internal staircase of residential buildings. This shall be 300 mm for assembly, hotels, educational, institutional, business and other buildings. The treads shall be constructed and maintained in a manner to prevent slipping.
4.9.8 The maximum height of riser shall be 190 mm for residential buildings and 150 mm for other buildings and the number shall be limited to 15 per flight.
4.9.9 Handrails shall be provided at a height of 1 000 mm to be measured from the base of the middle of the treads to the top of the handrails. Balusters/railing shall be provided such that the width of staircase does not reduce (see Fig. 1).
4.9.10 The number of people in between floor landings in staircase shall not be less than the population on each floor for the purpose of design of staircase. The design of staircase shall also take into account the following:
a) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
b) For building 15 m in height or more, access to main staircase shall be through a fire/smoke check door of a minimum 2 h fire resistance rating. Fire resistance rating may be reduced to 1 h for residential buildings (except hotels and starred hotels).
c) No living space, store or other fire risk shall open directly into the staircase or staircases.
d) External exit door of staircase enclosure at ground level shall open directly to the open spaces or through a large lobby, if necessary.
4.11External Stairs
An external staircase is desirable to be provided for high rise buildings.
External stairs, when provided shall comply the following:
4.11.1 External stairs shall always be kept in sound operable conditions.
4.11.2 All external stairs shall be directly connected to the ground.
4.11.3 Entrance to the external stairs shall be separate and remote from the internal staircase.
4.11.4 Care shall be taken to ensure that no wall opening or window opens on to or close to an external stairs.
4.11.5 The route to the external stairs shall be free of obstructions at all times.
4.11.6 The external stairs shall be constructed of non-combustible materials, and any doorway leading to it shall have the required fire resistance.
4.11.7 No external staircase, used as a fire escape, shall be inclined at an angle greater than 45° from the horizontal.
4.11.8 External stairs shall have straight flight not less than 1 250 mm wide with 250 mm treads and risers not more than 190 mm. The number of risers shall be limited to 15 per flight.
4.11.9 Handrails shall be of a height not less than 1 000 mm and not exceeding 1 200 mm. There shall be provisions of balusters with maximum gap of 150 mm.
4.11.10 The use of spiral staircase shall be limited to low occupant load and to a building not exceeding 9 m in height.
A spiral stair case shall be not less than 1 500 mm in diameter and shall be designed to give adequate headroom.
4.11.11 Unprotected steel frame staircase will not be accepted as means of escape. However, steel staircase in an enclosed fire rated compartment of 2 h will be accepted as means of escape.
c) Sub-division A-3 Dormitories — These shall include any building in which group sleeping accommodation is provided, with or without dining facilities for persons who are not members of the same family, in one room or a series of closely associated rooms under joint occupancy and single management, for example, school and college dormitories, students, and other hostels and military barracks.
These shall include any building or structure in which living quarters are provided for three or more families, living independently of each other and with independent cooking facilities, for example, apartment houses, mansions and chawls.
Sub-division A-5 Hotels — These shall include any building or group of buildings under single management, in which sleeping accommodation is provided, with or without dining facilities for hotels classified up to 4 Star Category.
f) Sub-division A-6 Hotels (starred) — These shall include the hotels duly approved by the concerned authorities as Five Star and above Hotels.
3.1.3 Group B Educational Buildings
These shall include any building used for school, college, other training institutions for day-care purposes involving assembly for instruction, education or recreation for not less than 20 students.
Buildings and structures under Group B shall be further sub-divided as follows:
Sub-division B-1 Schools up to senior secondary level
Sub-division B-2 All others/training institutions
a) Sub-division B-1 Schools up to senior secondary level — This sub-division shall include any building or a group of buildings under single management which is used for students not less than 20 in number.
b) Sub-division B-2 All others/training institutions — This sub-division shall include any building or a group of buildings under single management which is used for students not less than 100 in number.
In the case of temporary buildings/structures which are utilized for educational purposes, the provisions of 3.2.5.3 shall apply.
If residential accommodation is provided in the schools/institutions, that portion of occupancy shall be classified as a building in sub-division A-3.
3.1.4 Group C Institutional Buildings
These shall include any building or part thereof, which is used for purposes, such as medical or other treatment or care of persons suffering from physical or mental illness, disease or infirmity; care of infants, convalescents or aged persons and for penal or correctional detention in which the liberty of the inmates is restricted. Institutional buildings ordinarily provide sleeping accommodation for the occupants.
Buildings and structures under Group C shall be further sub-divided as follows:
Sub-division C-1 Hospitals and sanatoria
Sub-division C-2 Custodial institutions
Sub-division C-3 Penal and mental institutions
a) Sub-division C-1 Hospitals and sanatoria — This sub-division shall include any building or a group of buildings under single management, which is used for housing persons suffering from physical limitations because of health or age, for example, hospitals, infirmaries, sanatoria and nursing homes.
b) Sub-division C-2 Custodial institutions — This sub-division shall include any building or a group of buildings under single management, which is used for the custody and care of persons, such as children, convalescents and the aged, for example, homes for the aged and infirm, convalescent homes and orphanages.
c) Sub-division C-3 Penal and mental institutions — This sub-division shall include any building or a group of buildings under single management, which is used for housing persons under restraint, or who are detained for penal or corrective purposes, in which the liberty of the inmates is restricted, for example, jails, prisons, mental hospitals, mental sanatoria and reformatories.
3.1.5 Group D Assembly Buildings
These shall include any building or part of a building, where number of persons not less than 50 congregate or gather for amusement, recreation, social, religious, patriotic, civil, travel and similar purposes, for example, theatres, motion picture houses, assembly halls, auditoria, exhibition halls, museums, skating rinks, gymnasiums, restaurants, places of worship, dance halls, club rooms, passenger stations and terminals of air, surface and marine public transportation services, recreation piers and stadia, etc.
Buildings under Group D shall be further sub-divided as follows:
Sub-division D-1 Buildings having a theatrical or motion picture or any other stage and fixed seats for over 1 000 persons
Sub-division D-2 Buildings having a theatrical or motion picture or any other stage and fixed seats upto 1 000 persons
Sub-division D-3 Buildings without a permanent stage having accommodation for 300 or more persons but no permanent seating arrangement.
Sub-division D-4 Buildings without a permanent stage having accommodation for less than 300 persons with no permanent seating arrangement.
Sub-division D-5 All other structures including temporary structures designed for assembly of people not covered by sub-divisions D-1 to D-4, at ground level.
Sub-division D-6 Buildings having mixed occupancies providing facilities such as shopping, cinema theatres, and restaurants.
Sub-division D-7 All other structures, elevated or underground, for assembly of people not covered by sub-divisions D-1 to D-6.
a) Sub-division D-1 — This sub-division shall
include any building primarily meant for theatrical or operatic performances and exhibitions and which has a raised stage, proscenium curtain, fixed or portable scenery or scenery loft, lights, motion picture houses, mechanical appliances or other theatrical accessories and equipment and which is provided with fixed seats for over 1 000 persons.
Sub-division D-2 — This sub-division shall include any building primarily meant for use as described for sub-division D-1, but with fixed seats up to 1 000 persons.
c) Sub-division D-3 — This sub-division shall include any building, its lobbies, rooms and other spaces connected thereto, primarily intended for assembly of people, but which has no theatrical stage or permanent theatrical and/or cinematographic accessories and has accommodation for 300 persons or more, for example, dance halls, night clubs, halls for incidental picture shows, dramatic, theatrical or educational presentation, lectures or other similar purposes having no theatrical stage except a raised platform and used without permanent seating arrangement; art galleries exhibition halls, community halls, marriage halls, places of worship, museums, lecture halls, passenger terminals and Heritage and Archeological Monuments.
d) Sub-division D-4 — This sub-division shall include any building primarily intended for use as described in sub-division D-3, but with accommodation for less than 300 persons with no permanent seating arrangements.
e) Sub-division D-5 — This sub-division shall include any building or structure permanent or temporary meant for assembly of people not covered by sub-divisions D-1 to D-4, for example, grandstands, stadia, amusement park structures, reviewing stands and circus tents.
f) Sub-division D-6 — This sub-division shall include any building for assembly of people provided with multiple services/facilities like shopping, cinema theatres and restaurants, for example, multiplexes.
g) Sub-division D-7 — This sub-division shall include any building or structure permanent or temporary meant for assembly of people not covered by D-1 to D-6, for example, underground or elevated railways.
3.1.6 Group E Business Buildings
These shall include any building or part of a building which is used for transaction of business (other than that covered by Group F and part of buildings covered
by 3.1.1.1); for keeping of accounts and records and similar purposes, professional establishments, service facilities, etc. City halls, town halls, court houses and libraries shall be classified in this group so far as the principal function of these is transaction of public business and keeping of books and records.
Business buildings shall be further sub-divided as follows:
Sub-division E-1 Offices, banks, professional establishments, like offices of architects, engineers, doctors, lawyers and police stations.
Sub-division E-2 Laboratories, research establishments, libraries and test houses.
Sub-division E-3 Computer installations.
Sub-division E-4 Telephone exchanges.
Sub-division E-5 Broadcasting stations and T.V. stations.
3.1.7 Group F Mercantile Buildings
These shall include any building or part of a building, which is used as shops, stores, market, for display and sale of merchandise, either wholesale or retail.
Mercantile buildings shall be further sub-divided as follows:
Sub-division F-1 Shops, stores, departmental stores markets with area up to 500 m2.
Sub-division F-2 Shops, stores, departmental stores markets with area more than 500 m2.
Sub-division F-3 Underground shopping centres. Storage and service facilities incidental to the sale of merchandise and located in the same building shall be included under this group.
3.1.8 Group G Industrial Buildings
These shall include any building or part of a building or structure, in which products or materials of all kinds and properties are fabricated, assembled, manufactured or processed, for example, assembly plants, industrial laboratories, dry cleaning plants, power plants, generating units, pumping stations, fumigation chambers, laundries, buildings or structures in gas plants, refineries, dairies and saw-mills, etc.
Buildings under Group G shall be further sub-divided as follows:
Sub-division G-1 Buildings used for low hazard industries.
Sub-division G-2 Buildings used for moderate hazard industries.
Sub-division G-3 Buildings used for high hazard industries.
The hazard of occupancy, for the purpose of the Code, shall be the relative danger of the start and spread of
fire, the danger of smoke or gases generated, the danger of explosion or other occurrences potentially endangering the lives and safety of the occupants of the buildings.
Hazard of occupancy shall be determined by the Authority on the basis of the fire loads of the contents, and the processes or operations conducted in the building, provided, however, that where the combustibility of the material, the flame spread rating of the interior finish or other features of the building or structure are such as to involve a hazard greater than the occupancy hazard, the greater degree of hazard shall govern the classification.
For determination of fire loads and fire load density for arriving at the classification of occupancy hazard, guidance including the calorific values of some common materials, is given at Annex A.
A broad classification of industrial and non-industrial occupancies into low, moderate and high hazard classes is given at Annex B, for guidance. Any occupancy not covered in Annex B, shall be classified in the most appropriate class depending on the degree of hazard.
Where different degrees of hazard of occupancy exist in different parts of a building, the most hazardous of those shall govern the classification for the purpose of this Code, except in cases where hazardous areas are segregated or protected as specified in the Code.
a) Sub-division G-1 — This sub-division shall include any building in which the contents are of such comparative low combustibility and the industrial processes or operations conducted therein are of such a nature that there are hardly any possibilities for any self propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source.
b) Sub-division G-2 — This sub-division shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity or result in other hazardous situation and may give off a considerable volume of smoke, but from which neither toxic fumes nor explosions are to be feared in the event of fire.
c) Sub-division G-3 — This sub-division shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with extreme rapidity or result in other hazardous situation or from which poisonous fumes or explosions are to be feared in the event of a fire. For fire safety in petroleum and fertilizer plant, good practice [4(3)] may be referred.
3.1.9 Group H Storage Buildings
These shall include any building or part of a building used primarily for the storage or sheltering (including servicing, processing or repairs incidental to storage) of goods, ware or merchandise (except those that involve highly combustible or explosive products or materials) vehicles or animals, for example, warehouses, cold storage, freight depots, transit sheds, storehouses, truck and marine terminals, garages, hangers, grain elevators, barns and stables. Storage properties are characterized by the presence of relatively small number of persons in proportion to the area. Any new use which increase the number of occupants to a figure comparable with other classes of occupancy shall change the classification of the building to that of the new use, for example, hangars used for assembly purposes, warehouses used for office purposes, garage buildings used for manufacturing.
3.1.10 Group J Hazardous Buildings
These shall include any building or part of a building which is used for the storage, handling, manufacture or processing of highly combustible or explosive materials or products which are liable to burn with extreme rapidity and or which may produce poisonous fumes or explosions for storage, handling, manufacturing or processing which involve highly corrosive, toxic or noxious alkalis, acids or other liquids or chemicals producing flame, fumes and explosive, poisonous, irritant or corrosive gases; and for the storage, handling or processing of any material producing explosive mixtures of dust which result in the division of matter into fine particles subject to spontaneous ignition. Examples of buildings in this class are those buildings which are used for:
a) Storage, under pressure of more than 0.1 N/mm2 and in quantities exceeding 70 m3, of acetylene, hydrogen, illuminating and natural gases, ammonia, chlorine, phosgene, sulphur dioxide, carbon dioxide, methyloxide and all gases subject to explosion, fume or toxic hazard, cryogenic gases, etc;
b) Storage and handling of hazardous and highly flammable liquids, liquefiable gases like LPG, rocket propellants, etc;
c) Storage and handling of hazardous and highly flammable or explosive materials (other than liquids); and
d) Manufacture of artificial flowers, synthetic leather, ammunition, explosives and fireworks. NOTE — A list of hazardous substances giving quantities, for which or exceeding which owners handling such substances are required to be covered under the Public Liability Insurance Act, has been notified under Government of India, Ministry of Environment and Forests Notification No. G.S.R. 347(E) dated 1 August 1996.
3.1.11 Any building not covered by Annex B or 3.1.8 shall be classified in the group which most nearly resembles its existing or proposed use.
3.1.12 Where change in the occupancy of any building places it in a different group or in a different subdivision of the same group, such building shall be made to comply with the requirements of the Code for the new group or its sub-division.
3.1.13 Where the new occupancy of a building is less hazardous, based on life and fire risk, than its existing occupancy, it shall not be necessary to conform to the requirements of the Code for the new group or its subdivision.
3.1.14 A certificate of occupancy shall be necessary, as required under Part 2 ‘Administration’, before any change is effected in the character of occupancy of any building.
d) watchman’s booth, pumphouse, garbage shaft, electric cabin or sub-stations, and such other utility structures meant for the services of the building under consideration.
NOTE — For the purpose of this Part, covered area equals the plot area minus the area due for open spaces in the plot.
2.7 Down-comer — An arrangement of fire fighting within the building by means of down-comer pipe connected to terrace tank through terrace pump, gate valve and non-return valve and having mains not less than 100 mm internal diameter with landing valves on each floor/landing. It is also fitted with inlet connections at ground level for charging with water by pumping from fire service appliances and air release valve at roof level to release trapped air inside.
2.8 Dry Riser — An arrangement of fire fighting within the building by means of vertical rising mains not less than 100 mm internal diameter with landing valves on each floor/landing which is normally dry but is capable of being charged with water usually by pumping from fire service appliances.
2.9 Emergency Lighting — Lighting provided for use when the supply to the normal lighting fails.
2.10 Emergency Lighting System — A complete but discrete emergency lighting installation from the standby power source to the emergency lighting lamp(s), for example, self-contained emergency luminaire or a circuit from central battery generator connected through wiring to several escape luminaries.
2.11 Escape Lighting — That part of emergency lighting which is provided to ensure that the escape route is illuminated at all material times, for example, at all times when persons are on the premises, or at times the main lighting is not available, either for the whole building or for the escape routes.
2.12 Fire Door — A fire-resistive door approved for openings in fire separation.
2.13 Fire Exit — A way out leading to an escape route having panic bar hardware provided on the door.
2.14 Fire Lift — The lift installed to enable fire services personnel to reach different floors with minimum delay, having such features as required in accordance with this Part.
2.15 Fire Load — Calorific energy, of the whole contents contained in a space, including the facings of the walls, partitions, floors and ceilings.
2.16 Fire Load Density — Fire load divided by floor area.
2.17 Fire Resistance Rating — The time that a material or construction will withstand the standard fire exposure as determined by fire test done in accordance with the standard methods of fire tests of materials/structures.
2.18 Fire Resistance — Fire resistance is a property of an element of building construction and is the measure of its ability to satisfy for a stated period some or all of the following criteria:
a) resistance to collapse,
b) resistance to penetration of flame and hot gases, and
c) resistance to temperature rise on the unexposed face up to a maximum of 180°C and/or average temperature of 150°C.
2.19 Fire Separation — The distance in metres measured from the external wall of the building concerned to the external wall of any other building on the site, or from other site, or from the opposite side of street or other public space for the purpose of preventing the spread of fire.
2.20 Fire Separating Wall — The wall provides complete separation of one building from another or part of a building from another or part of a building from another part of the same building to prevent any communication of fire or heat transmission to wall itself which may cause or assist in the combustion of materials on the side opposite to that portion which may be on fire.
2.21 Fire Stop — A fire resistant material, or construction, having a fire resistance rating of not lesss than the fire separating elements, installed in concealed spaces or between structural elements of a building to prevent the spread/propagation of fire and smoke through walls, ceilings and like as per the laid down criteria.
2.22 Fire Tower — An enclosed staircase which can only be approached from the various floors through landings or lobbies separated from both the floor areas
and the staircase by fire-resisting doors, and open to the outer air.
2.23 Fire Resisting Wall — A fire resistance rated wall, having protected openings, which restricts the spread of fire and extends continuously from the foundation to at least 1 m above the roof.
2.24 Floor Area Ratio (FAR) — The quotient obtained by dividing the total covered area (plinth area) on all floors by the area of the plot:
FAR=Plot areaTotal covered area of all floors
2.25 High Rise Building — For the purpose of this Part, all buildings 15 m or above in height shall be considered as high rise buildings.
2.26 Horizontal Exit — An arrangement which allows alternative egress from a floor area to another floor at or near the same level in an adjoining building or an adjoining part of the same building with adequate fire separation.
2.27 Means of Egress — A continuous and unobstructed way of travel from any point in a building or structure to a place of comparative safety.
2.28 Occupancy or Use Group — The principal occupancy for which a building or a part of a building is used or intended to be used; for the purpose of classification of a building according to the occupancy, an occupancy shall be deemed to include subsidiary occupancies which are contingent upon it.
2.29 Plinth Area — The built-up covered area measured at the floor level of the basement or of any storey.
2.30 Pressurization — The establishment of a pressure difference across a barrier to protect a stairway, lobby, escape route or room of a building from smoke penetration.
2.31 Pressurization Level — The pressure difference between the pressurized space and the area served by the pressurized escape route, expressed in pascals (Pa).
2.32 Roof Exits — A means of escape on to the roof of a building, where the roof has access to it from the ground. The exit shall have adequate cut-off within the building from staircase below.
2.33 Site Plot — A parcel (piece) of land enclosed by definite boundaries.
2.34 Stack Pressure — Pressure difference caused by a temperature difference creating an air movement within a duct, chimney or enclosure.
2.35 Travel Distance — The distance to be travelled from any point in a building to a protected escape route, external escape route or final exit.
e)
2.36 Ventilation — Supply of outside air into, or the removal of inside air from an enclosed space.
2.37 Venting Fire — The process of inducing heat and smoke to leave a building as quickly as possible by such paths that lateral spread of fire and heat is checked, fire fighting operations are facilitated and minimum fire damage is caused.
2.38 Volume to Plot Area Ratio (VPR) — The ratio of volume of building measured in cubic metres to the area of the plot measured in square metres and expressed in metres.
2.39 Wet Riser — An arrangement for fire fighting within the building by means of vertical rising mains not less than 100 mm nominal diameter with landing valves on each floor/landing for fire fighting purposes and permanently charged with water from a pressurized supply.
NOTE — For definitions of other terms, reference shall be made to good practice [4(2)].
3.2.5.1 Temporary buildings and structures shall be permitted only in Fire Zones No. 1 and 2 as the case may be, according to the purpose for which these are to be used, by special permit from the Authority for a limited period and subject to such conditions as may be imposed in the permit.
3.2.5.2 Such buildings and temporary structures shall be completely removed on the expiry of the period specified in the permit.
3.2.5.3 Adequate fire precautionary measures in the construction of temporary structures and PANDALS shall be taken in accordance with good practice [4(4)].
3.2.6 Restrictions on the Type of Construction for New Buildings
3.2.6.1 Buildings erected in Fire Zone No. 1 shall conform to construction of Type 1, 2, 3 or 4.
3.2.6.2 Buildings erected in Fire Zone No. 2 shall conform to construction of Type 1, 2 or 3.
3.2.6.3 Buildings erected in Fire Zone No. 3 shall conform to construction of Type 1 or 2.
3.2.7 Restrictions on Existing Buildings
The existing buildings in any fire zone shall not be required to comply with the requirement of the Code unless these are altered, or in the opinion of the Authority, such building constitutes a hazard to the safety of the adjacent property or the occupants of the building itself or is an unsafe building. In the event of alteration, it shall be necessary to obtain permission of the Authority for such alteration consistent with fire hazard (see Part 2 ‘Administration’).
Alterations/modifications/renovations shall be accomplished so as to ensure conformity with all the
safety requirements of the new buildings. Such alterations shall not in anyway bring down level of fire and life safety below that which existed earlier. Any addition or alterations or construction of cubicles or partitioning for floor area exceeding 500 m2 for all high rise buildings shall be with approval of local fire authority.
i) Exterior walls:
a) Fire separation less than 3.7 m
a) Bearing
4
2
2
1
b) Non-bearing
2
1(1)/(2)
1
1
b) Fire separation of 3.7 m or more but less than 9 m
a) Bearing
4
2
2
1
b) Non-bearing
1(1)/(2)
1
1
1
c) Fire separation of 9 m or more
a) Bearing
4
2
2
1
b) Non-bearing
1
1
1
1
ii) Fire resisting walls
4
2
2
2
iii) Fire separation assemblies (like fire check doors)
4
2
2
2
iv) Fire enclosures of exitways, hallways and stairways
2
2
2
2
v) Shaft other than exitways, elevator and hoistways
2
2
2
2
vi) Exitway access corridors
1
1
1
1
vii) Vertical separation of tenant spaces
1
1
1
1
viii) Dwelling unit separation
1
1
1
1
Non-load bearing partitions
— At least half an hour —
ix) Interior bearing walls, bearing partitions, columns, girders, trusses (other than roof trusses) and framing
a) Supporting more than one floor
4
2
2
2
b) Supporting one floor only
3
1(1)/(2)
1
1
c) Supporting a roof only
3
1(1)/(2)
1
1
x) Structural members support walls
3
1(1)/(2)
1
1
xi) Floor construction including walls
3
1(1)/(2)
1
1
xii) Roof construction
a) 5 m or less in height to lowest member
2
1(1)/(2)
1
1
b) More than 5 m but less than 6.7 m in height to lowest member
1
1
1
1
c) 6.7 m or more in height to lowest member
0
0
0
0
Table 2Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (Hours) of
Load Bearing
Non-load Bearing
1(3)
1(1)/(2) (4)
2(5)
3(6)
4(7)
1(8)
1(1)/(2) (9)
2(10)
3(11)
4(12)
i)
Reinforced ¹⁾ cement concrete
120 (25)²⁾
140 (25)²⁾
160 (25)²⁾
200 (25)²⁾
240 (25)²⁾
ii)
Unreinforced cement concrete
150
175
—
—
—
iii)
No-fines concrete with :
a) 13 mm cement/sand or gypsum/sand
—
—
—
—
—
150
150
150
150
150
b) 13 mm light weight aggregate gypsum plaster
—
—
—
—
—
150
150
150
150
150
iv)
Bricks of clay:
a) Without finish
90
100
100
170
170
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
75
90
90
90
100
v)
Bricks of sand lime:
a) Without finish
90
100
100
190
190
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
75
90
90
90
100
vi)
Blocks of concrete:
a) Without finish
90
100
100
—
—
75
90
100
140
150
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
75
75
75
90
100
c) With 13 mm cement/sand or gypsum/ sand
75
90
90
100
140
vii)
Blocks of lightweight concrete:
a) Without finish
90
100
100
140
150
75
75
75
125
140
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
50
63
75
75
75
c) With 13 mm cement/sand or gypsum/ sand
—
—
—
—
—
75
75
75
90
100
viii)
Blocks of aerated concrete:
a) Without finish
90
100
100
140
180
50
63
63
75
100
b) With 13 mm lightweight aggregate gypsum plaster
90
90
100
100
150
Walls containing at least 1 percent of vertical reinforcement.
Minimum thickness of actual cover to reinforcement.
Table 3Masonry Walls: Hollow (Required to Resist Fire from One Side at a Time) (Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (Hours) of
Load Bearing
Non-load Bearing
1
1(1)/(2)
2
3
4
(1)/(2)
1
1(1)/(2)
2
3
4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
i)
Bricks of clay:
a) Without finish
170
170
170
200
200
75
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
100
100
170
170
170
75
75
90
90
90
100
ii)
Blocks of concrete:
a) Without finish
90
125
125
140
140
150
b) With 13 mm cement/sand or gypsum/sand
190
200
200
—
—
90
125
125
140
140
140
c) With 13 mm lightweight aggregate gypsum plaster
75
90
90
100
125
125
iii)
Blocks of lightweight concrete:
a) Without finish
100
100
100
—
—
75
90
90
100
140
150
b) With 13 mm cement/sand or gypsum/sand
—
—
—
—
—
75
75
75
100
140
140
c) With 13 mm lightweight aggregate gypsum plaster
—
—
—
—
—
63
63
63
75
90
100
Table 4Framed Construction, Load Bearing (Required to Resist Fire from One Side at a Time) (Clause 3.3.2)
Sl Nature of Construction and Materials/Timber Studs at Centres not Minimum Thickness (mm) of Protection No. Exceeding 600 mm, Faced on Each Side with for a Fire Resistance of 1h(1) (2) (3)
i) Plasterboard layers with joints staggered, joints in outer layer taped and filled - Total 25 thickness for each face ii) One layer of 12.7 mm plasterboard with a finish of lightweight aggregate gypsum 13 plaster iii) Metal lath and plaster, thickness of plaster: a) Sanded gypsum plaster (metal lathing grade) 22 b) Lightweight aggregate gypsum plaster 13
Table 5 Framed Construction, Non-Load Bearing (Required to Resist Fire from One Side at a Time)
(Clause 3.3.2)
Nature of Construction and Materials/Steel or Timber Frame at Centres not Exceeding 600 mm, Facings on Both Sides of
Stud Construction
Minimum Thickness (mm) of Protection for a Fire Resistance
(1)/(2)h
1 h
1(1)/(2)h
2 h
(1)
(2)
(3)
(4)
(5)
(6)
A) Dry lining with materials fixed direct to studs (without plaster finish)
1. One layer of plasterboard with taped and filled joints
Timber or steel
12.7
2. Two layers of plasterboard with joints staggered, joints in outer layer taped and filled — Total thickness for each face
Timber or steel
19
25
3. One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber
Timber or steel
9
12
4. One layer of wood wool slabs
Timber
25
5. One layer of chipboard or of plywood
Timber or steel
18
B) Lining with materials fixed direct to suds, with plaster finish:
Plasterboard of thickness:
Timber or steel
a) With not less than 5 mm gypsum plaster finish
9.5
b) With not less than 13 mm gypsum plaster finish
12.7
C) Wet finish:
Metal lath and plaster, thickness of plaster:
a) Sanded gypsum plaster
Timber or steel
13
b) Lightweight aggregate gypsum plaster
Timber
13
19
25
Steel
13
Table 6Framed External Walls Load Bearing (Required to Resist Fire from One Side at a Time)
Sl Nature of Construction and Materials Minimum Thickness (mm) of Protection No. for a Fire Resistance of 1 h(1) (2) (3)
Timber studs at centers not exceeding 600 mm with internal linings of : i) Plasterboard layers with joints in outer layer taped and filled, total thickness of 25 plasterboard
Table 7Framed External Walls Non-Load Bearing Required to Resist Fire only from Inside the Building (A) (Clause 3.3.2)
Nature of Construction and Materials
Mini ½ h
mum Th 1 h
ickness (Fire Re 1½ h
mm) of Pr sistance 2 h
otection 3 h
for a 4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Steel frame with an external cladding of non-combustible sheets (excluding
sheet steel), with a steel supporting framework and internal lining of:
1. Metal lath and plaster, thickness of plaster:
a) Sanded gypsum plaster (metal lathing grade)
13
13
b) Lightweight aggregate gypsum plaster
10
13
15
15
15
19
2. Two layer of plasterboard with joints staggered joints in outer layer
21
32
taped and filled - Total thickness
3. Plasterboard of thickness:
a) With not less than 5 mm gypsum plaster finish
12.7
b) With not less than 13 mm gypsum plaster finish
9.5
c) With not less than 10 mm lightweight aggregate gypsum plaster
9.5
4. One layer of asbestos insulating board with transverse joints backed by
9
9
12
12
12
12
fillers of asbestos insulating board not less than 9 mm thick, or by timber
5. One layer of wood/wool slabs without finish
50
6. One layer of compressed straw building slabs:
a) Without finish
50
b) With not less than 5 mm gypsum plaster finish
50
7. Aerated concrete blocks
50
50
63
63
75
100
8. Bricks of clay:
a) Without finish
75
75
90
90
100
100
b) With not less than 13 mm lightweight aggregate gypsum plaster
75
75
90
90
Table 8Framed External Walls Non-Load Bearing Required to Resist Fire only from Inside the Building (B) (Clause 3.3.2)
N Naattuurree o off C Coonnssttrruuccttiioonn a anndd M Maatteerriiaallss
M Miinniimmuumm T Thhiicckknneessss ( (mmmm)) o off P Prrootteeccttiioonn t too P Prroovviiddee S Suuffffiicciieenntt I Innssuullaattiioonn t too A Acchhiieevvee a a M Mooddiiffiieedd F Fiirree R Reessiissttaannccee o off U Upp t too 4 4 h h
( (11))
( (22))
S Stteeeell f frraammee w wiitthh a ann e exxtteerrnnaall c cllaaddddiinngg o off s shheeeett s stteeeell f fuullllyy l laappppeedd,, s stteeeell b boolltteedd a anndd
f fiixxeedd t too s stteeeell s shheeeettiinngg r raaiillss,, w wiitthh t tiimmbbeerr o orr s stteeeell s suuppppoorrttiinngg f frraammeewwoorrkk a anndd i inntteerrnnaall
l liinniinngg o off::
1 1.. M Meettaall l laatthh a anndd p pllaasstteerr,, t thhiicckknneessss o off p pllaasstteerr::
a a)) S Saannddeedd g gyyppssuumm p pllaasstteerr ( (mmeettaall l laatthhiinngg g grraaddee))
1 133
b b)) L Liigghhttwweeiigghhtt a aggggrreeggaattee g gyyppssuumm p pllaasstteerr
1 100
2 2.. O Onnee l laayyeerr o off p pllaasstteerrbbooaarrdd w wiitthh j jooiinnttss t taappeedd a anndd f fiilllleedd
1 122..77
3 3.. P Pllaasstteerrbbooaarrdd o off t thhiicckknneessss w wiitthh n noott l leessss t thhaann 5 5 m mmm g gyyppssuumm p pllaasstteerr f fiinniisshh
9 9..55
4 4.. O Onnee l laayyeerr o off a assbbeessttooss i innssuullaattiinngg b booaarrdd w wiitthh t trraannssvveerrssee j jooiinnttss b baacckkeedd b byy
9 9
f fiilllleerrss o off a assbbeessttooss i innssuullaattiinngg b booaarrdd n noott l leessss t thhaann 9 9 m mmm t thhiicckk,, o orr b byy t tiimmbbeerr
5 5.. O Onnee l laayyeerr o off w woooodd//wwooooll s sllaabbss
2 255
6 6.. O Onnee l laayyeerr o off c coommpprreesssseedd s sttrraaww b buuiillddiinngg s sllaabbss
5 500
7 7.. O Onnee l laayyeerr o off c chhiippbbooaarrdd o orr o off p pllyywwoooodd
1 188
8 8.. A Aeerraatteedd c coonnccrreettee b blloocckkss
5 500
9 9.. B Brriicckkss o off c cllaayy
7 755
1 100.. A Annyy i inntteerrnnaall d deeccoorraattiivvee l liinniinngg w wiitthh a a c caavviittyy f fiillll i innddeeppeennddeennttllyy s suuppppoorrtteedd
5500
a anndd r reettaaiinneedd i inn p poossiittiioonn o off m miinneerraall f fiibbrree i innssuullaattiinngg m maatteerriiaall ( (eexxcclluuddiinngg
g <sub>g</sub>l<sub>l</sub>a<sub>a</sub>s<sub>s</sub>s<sub>s</sub>)) a att a a d deennssiittyy o off 4 488 k kgg//mm<sup>33</sup>
Table 9Framed Walls Non-Load Bearing Required to Resist Fire only from Inside the Building (C) (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of 1½ h
(1)
(2)
Timber frame with external cladding of weather boarding or external plywood,
9.5 mm with an internal lining of:
1. Plasterboard not less than 9.5 mm thick, finished with:
a) Gypsum plaster
13
b) Lightweight aggregate gypsum plaster
10
2. Plasterboard not less than 12.7 mm thick, finished with:
a) Gypsum plaster
10
b) Lightweight aggregate gypsum plaster
10
3. One layer of asbestos insulating board with transverse joints backed by fillers
9
of asbestos insulating board not less than 9 mm thick, or by timber
12
Table 10 Reinforced Concrete Columns
(Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h
1 h
1(1)/(2)h
2 h
3 h
4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Fully exposed
Width
150
200
250
300
400
450
Cover
40
40
40
40
40
40
ii)
50 percent exposed
Width
125
160
200
200
300
350
Cover
40
40
40
40
40
40
iii)
One face exposed
Thickness
100
120
140
160
200
240
Cover
40
40
40
40
40
40
Table 11 Concrete Beams
(Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h
1 h
1(1)/(2)h
2 h
3 h
4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Reinforced concrete (simply supported)
Width
200
200
200
200
240
280
Cover
20
20
20
40
60¹⁾
70¹⁾
ii)
Reinforced concrete (continuous)
Width
200
200
200
200
240
280
Cover
20
20
20
30
40
50¹⁾
iii)
Prestressed concrete (simply supported)
Width
100
120
150
200
240
280
Cover
25
40
55
70
80
90
iv)
Prestressed concrete (continuous)
Width
80
100
120
150
200
240
Cover
20
30
40
55
70
80
Require attention to the additional measures necessary to reduce the risk of spalling.
Table 12 Concrete Floors(Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h (3)
1 h(4)
1(1)/(2)h (5)
2 h(6)
3 h(7)
4 h(8)
i)
Reinforced concrete (simply supported)
Thickness
75
95
110
125
150
170
Cover
20
20
25
35
45¹⁾
55¹⁾
ii)
Reinforced concrete (continuous)
Thickness
75
95
110
125
150
170
Cover
20
20
20
25
35
45¹⁾
Require attention to the additional measures necessary to reduce the risk of spalling.
Table 13Concrete Floors: Ribbed Open Soffit (Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h
1 h
1(1)/(2)h
2 h
3 h
4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Reinforced concrete (simply supported)
Thickness of floor
75
95
110
125
150
170
Rib width
125
125
125
125
150
175
Cover
20
20
35
45
55
65
ii)
Reinforced concrete (continuous)
Thickness
75
95
110
125
150
170
Width
125
125
125
125
150
175
Cover
20
20
20
35
45
55
Table 14Encased Steel Columns, 203 mm × 203 mm (Protection Applied on Four Sides) (Clause 3.3.2)
Nature of Construction and Materials
Minimu 1 h
m Dimensio for a F 1½ h
ns (mm) E ire Resista 2 h
xcluding an nce of 3 h
y Finish, 4 h
(1)
(2)
(3)
(4)
(5)
(6)
A) Hollow protection (without an air cavity over the flanges):
1. <sup>1</sup>) Metal lathing with trowelled lightweight aggregate gypsum plaster
13
15
20
32
2. Plasterboard with 1.6 mm wire binding at 100 mm pitch, finished with
lightweight aggregate gypsum plaster not less than the thickness
specified:
a) 9.5 mm plaster board
10
15
b) 19 mm plaster board
10
13
20
3. Asbestos insulating boards, thickness of board:
a) Single thickness of board, with 6 mm cover fillets at transverse
19
25
joints
b) Two layers, of total thickness
38
50
4. Solid bricks of clay, composition or sand lime, reinforced in every
50
50
50
75
100
horizontal joint, unplastered
5. Aerated concrete blocks
60
60
60
6. Solid blocks of lightweight concrete hollow protection (with an air
50
50
50
60
75
cavity over the flanges)
B) Asbestos insulating board screwed to 25 mm asbestos battens
12
19
C) Solid protections
1. Concrete, not leaner than 1:2:4 mix (unplastered):
a) Concrete not assumed to be load bearing, reinforced <sup>2</sup>)
25
25
25
50
75
b) Concrete assumed to be load bearing
50
50
50
75
75
2. Lightweight concrete, not leaner than 1:2:4 mix (unplastered): concrete
25
25
25
40
60
not assumed to be load bearing, reinforced <sup>2</sup>)
So fixed or designed, as to allow full penetration for mechanical bond.
Reinforcement shall consist of steel binding wire not less than 2.3 mm in thickness, or a steel mesh weighing not less than 0.5 kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 200 mm in any direction.
Table 15Encased Steel Beams, 406 mm × 176 mm (Protection Applied on Three Sides) (Clause 3.3.2)
Nature of Construction and Materials(1)
Minimum Thickness (mm) of Protection for a Fire Resistance of
(1)/(2) h(2)
1h(3)
1(1)/(2) h(4)
2h(5)
3h(6)
4h(7)
A) Hollow protection (without an air cavity beneath the lower flange):
1. ¹ Metal lathing with trowelled lightweight aggregate gypsum plaster
13
13
15
20
25
2. Plasterboard with 1.6 mm wire binding ²⁾ at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified:
a) 9.5 mm plaster board
10
10
15
b) 19 mm plaster board
10
10
13
20
3. Asbestos insulating boards, thickness of board:
a) Single thickness of board, with 6 mm cover fillets at transverse joints
19
25
b) Two layers, of total thickness
38
50
B) Hollow protection (with an air cavity below the lower flange):
1. Asbestos insulating board screwed to 25 mm asbestos battens
9
12
C) Solid protection:
1. Concrete, not leaner than 1:2:4 mix (unplastered):
a) Concrete not assumed to be load bearing, reinforced ³
25
25
25
25
50
75
b) Concrete assumed to be load bearing
50
50
50
50
75
75
2. Lightweight concrete ⁴ , not leaner than 1:2:4 (mix) unplastered
25
25
25
25
40
60
Table 16Timber Floors — Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 21 mm Finished Thickness (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
(1)/(2) h(2)
1h(3)
2h(4)
37 mm (minimum) timber joists with a ceiling of:
1. Timber lathing and plaster, plaster of thickness
15
2. Metal lathing and plaster, thickness of plaster:a) Sanded gypsum plaster (metal lathing grade)
15
b) Lightweight aggregate gypsum plaster
13
13
25
3. One layer of plasterboard with taped and filled joints
12.7
4. Two layers of plasterboard with joints staggered, joints in outer layertaped and filled total thickness
19
31
5. One layer of plasterboard not less than 9.5 mm thick, finished with:a) Gypsum plaster
5
b) Sanded gypsum plaster
13
c) Lightweight aggregate gypsum plaster
13
6. One layer of plasterboard not less than 12.7 mm thick, finished with:a) Gypsum plaster
5
b) Lightweight aggregate gypsum plaster
10
7. One layer of asbestos insulating board with any transverse jointsbacked by fillets of asbestos insulating board not less than 9 mmthick, or by timber
9
12
Table 17Timber Floors — Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 15 mm Finished Thickness (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
11⁄2 h(2)
1 h(3)
2 h(4)
37 mm (minimum) timber joists with a ceiling of:
1. Timber lathing and plaster, plaster of thickness
15
2. Metal lathing and plaster, thickness of plaster for:
a) Sanded gypsum plaster (metal lathing grade)
15
b) Lightweight aggregate gypsum plaster
13
13
25
3. One layer of plasterboard with taped and filled joints
12.7
4. Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
22
31
5. One layer of plasterboard not less than 9.5 mm thick, finish with:
a) Gypsum plaster
5
b) Sanded gypsum plaster
15
c) Lightweight aggregate gypsum plaster
13
6. One layer of plasterboard not less than 12.7 mm thick, finished with:
a) Gypsum plaster
5
b) Lightweight aggregate gypsum plaster
10
7. One layer of asbestos insulating board, with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber
9
12¹⁾
Finished on top with 25 mm minimum thick glass fibre or mineral wool laid between joints.
Table 18Timber Floors — Any Structurally Suitable Flooring of Timber or Lignocelluloses Boards (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
(1)
(1)/(2) h(2)
1h(3)
37 mm (minimum) timber joists with a ceiling of:
1. Timber lathing and plaster, plaster of thickness
15
2. Metal lathing and plaster, thickness of plaster for:
a) Sanded gypsum plaster (metal lathing grade)
15
b) Lightweight aggregate gypsum plaster
13
19
3. One layer of plasterboard with joints taped and filled and backed by timber
12.7
4. Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
25
5. Two layers of plasterboard, each not less than 9.5 mm thick, joints between boards staggered and outer layer finished with gypsum plaster
5
6. One layer of plasterboard not less than 9.5 mm thick, finish with:
a) Sanded gypsum plaster
13
b) Lightweight aggregate gypsum plaster
15
7. One layer of plasterboard not less than 12.7 mm thick, finished with:
a) Sanded gypsum plaster
15
b) Lightweight aggregate gypsum plaster
13
8. One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber
12
3.3.3 Steel Construction
Load bearing steel beams and columns of buildings having total covered area of 500 m2 and above shall be protected against failure/collapse of structure in case
of fire. This could be achieved by use of appropriate methodology using suitable fire resistance rated materials alongwith suppression system {see Table 14, Table 15 and also accepted standard [4(5)]}.
The comparative floor area ratios for different occupancies and types of construction are given in
Table 19 (see also Part 3 ‘Development Control Rules and General Building Requirements’).
Table 19Comparative Floor Area Ratios for Occupancies Facing One Public Street Atleast 9 m Wide (Clauses 2.6 and 3.4.5)
Occupancy Classification(1)
Type of Construction
Type 1(2)
Type 2(3)
Type 3(4)
Type 4(5)
Residential
UL
2.0
1.4
1.0
Educational
UL
2.0
1.4
1.0
Institutional
UL
1.5
1.0
0.8
Assembly
UL
1.0
0.7
0.5
Business
UL
2.9
2.3
1.6
Mercantile
8.0
1.8
1.4
1.0
Industrial
7.5
1.9
1.6
1.3
Storage (see Note 5)
6.0
1.5
1.3
1.0
Hazardous (see Note 5)
2.8
1.1
0.9
NP
UL — Unlimited.
NP — Not permitted.
NOTES
1 The FAR values given in this table are subject to overall restrictions on the heights of buildings in the case of educational, institutional, assembly, storage and hazardous occupancies as specified in col 2 of Table 23.
2 This table has been prepared, taking into account the combustible content in the different occupancies as well as the fire resistance offered by the type of construction.
3 This table should be modified by the Authority, taking into account the other aspects as given below:
a) Density in terms of dwelling units per hectare;
b) Traffic considerations;
c) Parking spaces;
d) Local fire fighting facilities; and
e) Water supply, drainage and sanitation requirements.
4 The FAR values specified in this table may be increased by 20 percent for the following services:
a) A basement or cellar space under a building constructed on stilts and used as a parking space and airconditioning plant room used as accessory to the principal use;
b) Watchman’s booth, pumphouse, garbage shaft, electric cabin or sub-station and other utility structures meant for the services of the building under considerations;
c) Projections and accessory buildings as specifically exempted under the Code; and
d) Staircase room and lift rooms above the topmost storey; architectural feature; and chimneys and elevated tanks of dimensions as permissible under the Code; the area of the lift shaft shall be taken only on one floor.
5 In so far as single storey storage and hazardous occupancies are concerned, they would be further governed by volume to plot area ratio (VPR) to be decided by the Authority.
3.4.5.1 Each portion of a building, which is separated by one or more continuous fire resisting walls, having a fire resistance of not less than 2 h, extending from the foundation to 1 m above the roof at all points, may
be considered to be a separate building for the calculation of maximum permissible height and floor area, provided openings, if any, in the separating wall are also protected by fire assemblies of not less than 2 h.
3.4.6 Open Spaces
The open spaces around or inside a building shall conform to the requirements of Part 3 ‘Development Control Rules and General Building Requirements’.
3.4.6.1 For high rise buildings, the following additional provisions of means of access to the building shall be ensured (see Part 3 ‘Development Control Rules and General Building Requirements’):
a) The width of the main street on which the building abuts shall not be less than 12 m and one end of this street shall join another street not less than 12 m in width;
b) The road shall not terminate in a dead end; except in the case of residential building, up to a height of 30 m.
c) The compulsory open spaces around the building shall not be used for parking; and
d) Adequate passageway and clearances required for fire fighting vehicles to enter the premises shall be provided at the main entrance; the width of such entrance shall be not less than 4.5 m. If an arch or covered gate is constructed, it shall have a clear head-room of not less than 5 m.
3.4.7 Mixed Occupancy
When any building is used for more than one type of occupancy, then in so far as fire safety is concerned, it shall conform to the requirements for the occupancies of higher hazard. Unless the high hazard area is separated by separating walls of 4 h rating, the occupancies shall not be treated individually.
3.4.8 Openings in Separating Walls and Floors
At the time of designing openings in separating walls and floors, particular attention shall be paid to all such factors as will limit fire spread through these openings and maintain fire rating of the structural member.
3.4.8.1 For Types 1 to 3 construction, a doorway or opening in a separating wall on any floor shall be limited to 5.6 m2 in area with a maximum height/width of 2.75 m. Every wall opening shall be protected with fire-resisting doors having the fire rating of not less than 2 h in accordance with accepted standard [4 (7)]. All openings in the floors shall be protected by vertical enclosures extending above and below such openings, the walls of such enclosures having a fire resistance of not less than 2 h and all openings therein being
protected with a fire-resisting assembly as specified in 3.4.9.
3.4.8.2 For Type 4 construction, openings in the separating walls or floors shall be fitted with 2 h fireresisting assemblies.
3.4.8.3 Openings in walls or floors which are necessary to be provided to allow passages of all building services like cables, electrical wirings, telephone cables, plumbing pipes, etc, shall be protected by enclosure in the form of ducts/shafts having a fire resistance not less than 2 h. The inspection door for electrical shafts/ducts shall be not less than 2 h and for other services shafts/ducts, the same shall have fire resistance not less than 1 h. Medium and low voltage wiring running in shafts/ducts, shall either be armoured type or run through metal conduits. Further, the space between the conduits pipes and the walls/ slabs shall be filled in by a filler material having fire resistance rating of not less than 1 h.
NOTE — In the case of buildings where it is necessary to lower or lift heavy machinery or goods from one floor to the other, it may be necessary to provide larger openings in the floor. Such openings shall be provided with removable covers which shall have the same strength and fire resistance as the floor.
3.4.8.4 Vertical opening
Every vertical opening between the floors of a building shall be suitably enclosed or protected, as necessary, to provide the following:
a) Reasonable safety to the occupants while using the means of egress by preventing spread of fire, smoke, or fumes through vertical openings from floor to floor to allow occupants to complete their use of the means of egress. Further it shall be ensured to provide a clear height of 2 100 mm in the passage/escape path of the occupants.
b) Limitation of damage to the building and its contents.
3.4.9 Fire Stop or Enclosure of Openings
Where openings are permitted, they shall not exceed three-fourths the area of the wall in the case of an external wall and they shall be protected with fire resisting assemblies or enclosures having a fire resistance equal to that of the wall or floor in which these are situated. Such assemblies and enclosures shall also be capable of preventing the spread of smoke or fumes through the openings so as to facilitate the safe evacuation of building in case of a fire {see also accepted standard [4 (8)]}.
3.4.10 Electrical Installations
For requirements regarding electrical installations from the point of view of fire safety, reference may be made
to good practice [4(9)] (see also Part 8 ‘Building Services, Section 2 Electrical and Allied Installations’).
3.4.11 Air-conditioning and Ventilation
Air-conditioning and ventilation requirements of different rooms or areas in any occupancy shall be as given in Part 8 ‘Building Services, Section 1 Lighting and Ventilation and Section 3 Air-conditioning, Heating and Mechanical Ventilation’.
3.4.11.1 Air-conditioning and ventilating systems shall be so installed and maintained as to minimize the danger of spread of fire, smoke or fumes from one floor to other or from outside to any occupied building or structure (see C-1.17).
3.4.11.2 Air-conditioning and ventilating systems circulating air to more than one floor or fire area shall be provided with dampers designed to close automatically in case of fire and thereby preventing spread of fire or smoke and shall be in accordance with the accepted standard [4(10)]. Such a system shall also be provided with automatic controls to stop fans in case of fire, unless arranged to remove smoke from a fire, in which case these shall be designed to remain in operation.
3.4.11.3 Air-conditioning system serving large places of assembly (over 1 000 persons), large departmental stores or hotels with over 100 rooms in a single block shall be provided with effective means for preventing circulation of smoke through the system in the case of a fire in air filters or from other sources drawn into the system, and shall have smoke sensitive devices for actuation in accordance with the accepted standards [4(11)].
3.4.11.4 From fire safety point of view, separate air handling units for the various floors shall be provided so as to avoid the hazards arising from spread of fire and smoke through the air-conditioning ducts. The requirements of air-conditioning ducts shall be in accordance with good practice [4(12)].
3.4.11.5 For normal operation, air changes schedule shall be as given in Part 8 ‘Building Services, Section 3 Air-conditioning, Heating and Mechanical Ventilation’.
3.4.12 Smoke Venting
3.4.12.1 Smoke venting facilities for safe use of exits in windowless buildings, underground structures, large area factories, hotels and assembly buildings (including cinema halls) shall be automatic in action with manual controls in addition.
3.4.12.2 Natural draft smoke venting shall utilize roof vents or vents in walls at or near the ceiling level; such vents shall be normally open, or, if closed, shall be designed for automatic opening in case of fire, by release of smoke sensitive devices.
3.4.12.3 Where smoke venting facilities are installed for purposes of exit safety, these shall be adequate to prevent dangerous accumulation of smoke during the period of time necessary to evacuate the area served, using available exit facilities with a margin of safety to allow for unforeseen contingencies. It is recommended that smoke exhaust equipment should have a minimum capacity of 12 air changes per hour. Where mechanical venting is employed, it shall be firesafe.
3.4.12.4 The discharge apertures of all natural draft smoke vents shall be so arranged as to be readily accessible for opening by fire service personnel.
3.4.12.5 Power operated smoke exhausting systems shall be substituted for natural draft vents only by specific permission of the Authority.
3.4.13 Heating
Installation of chimney and heating apparatus shall be in accordance with good practice [4 (13)].
3.4.14 Additional Precautions
In addition to the factors covered by 3.4.2 to 3.4.12 there are certain aspects, applicable to particular occupancies only, which may effect the spread of fumes and thus the safe evacuation of the building in case of fire. Some such aspects are:
a) interior finish and decoration;
b) seating, aisles, railings, turnstiles and revolving doors in places of assembly;
c) service equipment and storage facilities in buildings other than storage buildings; and
d) hazards on stage, in waiting spaces, projection booths, etc, in theatres and cinemas.
3.4.15 Surface Interior Finishes
3.4.15.1 The use of combustible surface finishes on walls (including facade of the building) and ceilings affects the safety of the occupants of a building. Such finishes tend to spread the fire and even though the structural elements may be adequately fire resistant, serious danger to life may result. It is, therefore, essential to have adequate precautions to minimize spread of flame on wall, facade of building and ceiling surfaces.
The finishing materials used for various surfaces and décor shall be such that it shall not generate toxic smoke/fumes.
3.4.15.2 The susceptibility to fire of various types of wall surfaces is determined in terms of the rate of spread of flame. Based on the rate of spread of flame, surfacing material shall be considered as divided into four classes as follows {see also good practice [4(14)]}.
Class 1 Surfaces of very low flame spread.
Class 2 Surfaces of low flame spread.
Class 3 Surfaces of medium flame spread.
Class 4 Surfaces of rapid flame spread.
3.4.15.3 The uses for which surface materials falling into various classes shall be adopted in building construction are given below:
Class 1
Class 2
Class 3
May be used in any situation
May be used in any situation, except on walls, facade of the building, staircase and corridors
May be used only in living rooms and bed rooms (but not in rooms on the roof) and only as a lining to solid walls and partitions; not on staircases or corridors or facade of the building.
NOTE — Panelling (lining) shall be permitted in a limited area. It shall not be permitted in a vestibule.
3.4.15.4 Materials of Class 4 which include untreated wood fibreboards may be used with due fire retardant treatment as ceiling lining, provided the ceiling is at least, 2.4 m from the top surface of the floor below, and the wall surfaces conform to requirements of class [see Note under 3.4.15.3] Class 4 materials shall not be used in kitchens, corridors and staircases. Some materials contain bitumen and, in addition to risk from spread of fire, emit dense smoke on burning; such materials shall be excluded from use under these conditions and shall also not be used for construction of ceiling where the plenum is used for return air in air-conditioned buildings [see also 5.1.7(m)].
3.4.15.5 When frames, walls, partitions or floors are lined with combustible materials, the surfaces on both sides of the materials shall conform to the appropriate class, because there is considerable danger from fire starting and rapidly spreading within the concealed cavity unknown to the occupants whose escape may be hampered there by. For detailed information on materials and details of construction with their fireresistance rating, reference may be made to good practice [4(15)].
3.4.16 Glazing
3.4.16.1 Building of Types 1 to 4 construction shall employ one of the two types of glazing described in 3.4.16.2 and 3.4.16.3 except that Type 4 construction may have the alternative of hardwood sashes or frames or both.
3.4.16.2 Wired glass shall comply with the following requirements:
a) Wired glass — The wired glass shall be of minimum half hour fire resistance rating.
b) Sashes and frames — The sashes or frames or both shall be entirely of iron or other suitable metal such as stainless steel, securely bolted or keyed into the wall, except in the case of panels in internal doors.
c) Setting of glass — The panels of glass shall be set in rebates or grooves not less than 6.0 mm in width or depth, with due allowance for expansion, and shall be secured by hard metal fastenings to the sashes or frames independently of any cement or putty used for weather-proofing purposes.
3.4.16.3 Electro-copper glazing shall comply with the following requirements:
a) Electro-copper glazing — The electro-copper glazing shall be of minimum half hour fire resistance rating.
b) Sashes and frames — The sashes or frames or both shall be entirely of iron or other hard metal, securely bolted or keyed into the wall, except when in panels in internal doors.
c) Fixing of sectional lights — The sectional lights shall be set in rebate or grooves not less than 6.5 mm in width or depth, with due allowance for expansion and shall be secured by hard metal fastenings to the sashes or frames independently of any lead, cement or putty used for weather-proofing purposes.
3.4.16.4 Maximum permissible area shall be 5 m2 for protection by wired glass or electro-copper glazing.
3.4.16.5 Casement
Hard metal casements, not exceeding 0.8 m2 fitted with wired glass or electro-copper glazing in accordance with 3.4.16.2 and 3.4.16.3, secured to the frames by hard metal hinges not more than 600 mm apart and by fastening at top, centre and bottom shall be permissible.
3.4.17 Skylights
3.4.17.1 Wired glass for skylights or monitor lights shall comply with the following requirements:
a) Wired glass for skylights or monitor lights — The wired glass for skylights or monitor lights shall be of minimum half hour fire resistance rating.
b) Frames and glazing — The frame shall be continuous and divided by bars spaced at not more than 700 mm centres. The frame and bars shall be of iron or other hard metal, and supported on a curb either of metal or of wood covered with sheet metal. The toughened glass
shall be secured by hard metal fastenings to the frame and bars independently of any lead, cement or putty used for weather-proofing purposes.
3.4.18 Louvers
Louvers wherever provided shall be of minimum half hour fire resistance rating.
3.4.19 Glass of facade for high rise buildings, etc shall be of minimum 1 h fire resistance rating.
4.3.1 Mezzanine
The occupant load of a mezzanine floor discharging to a floor below shall be added to that floor occupancy and the capacity of the exits shall be designed for the total occupancy load thus established.
e) The main and external staircases shall be continuous from ground floor to the terrace level.
f) No electrical shafts/AC ducts or gas pipes, etc, shall pass through or open in the staircases. Lifts shall not open in staircase.
g) No combustible material shall be used for decoration/wall paneling in the staircase.
h) Beams/columns and other building features shall not reduce the head room/width of the staircase.
FIG. 1 TYPICAL DETAIL FOR HANDRAIL/BLUSTERS OF A STAIRCASE
j) The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further, all landings of floor shall have floor indicating boards prominently indicating the number of floor as per bye-laws.
The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 m × 0.5 m.
k) Individual floors shall be prominently indicated on the wall facing the staircases.
m) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. The second staircase may lead to basement levels provided the same is separate at ground level by ventilated lobby with discharge points to two different ends through enclosures.
4.10 Pressurization of Staircases (Protected Escape Routes)
4.10.1 Though in normal building design, compartmentation plays a vital part in limiting the spread of fire, smoke will readily spread to adjacent spaces through the various leakage openings in the compartment enclosure, such as cracks, openings around pipes ducts, airflow grills and doors, as perfect sealing of all these openings is not possible. It is smoke and toxic gases, rather than flame, that will initially obstruct the free movement of occupants of the building through the means of escape (escape routes). Hence the exclusion of smoke and toxic gases from the protected routes is of great importance.
4.10.2 Pressurization is a method adopted for protected escape routes against ingress of smoke, especially in high-rise buildings. In pressurization, air is injected into the staircases, lobbies or corridors, to raise their pressure slightly above the pressure in adjacent parts of the building. As a result, ingress of smoke or toxic gases into the escape routes will be prevented. The pressurization of staircases shall be adopted for high rise buildings and building having mixed occupancy/ multiplexes having covered area more than 500 m2.
4.10.3 The pressure difference for staircases shall be as under:
Building Height
Pressure Difference
Reduced Operation (Stage 1 of a 2-Stage System)
Emergency Operation (Stage 2 of a 2-Stage System or Single Stage System)
(Pa)
(Pa)
Less than 15 m
8
50
15 m or above
15
50
If possible, the same levels shall be used for lobbies and corridors, but levels slightly lower may be used for these spaces if desired. The difference in pressurization levels between staircase and lobbies (or corridors) shall not be greater than 5 Pa.
4.10.4 Pressurization system may be of two types:
a) Single-stage, designed for operation only in the event of an emergency, and
b) Two-stage, where normally a level of pressurization is maintained in the protected escape routes and an increased level of pressurization can be brought into operation in an emergency.
4.10.5 The normal air-conditioning system and the pressurization system shall be treated as an integral one, especially for a two-stage system. When the emergency pressurization is brought into action, the following changes in the normal air-conditioning system shall be effected:
a) Any re-circulation of air shall be stopped and all exhaust air vented to atmosphere;
b) Any air supply to the spaces/areas other than escape routes shall be stopped;
c) The exhaust system may be continued provided:
the positions of the extraction grills permit a general air flow away from the protected escape route entry;
the construction of the ductwork and fans is such that, it will not be rendered inoperable by hot gases and smoke; and
there is no danger of spread of smoke to other floors by the path of the extraction system which can be ensured by keeping the extraction fans running.
4.10.6 The pressurization system can be interconnected with the automatic/manual fire alarm system for actuation.
4.10.7 It will be desirable to have all the staircases in a building pressurized, if pressurization system is to
be resorted to. The use of pressurized and naturally ventilated staircases in the same building may introduce difficulties and hence shall be avoided. Under no circumstances shall a pressurized staircase be connected by a corridor or lobby to an un-pressurized staircase. Wherever pressurized staircase is to be connected to un-pressurized area, the two areas shall be segregated.