14.1 General
This section, which has been framed in accordance with National Building Code 2016, covers the requirement for fire prevention, life safety in relation to fire and fire protection of buildings. Notwithstanding anything contained anywhere else, this section shall be followed by the fire department and all the authorities required to issue fire and safety permissions. Notwithstanding anything else contained anywhere else in proposed or finalised ‘Dadra and Nagar Haveli and Daman & Diu Fire and Emergency Service Regulation, 2022’ or in any other such law, these bye-laws shall be deemed to be Bye-Law within the meaning of 2(e) of the draft Dadra and Nagar Haveli and Daman & Diu Fire and Emergency Service Regulation, 2022 and the fire department shall follow the provisions of this part of GDR in supersession of anything contained anywhere else in NBC or any other law. In case there is any confusion regarding any provision in this Part the same may be referred to the Planning and Development Authority whose decision in this regard shall be final. A certificate of the fire department to the effect shall be sufficient proof that all requirements of this chapter have been met.
14.2.3Types of Building Construction
The design of any building and the type of materials used in its construction are important factors in making the building resistant to a complete burn-out and in preventing the rapid spread of fire, smoke or fumes, which may otherwise contribute to the loss of lives and property.
The fire resistance of a building or its structural and non-structural elements is expressed in minutes against a specified fire load which is expressed in kcal/m2, and against a certain intensity of fire. The fire-resistance test for structural element shall be done in accordance with accepted standards.
Types of construction according to fire resistance shall be classified into four categories:
a) Type 1 Construction,
b) Type 2 Construction,
c) Type 3 Construction
d) Type 4 Construction.
The minimum fire resistance ratings of structural and non-structural members for various types of construction shall be as given in Table No. 14.3. Non-combustible materials should be used for construction of buildings, and the internal walls of staircase enclosures should be of brick work or reinforced concrete or any other material of construction with minimum of 120 min rating. The walls for the chimney shall be of Type 1 or Type 2 Construction depending on whether the flue gas temperature is above 200°C or less, respectively. Load bearing steel beams and columns of buildings having total covered area of 500 m2and above shall be protected against failure/collapse of structure in case of fire.
It is required that a structural and/or non-structural element/component shall have the requisite fire resistance rating (Refer Table No. 14.3). The fire resistance rating for the structural and non-structural elements shall be based on guidelines as per approved and accepted standards. The fire rating shall be validated and certified with a view to meeting the requirements of Table No. 14.3. In the absence of any validated/certified rating, guidance may be obtained from the information available in Annexure C.
Load bearing steel beams and columns of buildings having total covered area of 5 0 0 ~ m 2 and above shall be protected against failure/collapse of structure in case of fire. This could be achieved by use of appropriate methodology using suitable fire resistance rated materials along with suppression system (Refer Annexure C, Table 25 and Table 26 Timber Floors).
The false ceiling, including all fixtures used for its suspension, shall be of non-combustible material and shall provide adequate fire resistance to the ceiling in order to prevent spread of fire across ceiling.
Page No 28
Table No.14.3: Fire Resistance Ratings of Structural and Non-Structural Elements (minutes)
No.
Structural Element
Fire Resistance Ratings (min) for Type of Construction
Type1
Type2
Type3
Type4
(1)
(2)
(3)
(4)
(5)
(6)
i)
Exterior walls:
a)
Fire less than 3.7 m:
1)
Bearing
240
120
120
60
2)
Non-bearing
120
90
60
60
b)
Fire separation of 3.7 m or more but less than 9 m
1)
Bearing
240
120
120
60
2)
Non-bearing separation
90
60
60
60
c)
Fire separation of 9 m or more:
1)
Bearing
240
120
120
60
2)
Non-bearing
60
60
60
60
ii)
Fire separation assemblies (like fire check doors)
120
120
120
120
iii)
Fire enclosures of exits
120
120
120
120
iv)
Shafts for services, lift hoist way and refuse chutes
120
120
120
120
v)
Vertical separation between adjacent tenant spaces
60
60
60
60
vi)
Dwelling unit separation:
a)
Load bearing
120
120
60
60
b)
Non-load bearing
60
60
30
30
vii)
Interior bearing walls, bearing partitions, columns, beams, girders, trusses (other than roof trusses) and framing:
a)
Supporting more than one floor
240
120
120
120
b)
Supporting one floor only
14.2Fire Prevention
14.2.1 Classification of Buildings based on Occupancy
All buildings/uses, whether existing or hereafter erected shall be classified according to use or the character of occupancy in one of the following groups as indicated in the table below. The table also summarizes the types of examples of buildings:
Page No 15
Table No. 14.1: Classification of Buildings based on Occupancy and Fire Divisions
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Final Remarks
Stairways
Level Componen ts and Ramps
Types 1 and 2
Types 3 and 4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
1
A
A-1
Dwelling 1
Detached dwelling unit. Clinic not having indoor treatment facility.
Fire Division 1
12.50
10.00
6.50
30.00
22.50
Firefighting installations in Table No. 14.7
Agriculture 1 (Part)
Farmhouse.
Dwelling 1a
Detached dwelling unit - affordable Housing
Dwelling 2
Semi-detached dwelling unit Row House Tenement Cottage Industry
12.50
10.00
6.50
30.00
22.50
Firefighting installations in Table No. 14.7
Dwelling 2a
Semi Detached dwelling unit - affordable Housing
Agriculture 1 (Part)
Farmhouse
2
A-2
Dwelling 3 (Part)
Old Age Home Orphanage
7.5
15
13
30.00
22.50
Firefighting Installation in Table No. 14.7, vary with Height of the Building.
3
A-3
Dwelling 3 (Part) Dormitory
Hostels Dormitories Dharamshala Homestay Night Shelter
12.50
10.00
6.50
30.00
22.50
Firefighting Installation in Table No. 14.7, vary with Height of the Building.
Polytechnic Industrial Training Institutes (ITI) Vocational Training Centre College University and Ancillary use
8
C-2
Education 3
Research and Development Establishments/ Centre
Fire Division 2
10
10.00
6.50
30.00
30.00
9
D
D-1
Health 1
PHC, Clinic without indoor facility Dispensary Health and Wellness Centre Ayushman Bharat
Fire Division 1
10(Outdoor Patients area)15(Indoor Patients area)
15
13
30.00
22.50
Firefighting Installation in Table No. 14.7, vary with Height of the Building, area of Building Unit and No. of Beds
Health 2
Clinic with indoor facility Indoor Hospital facility up to 20 Bed Surgical Hospital, Nursing Home, Maternity Home, Community Health Centre Veterinary Facilities
Planning and Development Authority
Page No 18
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Final Remarks
Stairways
Level Componen ts and Ramps
Types 1 and 2
Types 3 and 4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
Health 3
Multi-specialty hospital- Upto 100 beds Medical College, Research and Development Centre Hospital- more than 100 beds
10
D-2
Health 4
Hospital for infectious diseases Mental Hospital / Asylum
15(see Note2)
15
13
30.00
22.50
Firefighting Installation in Table No. 14.7, vary with Height of the Building and number of persons
Public / Public Office
Custodial and Penal institutions Jails Prison Mental hospitals Houses of Correction Detention Reformatories
11
D-3
Public / Public Office
Offices for public Government / semi government entities for Health Transport Communication Security Ward Office Law Courts, Police Stations / Chowkis Panchayat Circuit House etc.
10
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building
12
E
E-1
Assembly 1
Community Hall Banquet Hall (No permanent seating and no permanent stage)
Fire Division 1
0.65
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building and number of persons
Assembly 2
Town Hall Convention Centre Exhibition Hall Studio
Page No 19
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Final Remarks
Stairways
Level Componen ts and Ramps
Types 1 and 2
Types 3 and 4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
Performing Arts Theatre Gymnasium (without spectator seating) Club (No permanent seating and no permanent stage)
Assembly 4
Party Plot (No permanent seating and no permanent stage)
13
E-2
Assembly 2
Convention Centre Auditorium Planetarium Museum Performing Arts Theatre (with Fixed seatings)
N *1.2 (where N = number of seats) (see Note4)
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building and number of persons.
Assembly 3
Theatre Cinema Multiplex (with Fixed seatings)
14
E-3
Religious
Temple Shrine Church / Chapel Mosque / Dargah Gurudwara Synagogue Ashram / Upashraya / Math / Sant Niwas Any other Religious Structure. ( No permanent seating and no permanent stage)
Fire Division 1
0.65
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building and number of persons
Planning and Development Authority
Page No 20
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Final Remarks
Stairways
Level Componen ts and Ramps
Types 1 and 2
Types 3 and 4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
15
E-4
Sports and Leisure
Gymnasium Sports complex Swimming pool Playfield Water sports facilities Theme Amusement Park Aquarium Exhibition Mela Shooting Range
Fire Division 1
1.4(see Note3)
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building and number of persons.
Cremation and Burial
Crematorium
Temporary Use
Fair Circus Exhibition Mela Pandal Concrete batching plant for construction Seasonal Market
16
F
F-1
Transportation
Bus Terminal / station (public / private) Transport Terminal for Passengers
Fire Division 1
30
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building and number of persons
EP 2
Port Harbour Hover ports for Coast Guards Jetties
17
F-2
Transportation
Transport Terminal for Goods (Truck)
Fire Division 3
30
10
6.5
30(see Note 8)
NA
Firefighting Installation in Table No. 14.7, vary with Height of the Building and Covered area
Page No 21
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Final Remarks
Stairways
Level Componen ts and Ramps
Types 1 and 2
Types 3 and 4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
18
G
G-1
Agriculture 1 (Part)
Green Houses Dairy Development Animal rearing and breeding/gaushala Poultry Farm
Fire Division 2
1.4
10
6.5
45(see Note 8)
NA
Firefighting Installation in Table No. 14.7, vary with Height of the Building and Covered area
19
G-2
Agriculture 2
Animal Shed Agro-Based Storage
Fire Division 3
30
10
6.5
30(see Note 8)
NA
Firefighting Installation in Table No. 14.7, vary with Height of the Building and Covered area
Communication Infrastructure - telephone, microwave tower or other means of communication facilities
25
J
J-1*
Utility
Infrastructure for Water Supply - treatment / purification plant, pumping station.
Fire Division 2
10
10
6.5
45(see Note 8)
NA
Firefighting Installation in Table No 14.7, vary with Height of the Building and Covered area
Industrial 1
All White Category of Industries as defined by CPCB in Classification of Industrial Sector(2016)
Industrial 2
All Green Category of Industries as defined by CPCB in Classification of Industrial Sector (2016), CETP
Industrial 3
All Orange Category of Industries as defined by CPCB in Classification of Industrial Sector (2016), CETP Dumping of Solid Waste Mining and Quarrying Brick Kiln Roof Tiles Tannery Slaughterhouse
Page No 23
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Firefighting Installation in Table No. 14.7, vary with Height of the Building and Covered area
Utility
Electric substations
Industrial 1
All White Category of Industries as defined by CPCB in Classification of Industrial Sector(2016)
Industrial 2
All Green Category of Industries as defined by CPCB in Classification of Industrial Sector (2016), CETP
Industrial 3
All Orange Category of Industries as defined by CPCB in Classification of Industrial Sector (2016), CETP Dumping of Solid Waste Mining and Quarrying Brick Kiln Roof Tiles Tannery Slaughterhouse Petroleum Storage Roofing Tiles and Cement Pipes
27
J-3*
Industrial 1
All White Category of Industries as defined by CPCB in Classification of Industrial Sector(2016)
Fire Division 3
10
10
6.5
22.5(see Note 8)
NA
Fire fighting Installation in Table No. 14.7, vary with Covered Area
Industrial 2
All Green Category of Industries as defined by CPCB in
Planning and Development Authority
Page No 24
No
Main
Sub
Use Group as per proposed ODP GDR
Detailed Uses As per proposed ODP GDR
Fire Divisions
Occupant Load Factor(sqm/person) As per NBC**
Capacity Factors (Width Per Person in mm) As per NBC
Maximum Travel Distance (Based on Occupancy and Construction Type in m) As per NBC***
Final Remarks
Stairways
Level Componen ts and Ramps
Types 1 and 2
Types 3 and 4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
Classification of Industrial Sector (2016), CETP
Industrial 3
All Orange Category of Industries as defined by CPCB in Classification of Industrial Sector (2016), CETP Dumping of Solid Waste Mining and Quarrying Brick Kiln Roof Tiles Tannery Slaughterhouse Petroleum Storage Roofing Tiles and Cement Pipes
Notes: *Detailed uses of Subgroup J-1, J-2 and J-3 will correspond to low hazard, moderate hazard and high hazard respectively as in accordance with Annex B ** Occupant load 1 Gross area shall be the floor area. All factors expressed are in gross area unless marked net. 2 Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums, etc where sleeping accommodation is provided shall be calculated at not less than 7.5 m2 gross floor area / person. 3 These shall include gymnasium, table tennis room, billiard room and other gaming rooms, library, swimming pool and like. 4 In case of assembly occupancy having fixed seats, the occupant load shall be determined by multiplying the number of seats by 1.2. 5 Car parking areas under occupancy other than storage shall also be 30 m2 per person. *** Travel Distance 6 For fully sprinklered building, the travel distance may be increased by 50 percent of the values specified. 7 Ramp shall not be counted as an exit in case of basements below first basement in car parking. 8 Construction of Type 3 or Type 4 is not permitted.
Page No 25
180
90
60
60
c)
Supporting a roof only
180
90
60
60
viii)
Walls supporting structural members
180
90
60
60
ix)
Floor construction
120
90
60
60
x)
Roof construction:
a)
5 m or less in height to lowest member
120
90
60
60
b)
More than 5 m but less than 6.7 m in height to lowest member
60
60
60
60
c)
6.7 m or more in height to lowest member
0
0
0
0
NOTES: 1 The above fire resistance rating shall be required to achieve the respective type of construction unless otherwise specified in the respective clauses for different applications/use. 2 In case of lift bank, the partition wall, if any, need not be of fire rating specified in this table.
23
H-4
Mercantile 2
Vegetable Fish Market Agriculture Horticulture Produce
Fire Division 1
3
10
6.5
30.00
30.00
Firefighting Installation in Table No. 14.7, vary with Height of the Building and Area
Mercantile 3
Wholesale Market and ancillary uses Timber mart / Lathi Bazaar