2 Life Safety
a) The common path of travel shall be 30 m. The maximum dead end of corridor distance shall not exceed 6 m.
b) Principle of progressive horizontal evacuation is of paramount consideration for hospital patients particularly those lacking self-preservation. This calls for moving occupants from a fire affected area to an adjoining area at the same level through a fire-resistant wall, to protect them from the immediate dangers of fire and smoke (Figure No.14.15).
c) Progressive horizontal evacuation operates on the basis of evacuation from compartment to compartment and on use of adjacent compartments as temporary means of refuge. All compartments shall be divided with self-closing (door closers) fire doors with electromagnetic hold open. A coordinator shall be provided to sequence the closing of double leaf in case of emergency.
d) Doors in fire resistant walls shall be so installed that these may normally be kept in open position but will close automatically. Corridor door openings shall be not less than 2.0 m in width of double swing double leaf type door. A coordinator shall be provided as above, for closing of double leaf in case of emergency.
e) Exits and other features for penal and mental institutions, and custodial institutions shall be the same as specified for hospitals (Refer clause 14.5.3 (2)) in so far as applicable. Reliable means shall be provided to permit the prompt release of inmates from any locked section in case of fire or other emergency.
f) All buildings or sections of buildings in penal and mental institution used for manufacturing, storage or office purposes shall have exits in accordance with the provisions of the Code for those occupancies.
g) For hospitals (Subdivision D-1), the following shall also be complied with:
i Compartmentation shall meet the requirement as per Rule No. 14.3.5
ii Each compartment (Refer Rule No. 14.3.5) shall be able to accommodate, in addition to its own, the patients from adjoining compartment also considering 3.5 m2 per person. If patients are not bed-ridden, a factor of 0.6 m2 per person is recommended.
iii All critical patients and those incapables of self-preservation and having physical impairment shall be housed within 30 m height.
iv Other types of patients and occupancies incidental to the hospitals such as consultation rooms, nurses’ stations, medical shops, canteens, etc may be housed at heights beyond 30 m but not more than 45 m.
v Basement shall not be used to store flammables or for pathological or other laboratories particularly those involving usage of chemicals.
vi Operation theatres, delivery rooms, intensive care units, recovery rooms, etc, that containing patients lacking self-preservation in case of emergencies shall be fire/smoke separated (120 min minimum rating) from all the adjoining areas.
vii Aisles, corridors, ramps, etc, through which patients are moved, shall have a minimum width of 2.4 m throughout. Aisles, corridors, and ramps in other areas not intended for the housing, treatment, or use of inpatients shall be not less than 1.5 m in width.
viii All exits from hospital or infirmary sections shall be not less than 2.0 m in width.
ix Minimum width of door of single or double occupancy patient room shall be 1.25 m while for the wards for 3 to 5 patient beds shall be 1.50 m, to permit movement of patients. The minimum width of door for wards for more than 5 patient beds and for areas necessarily requiring patient evacuation on bed (such as ICU, recovery units,
Page No 75
delivery rooms, etc), shall have door width of 2.0 m. The width of 2.0 m may be reduced to minimum of 1.5 m where two such doors are provided in such areas.
x Any sleeping accommodation or suite exceeding 100 m2in area shall have at least two doorways leading to the exit access corridors.
xi Floor surface of corridors shall not be inclined at a gradient steeper than 1 in 12 to the horizontal.
xii Exit access corridors from a compartment to another compartment shall be divided at the compartment intersection by a fire door of 120 min fire rating in the fire compartment wall.
xiii Rooms designated for laboratory and the like shall not exceed 100 m2 in area and if additional space is required, fire separation of 120 min shall be provided.
xiv Storage of flammable liquids in laboratories or in any other area shall be not more than 3 litre for every 10 m2 area.
xv Disposal of any equipment and other (particularly hazardous) materials shall be accomplished in the premises by a disposal specialist or at a safe location away from the health care facility by competent personnel using procedures established in concurrence with the safe practices.
xvi A stretcher lift in a lift bank shall also act as fireman’s lift meeting the requirements of Part VIII ‘Building Services, Section 5 Installation of Lifts, Escalators and Moving Walks, Subsection 5A Lifts’, National Building Code.
h) Progressive evacuation strategy (Refer Figure No. 14.16) in which, as an example, the exit calculations at two locations shall be based on requirements of total occupancy for area (A, B, C and D) divided by 2 considering progressive evacuation strategy.