Access for all Buildings
Access from the building unit entry to the building entry or the plinth shall have a minimum width of 1.8 m for DW1 and DW2 and 3.5 m for all other buildings. The surface shall be even.
2 In case of a sloping access path, the gradient shall not be greater than 1:15.
3 Selection of floor material shall be made suitably to attract or to guide visually impaired persons (limited to coloured floor material) whose colour and brightness is conspicuously different from that of the surrounding floor material or the material that emits different sound to guide visually impaired persons; hereinafter referred as "guiding floor material". Finishes shall have a non-slip surface with a texture traversable by a wheelchair. Kerbs wherever provided should blend well.
Ramped Access for all Buildings (Except Dwelling 1 and 2):
1 Minimum one ramp entrance shall be provided that is accessible by people with disability and accompanied by appropriate signages as per Rule No. 13.7.
2 Minimum width of the ramped access shall be 1.2 m, 1.5 m and 1.8 m for ramp having length upto 3.6 m, upto 9 m and more than 9 m respectively.
3 The pedestrian ramp leading main entrance required as per these Rules may be provided in the margin.
4 Ramp specifications shall be as follows:
a) The gradient shall not be greater than 1:15.
b) Minimum width of ramp shall be 1.2 m and the maximum continuous length shall be 9 m. Such ramp shall have 800 mm high handrail on both sides extending 300 mm beyond top and bottom of the ramp. Minimum gap from the adjacent wall to the handrail shall be 50 mm (Refer Figure No. 13.2).
c) Entrance landing shall be provided adjacent to ramp, with the minimum dimension 1.2 m x 1.5 m.
d) The surface shall be adequately prepared as a guide to visually impaired person by using colour and material guide brightness that is different from the surrounding floor material or by using ‘guiding floor material’ that emits different sounds.
e) Finishes shall have a non-slip surface traversable by a wheelchair.
f) Kerbs, wherever provided, should blend to a common level.
Page No 120

Figure No. 13.2: Details for Sloping Access Path
Additional stepped approach for all buildings:
a) Minimum width shall be 1.35 m.
b) Size of tread shall not be less than 300 mm and maximum riser shall be 150 mm.
c) The steps shall not have abrupt (square) nosing.
d) Maximum number of risers on a continuous flight without landing shall be limited to 12.
e) The stepped approach shall be provided with 1150 mm, high handrail on both sides. Handrails shall extend 300 mm on the top and bottom flight of the steps.
f) All steps edges shall have a contrasting colour band of 50 mm width stretched entirely across the step width.
g) The edges should also be non‐slippery.

Figure No. 13.3: Details for Stepped Approach
Page No 121