Any buildings of 15m and above height shall be considered as high rise building. For the buildings categorized as High Rise, clearance from Delhi Fire Service shall be mandatory. These provisions shall be in addition to the general building requirements (low/ high) given in Chapter 7 of this document and structural safety given in Chapter 9.
8.1 Plot Area
Plots to be used for high rise development should be located in a Layout plan, Comprehensive plans or sub division plans as prepared and approved by competent authorities/ as per policy of Government of INDIA or Government of NCT Delhi.
8.2Means of Access
To be read along with ‘Means of Access, clause 2.0.4.j.(iv)’of these building bye laws.
a. A building shall abut on a street or upon spaces directly connected from the street by a hard surface approach road; width of the approach road is 18.0 m ROW (7.5 m ROW for the Redevelopment Areas/ Rehabilitation Colonies/ Special Area/ Village [Lal Dora/ Firni]/ Extended Lal Dora).
b. The hard surface approach road to the building all around shall be capable of taking the weight of fire engine, weighing upto 45 ton having 6.0 m width (with 9.0 m turning circle at the corners) for building upto 40.0 m in height and 9.0 m width (with 12.0 m turning circle at the corners) in case of buildings more than 40.0 m in height shall be provided and the layout for the same shall be done in consultation with Delhi Fire Service. The said open space shall be kept free of obstructions and shall be motorable.
Main entrance to the premise shall be of adequate width to allow easy access to the fire tender and in no case it shall measure less than 6.0 m. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for the movement of the fire service vehicle. If archway is provided over the main entrance the height of the archway shall not be of less than 5.0 m in height.
8.3 Parking Spaces
a. The parking spaces shall be provided as per the provisions of MPD or Zonal Plan as prevalent. The location of parking spaces shall be well ventilated.
b. In case of high-rise buildings parking would be permitted at any or all of the following:
i. Open Area : 23 sq.m per E.C.S
ii. Basements : 32 sq.m per E.C.S
iii. Stilts: 28 sq.m per E.C.S
iv. Podium: 28 sq.m per E.C.S
v. Roof top:28 sq.m per E.C.S
c. Stacked Parking: 16 sq.m / Multi-level (with ramp): 30 sq.m/ Multi level- Automated parking: 16 sq.m per E.C.S is also permitted.
8.4Building Components
8.4.1 Doorways
a. Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
b. No exit doorway shall be less than as required under clause 7.12.2.
c. Exit doorways shall open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 0.9 m, overhead or sliding doors shall not be installed.
d. Exit door shall not open immediately upon a flight or stairs. A landing equal to at least the width of the door shall be provided in the stairway at each doorway. Level of landing shall be the same as that of the floor which it serves.
e. Exit doorways shall be openable from the side which they serve without the use of a key.
f. Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
8.4.2 Revolving Doors
Revolving door shall not be provided as exit doors for required exits.
8.4.3Stairways
a. A staircase shall not be arranged around a lift shaft.
b. The staircase shall be ventilated to the atmosphere at each landing and a vent at the top; the vent openings shall be of0.5 sq.m in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 Pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1 m above the surrounding roof. Glazing or glass bricks if used in staircase, shall have fire resistance rating of minimum two hour.
c. The minimum width of staircase shall be as table given below:
Table 8.1Minimum width of staircase for different types of buildings (clear width excluding handrail and balustrade)
Type of Building
Minimum Width
Residential buildings (Group Housing)
1.5m
Hotel buildings
1.5m
Assembly buildings like auditorium, theatres, cinemas etc.
2.0m
Educational buildings up to 30 m in height
1.5m
Above 30 m
2.0 m
Institutional buildings like hospitals etc.
2.0m
All other buildings including commercial
1.5m
Industrial building
1.5m
d. The minimum width of treads without nosing shall be 0.3m. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 0.15 m in the case of other buildings and shall be limited to 15 risers per flight.
e. For Handrails and Grab Bars refer 11.5.3. The balusters/ railing shall not reduce the width of staircase.
f. The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
g. Access to main staircase shall be gained through adequate fire resistance rating (Refer NBC Part 4, Fire and Life safety Table no1 to 18) Automatic closing doors placed in the enclosing walls of the staircases. It shall be a swing type door opening in the direction of the escape.
h. No living space, store or other fire risk, shall open directly into the staircase or staircases.
i. External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
j. The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment’s. Further all landings of floor shall have floor indication boards indicating the number of floor. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5x0.5m and it shall be prominently placed on the wall facing the staircase.30
k. In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. However, the second staircase shall lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door (Refer NBC Part 4, Fire and Life safety) or through a fire protected corridor.