As compared to the various types of indoor installations covered in other Parts of this Code, outdoor installations are distinct in nature by virtue of their being exposed to moderate to heavy environmental conditions. In addition, electric power in outdoor installations is normally utilized for specific purposes, such as lighting or for meeting the needs of heavy machinery (for example, open cast mines). In the case of the latter, the duties would be more onerous than those normally encountered in indoor situations, thereby calling for special considerations in their design.
Keeping the above in view, Part 5 of this Code deals with installations erected outdoor. Some outdoor installations are erected to serve for a small duration of time after which they are meant to be dismantled. Such installations are called temporary installation. For convenience, and keeping other aspects of safety provisions in view, this duration is defined as not exceeding six months. Permanent outdoor installations are those which are generally in use for longer periods of time. This Part 5 of this Code basically deals with these two types of outdoor installations.
Part 5 consists of the following sections:
Section 1 Public Lighting Installations
Section 2 Temporary Outdoor Installations
Section 3 Permanent Outdoor Installations
Even though installations for lighting of public thoroughfares are permanent in nature, they are dealt with separately in Section 1.
It may, however, be noted that small outdoor locations around building installations (for example, gardens around hotel installations or storage yards in industries) do not fall under the scope of Part 5. For requirements, pertaining to this, reference should be made to relevant parts of this Code.
Public Lighting Installations
One of the most common forms of permanent outdoor installations is the public lighting installations intended for lighting of public thoroughfares. With the availability of variety of light sources for such installations and the need for proper illumination of a variety of traffic routes and city centres, it has been found necessary to lay down guidelines for designing on efficient and economical lighting installation. This Section of this Code is intended to cover general principles governing the lighting of public thoroughfares and to lay down recommendations on the quantity and quality of lighting to be provided. The actual details of design would entirely depend on the local circumstances.
The requirements given in this Section are, as far as, practicably aligned with the recommendations of the International Commission on Illumination (CIE) modified to suit the local conditions and regulations.
4Classification
Ideally, both from the points of view of traffic safety and comfort, a high standard of lighting is advisable on all roads. The system of lighting, from good engineering point of view as well as economy should take into account all the relevant factors, such as the presence of factories, places of public resort, character of the street (whether a shopping area or a ring-road in non-built-up area), aesthetic considerations, the properties of the carriageway surface, the existence of lumps, bends or long straight stretches and over hanging trees, probable particle contamination in air due to road ambient conditions effecting out of smoke/smog/fog/vehicle exhaust.
4.1 The classification of lighting installations in public thorough fares given in 4.2 is based on volume, speed and composition of the traffic using them. It is left to the local engineer to decide upon the category of the lighting for the given road. Further, amplification of the types of thoroughfares can be had from Annex A, wherein description of terms is given for guidance.
4.2 Types of Roads
For the purposes of this Section, roads are classified as given in Table 1.
Table 1 Road Classification(Clause 4.2)
SI No.
Group[as in IS : 1944 (Part 1 and 2)]
Description
(1)
(2)
(3)
i)
A
Main Roads.
A1
Very important routes with rapid and dense traffic where safety, speed of traffic and comfort to drivers are the only consideration.
A2
Other main roads with considerable mixed traffic like main city streets, arterial roads, etc.
ii)
B
Secondary roads — Roads which do not require lighting up to Group A standard.
B1
Secondary roads of considerable traffic such as principal local traffic routes, shopping streets, etc.
B2
Secondary roads with comparatively light traffic.
iii)
C
Residential and unclassified roads. These are roads not included in Groups A and B.
iv)
D
Grade separated junctions, bridges, and elevated roads (see Note 2).
v)
E
Town and city centers and areas of civic importance (see Note 2).
vi)
F
Roads with special requirements (see Note 3).
vii)
G
Tunnels (roads underground).
NOTES
1 For the purposes of lighting installations, bridges are classified short or long when their lengths are less than or greater than 60 m.
2 Such areas are set apart since their standard of lighting is different from and higher than that described for other groups. Group E also includes important shopping streets, boulevards, promenades, and such other places which are the focus of special activities after dark.
3 Group F includes roads in the vicinity of aerodromes, railways, docks, and navigable waterways; where special lighting requirements are to be met in addition to compliance with general principles.
1Scope
1.1 This Section of the Code (Part 5/Sec 1) covers requirements of public lighting installations to provide guidance to those concerned with the preparation of public lighting schemes, their installation and maintenance (see also SP 72).
1.2 This Section deals only with electric lighting sources and does not include gas or other types of lighting.
1.3 This Section also does not cover exterior lighting installations, such as those which apply for parks, shopping enclaves, flood lighting of routes and structures of architectural importance, etc.
2References
IS No.
Title
SP 72 : 2010
National Lighting Code
1885 (Part 16/Sec 2) : 1968 Electrotechnical vocabulary: Part 16 Lighting, Section 2 General illumination lighting fittings and lighting for traffic and signalling
1944 (Parts 1 and 2) : 1970 Code of practice for lighting of public thorough fares:
Part 1 General principles
Part 2 Lighting for traffic routes (Groups A1, A2, B1 and B2) (first revision)
1944 (Part 5) : 1981 Code of practice for lighting of public thoroughfares: Part 5 Lighting of grade separated junctions, bridges, and elevated road (Group D)
1944 (Part 6) : 1981 Code of practice for lighting of public thoroughfares: Part 6 Lighting for town and city centres and areas of civic importance (Group E)
3Terminology
For the purpose of this Section, the following terms together with those provided in IS 1885 (Part 16/Sec 2) shall apply.
3.1 Terms Relating to Highways
3.1.1 Highway — A way for the passage of vehicular traffic over which such traffic may lawfully pass.
3.1.2 Layout — All those physical features of a high way other than the surfacing of the carriage way, which must be considered in planning a lighting installation.
3.1.3 Carriageway — That portion of a highway intended primarily for vehicular traffic.
3.1.4 Dual Carriageway — A layout of the separated carriageways, each reserved for traffic in one direction only.
SP 30 : 2023
3.1.5 Central Reserve — A longitudinal space dividing a dual carriageway.
3.1.6 Service Road — A subsidiary road between principle road and buildings or properties facing thereon or a parallel road to the principal road and giving access to the premises and connected only at selected points with the principle road.
3.1.7 Cycle Track — A way or part of a highway for use by pedal cycles only.
3.1.8 Footway — That portion of a road reserved exclusively for pedestrians.
3.1.9 Verge — The unpaved area flanking a carriageway, forming part of the highway and substantially at the same level as the carriageway.
3.1.10 Shoulder — A strip of highway adjacent to and level with the main carriageway to provide an opportunity for vehicles to leave the carriageway in an emergency.
3.1.11 Refuge — A raised platform or a guarded area so sited in the carriageway as to divide the streams of traffic and to provide a safety area for pedestrians.
3.1.12 Kerb — A border of stone, concrete or other rigid material formed at the edge of a carriageway.
3.2 Terms Relating to Lighting Installation. . p
3.2.1 Lighting Installation — The whole of the equipment provided for lighting the highway comprising the lamps, luminaires, means of support and electrical and other auxiliaries.
3.2.2 Lighting System — An array of luminaires having a characteristic light distribution sited in a manner concordant with this distribution (lighting systems are commonly designated by the name of the characteristic light distribution, for example, cut-off, semi-cut-off, etc.).
3.2.3 Luminaire — A housing for one or more lamps, comprising a body and any refractor, reflector, diffuser, or enclosure associated with the lamp(s).
8Guidelines for Specific Locations
8.1 Several factors contribute to good public lighting and those are enumerated for guidance in various parts of IS 1944 series. Recommendations are made on the various components of design of public lighting installations and those require detailed calculations of the level and uniformity of illumination on the road surface and of glare. Several criteria may not be satisfied for want of data, such as characteristics of surface, etc. To get some idea of the extent to which the installation would perform, it may be preferable to make a mock-up installation of a few luminaires on a stretch of road to be lighted.
8.2 Tables 6, 7 and 8 give a summary of recommendations on the various types of thoroughfares. These shall be used as ready reckoners, though for a detailed guidance reference should be made to the relevant part of IS 1944.
NOTE — Recommendations for Groups C, F and G lighting gear are under consideration.
Table 6 Lighting Installation in Group A and B Roads
(Clause 8.2)
Sl No
Description
Group A1
Group A2
Group B2
Group B2
(1)
(2)
(3)
(4)
(5)
(6)
i)
Average level of illumination on road surface, lux
30
15
8
4
ii)
Ratio minimum/average illumination ratio
0.4
0.4
0.3
0.3
iii)
Transverse variation of illumination, percent
33
33
20
20
iv)
Preferred Type of luminaire:
Cut-off
Cut-off
Cut-off or semi cut-off
Cut-off or semi cut-off
Permitted
Semi-cut-off
Semi cut-off
Non cut-off
Non cut-off
v)
Mounting height, m
9-10
9-10
7.5-9
7.5-9
vi)
Maximum spacing of luminaire/height ratio
Cut-off = 3
Cut-off = 3
6Design
6.1 Lighting Layout of Roads
The design, spacing and column heights are governed by the road-width and the classification of the roads. Typical layouts for various road width are given in Table 2. (See also Fig. 2.)
Table 2 Classification of Roads and Recommended Arrangement of Columns
(Clause 6.1)
Sl No.
Width of Carriage Way (m)
Group
Arrangement as in Fig.
Column Height H (m)
Spacing S
(1)
(2)
(3)
(4)
(5)
(6)
i)
24
A1
2F
9-14
2.5-3.0 H
ii)
A2
2E
9
2.5 H
iii)
18-20
A1
2D
9-14
2.5-3.0 H
iv)
2C
9
2.5 H
v)
A2
2D
9
2.5 H
vi)
2C
9
2.5 H
vii)
B1
2C
9
3.0 H
viii)
12
A2
2C
9
2.5 H
ix)
B1
2C
9
3.0 H
x)
B2
2B
9
3.0 H
xi)
C
2B
9
2.0 H
xii)
9
B2
2B
9
3.0 H
xiii)
C
2B
7
3.5 H
xiv)
6
C
2A
7
3.5 H
6.2 Lighting Layout of Flyovers
The design and column heights on flyovers are governed by the layout of flyovers, height above normal ground level and the width of the low-level roads. The spacing may be governed by the structural design of the flyovers. The layout of typical flyovers is given in Fig. 3A to 3D.
5General Principles
5.1 Aims of Public Lighting Installations
5.1.1 Main Roads
The aim of public lighting along main roads, bridges and flyovers (Groups A, B and D) is to permit users of the roads at night to move about with greatest possible safety and comfort so that the traffic capacity of the road at night is as much equal to that planned for daytime as possible. Towards this, end consideration has to be given designing the lighting on road junctions and pedestrian crossings so that these can be easily identified by the drivers.
5.1.2 Roads in Residential Areas
The principle aim of public lighting along roads in residential areas (Group C) is to provide light along the stretch of carriage way and footpath for safety and comfort of road users mainly the pedestrians; consideration has to be given to ensure that the lighting is soft and does not cause glare.
5.1.3 Roads in City Centres
The main consideration while designing the lighting in city centres (Group E) is proper illumination of footpaths for pedestrians, besides the comfort of the drivers. Also, care is required to easily identify flow of traffic and road dividers, islands, roundabouts, etc.
5.1.4 Roads with Special Requirements (Group F)
Separate considerations are required to be given for each of the following:
a) Airports
The main consideration in designing lighting of roads in the vicinity of airports is to ensure that under no circumstances, would a pilot mistake the stretch of the road as airport landing strip/runway/taxiway on airport
at night time. Also the pattern of luminaire siting and colour of light source should no way resemble/match the runway. Also, the lamps should not cause glare to the pilot either while taking off or more specifically while landing, which may interfere with his/her judgement.
b) Railways and docks
The driver of the railway is required to observe a number of signal should the tracks in the course of his work. It is necessary that none of the street lamps either glare to the driver or is mistaken by the driver for track signals due to/form/shape/colour of the light. Similar considerations are applicable to navigators in the vicinity of docks.
5.2 Principles of Vision in Public Lighting
9Power Installation Requirements
9.1 The electrical design aspects of public lighting installations not only consider the illumination principles, but also economic considerations giving allowance for cost of electrical control units, cable ducts, switching, etc.
9.1.1 Lamps and Luminaires
All lamps and luminaires and other fittings used in public lighting installations shall conform to the relevant Indian Standards.
9.2 Cables
9.2.1 Underground cables shall be laid for power supply to the streetlamps. For roads under Groups A, B and D, separate mains shall be laid for group control of lamps on these roads. The street lighting cables shall be terminated in separate junction boxes or street lighting pillars. The pillars shall be provided with electrically operated contactors of suitable current rating. Auxiliary terminals of these contactors could provide facility of return indication in case of supervisory remote control. In addition, as an alternative to this, it should have programmable timers to facilitate automatic time-based switching control depending on seasonal variations
in sunrise/sunset. The contactor circuits shall be provided with externally mounted switches for local manual operation. A typical street lighting pillar with control circuit is shown in Fig. 12.
9.2.2 The cable circuits for each section of the roads shall be so designed as to prevent important section of the roads from being completely off in case of a fault on the underground cables. For roads under Groups A1, A2 and D, each stretch of road shall be lit by two independent circuits, preferably emanating from two separate street lighting pillars.
For junctions also, the lamps shall be divided into at least two circuits in such a way that in case of fault on one circuit the entire junction or a section of it does not become completely dark.
Table 8Lighting Installations in Group E Roads
SI No.
Description
Remarks
(1)
(2)
(3)
i)
Main squares [see IS 1944 (Part 6)]:
1) Average level of illumination, lux
20
7Selection of Equipment
7.1 Electric Light Sources
The choice of source for public lighting is guided by the following considerations:
a) Luminous flux,
b) Economy (determined by lumens/watt and life),
c) Dimensions of the light sources, and
d) Colour characteristics.
7.1.1 The sources normally used in public lighting are:
a) LED lamps,
b) Sodium vapour lamps,
c) Metal-halide lamps, and
d) High pressure sodium vapour lamps.
7.1.1.1 LED lamps
These lamps are the most improved version of a light source with efficacy to the order of 100-140 lm/W with better colour rendering as well as colour changing capability. It is the most energy efficient and satisfactory solution as off now for operational economy. Also, luminaires can be made more compact due to variety in placement of LED formations making dimensions of these lamps flexible. It also has superior light control for specific applications.
7.1.1.2 Sodium vapour lamps
The use of sodium lamps is convenient when colour rendering is not important and when a high luminous efficacy is desired. Their colour is sometimes useful to provide visual guidance. It is also particularly suitable under foggy conditions. However, now a days these lamps are getting obsolete due to introduction of LED lamps which are widely used due to energy saving drive promoted by Government.
7.1.1.3 Metal halide lamps
These lamps are improved versions of HPMV lamps and having very much higher efficiencies in the order of 80 lm/W combined with good colour characteristics. However, now a days, these lamps are getting obsolete due to introduction of LED lamps which are widely used due to energy saving drive promoted by Government.
7.1.1.4 High pressure sodium vapour lamps
These lamps are improved versions of sodium vapour with efficiency of the order of to 100 lm/W with colour rendering satisfactory and of dimensions suited to fittings of small size and accurate light control. However, now
a days, these lamps are getting obsolete due to introduction of LED lamps which are widely used due to energy saving drive promoted by Government.
7.2 Luminaires
The luminaire has double role of protecting the light source from the weather and redistributing the luminous flux of the source. In the choice of the luminaire the following points should be considered:
10Miscellaneous Considerations
10.1 Aesthetics
The aesthetics of a lighting installation are principally judged by day. Half of the time, the lighting installation serves no useful purpose; an attractive or at least a non-disturbing daytime appearance which harmonises well with the surroundings is, therefore, of great importance. Aesthetic considerations should relate to the unit formed by the luminaire and its support and the situation in which it is placed.
647
Firstly, the unit formed by the luminaire and its support should be considered. Secondly, the siting of the luminaires in the scene may lead to unpleasant effects even if the luminaires themselves considered in isolation, are aesthetic. There are no simple or universal rules for aesthetically satisfactory design and layout since every city, town and village has its own character and what may look well in one place may be incongruous in another.
The points of general application are:
a) Design and siting;
b) Columns and surroundings;
c) Size and type of luminaire;
d) Form of bracket;
e) Assembly of column, bracket and luminaire;
f) Arrays of luminaires; and
g) Material and colour.
10.2 Lighting Columns as Hazards
A motor vehicle involved in an accident frequently leaves the carriageway and the probability of this happening increases with the speed of the vehicle. If the vehicle collides with a lighting column the severity of injuries to the occupants is likely to be increased. There is evidence to suggest that the number of such collisions decreases with the increase of distance of the column from the edge of the carriageway.
Normally the clearance between column and carriageway should be at least 1.5 m. Where there is a footway close to the carriageway, the column should be sited behind the footway. In exceptional cases, a smaller clearance may be used.
If possible, the column itself can be provided with reflective coating up to 1.5-2 m from ground in order to achieve enhanced visual presence in dusty/dim atmosphere.
8Protection and Safety
8.1 The installation shall be protected against overload, short circuit and earth leakage by suitable protective devices.
655
8.2 At the mains incoming the protective earth conductor and the Neutral of the supply system shall be interconnected. If this connection is not allowed by the power supplier, a residual current device (RCCB or CBCT with relay) with a residual current not higher than 30 mA shall be installed at the origin of installation.
8.3 The fault loop impedance at the origin and sub circuits shall be lesser to allow disconnection of supply. This shall be measured to ensure automatic disconnection of supply during fault.
8.4 Temporary supply is generally used at public places and for public functions and, therefore, extreme care shall be taken to ensure that there is no risk of any type of hazard either from electrical shock or fire. No flammable material shall be stored near the service intake point or the operational area of electrical equipment or appliances. For large public functions, exhibitions, etc., suitable fire extinguishers shall be kept at the supply intake point and near the main switch of the installation.
8.5 In construction sites, protection of persons against indirect contact shall be assured by automatic disconnection of supply appropriate to the system of earthing. Socket outlet shall either be protected by residual current devices having operating current not exceeding 30 mA or be supplied by safety extra low voltage or electrical separation of circuit each socket outlet being supplied by a separate transformer.
8.6 All temporary and portable DB’s shall be of double insulated type.
8.7 Plugs, sockets and couplers used shall be of industrial grade confirming to IS/IEC 60309 (Parts 1 and 2). All outdoor sockets shall be of IP 67. Supplies to emergency services shall be fed from sockets having interlock facility to limit unauthorised use.
9Testing and Commissioning
9.1 Supply to all temporary installations should be connected by a specific date for the user and therefore, the installation work meant for types of installations in 4.1(a), (b) and (c) shall be ready at least 24 h prior to connection of supply, so as to properly test the installation and find the loads in different sub-circuits. In the case of installation described in 4.1(c), there should be a period of at least 6 h after completion of the work and prior to connecting supply for the purpose of testing the installation and visual inspection.
9.2 The various tests on the installation shall be carried out as laid down in Part 1/Section 14 and Part 3 of this Code.
9.3 When the specified duration of use of the installation as defined in 3.1 is required to be extended beyond the stipulated period of 6 months, the guidelines specified in this Section shall be applicable subject to fresh inspection and tests as above, with the prior approval of the supply authority.
7Additional Requirements for Temporary Outdoor Installations
7.1 Supply Intake Arrangements
The type of outdoor installations will depend on the magnitude and duration of the installation. Depending on the availability of spare capacity, of the existing distribution system, the supply intake arrangements could be through either of the following:
a) A HV feeder,
b) A HV feeder and step-down transformer,
c) LV SERVICE LINE (SINGLE/THREE PHASE), or
d) A tapping form one of the existing service connection.
One construction site may be served by several sources of supply, including fixed or mobile power generators. All the circuits supplied from the same point of supply comprise one installation and it is important to clearly differentiate them; in particular, a single distribution point, cabinet or distribution board shall consist of only components belonging to one and the same installation except for circuits for standby supplies, signalling or control.
7.1.1 Commissioning of Substation
In case the loads at construction sites or to exhibitions, circuses, etc, are large and the power supply authority has no network in the vicinity of the temporary installation that could be utilised then it would be necessary to
establish a temporary substation where the switchgear and transformer can be installed. The substation site shall be so selected that it is as close to the load centre as possible.
The power supply authority’s line should be brought up to the substation in a separate enclosure. If overhead line is laid up to the temporary substation, then the supporting poles, conductors, materials of the line, insulation and the method of stringing the conductors and the mechanical strength of the line as a whole shall conform to the relevant provisions of IS 5613 (Part 1/Sec 1) and IS 5613 (Part 1/Sec 2). In case supply at voltages above 650 V is required, a suitable enclosure to install the switchgear and the metering arrangement shall also be erected.
7.1.2 Power Distribution
7.1.2.1 At the origin of each installation a unit containing the main control gear and the principal protective device shall be provided. Incoming OCPD shall be installed in an earthed metallic enclosure and as close to the metering point as possible (see also 7.2.1.1). The fault loop impedance and the prospective fault current at the origin of installation shall be measured. Type and rating and the OCPD shall be selected based on this measurement in order to ensure automatic disconnection with in the time specified in IS 3043 and IS 732.
3.2.4 Outreach — The distance measured horizontally between the centre of the column or wall face and the centre of a luminaire (see Fig. 1).
p= outreach, h = mounting height of luminaires, s = overhang, L = width of the carriage way d p = outreach, h = mounting height of luminaires, s = overhang, L = width of the carriage way d – Spacing, – Spc = clearance
Fig. 1 Siting of Luminaires Characteristic Dimensions
PART 5 OUTDOOR INSTALLATIONSy .
3.2.5 Overhang — The distance measured horizontally between the centre of a luminaire mounted on a bracket and the adjacent edge of the carriageway (see Fig. 1).
3.2.6 Mounting Height — The vertical distance between the centre of the luminaire and the surface of the carriage (see Fig. 1).
3.2.7 Spacing — The distance, measured along the centre line of the carriageway, between successive luminaires in an installation (see Fig. 1).
NOTE — In a staggered arrangement, the distance is measured, along the centre line of the carriageway, between a luminaire on one side of the carriageway and the next luminaire, which is on the other side of the carriage. It is not the distance measured on the diagonal joining them, nor the distance between successive luminaires on the same side of the carriageway.
3.2.8 Span — That part of the highway lying between successive luminaires in an installation.
3.2.9 Width of Carriageway — The distance between kerb lines measured at right angles to the length of the carriage way (see Fig. 1).
3.2.10 Arrangement — The pattern according to which luminaires are sited on plan, for example, staggered, axial, opposite.
3.2.11 Geometry (of a Lighting System) — The inter related linear dimensions and characteristics of the system, namely the spacing, mounting height, width, overhang and arrangement.
3.3 Photometric Terms
3.3.1 Luminous Flux — The light given by a light source or a luminaire or received by a surface irrespective of the directions in which it is distributed. The unit of the luminous flux is lumen (l m).
3.3.2 Lower Hemispherical Flux or Downward Flux — The luminous flux emitted by a luminaire in all directions below the horizontal.
3.3.3 Luminous Intensity — The quantity which describes the light-giving power of a luminaire in any direction. The unit of luminous intensity is Candela (cd).
3.3.4 Illumination — The luminous flux incident on a surface per unit area. The unit of illumination is lumen per square metre (lux).
3.3.5 Luminance (at a Point of Surface and in a Given Direction) — The luminous intensity per unit projected area of a surface. If a very small portion of a surface has an intensity I in a particular direction and its orthogonal projection (that is, its projection on a plane perpendicular to the given direction) has an area D, the luminance in this direction is I/D candelas per unit area. The usual unit is candela per square metre (cd/m2).
3.3.6 Luminosity — The attribute of visual sensation according to which an area appears to emit more or less light. It is sometimes called brightness.
NOTE — Luminosity is the visual sensation which correlates approximately with the photometric quantity ‘luminance’.
3.3.7 Light Output — The luminous flux emitted by a luminaire.
3.3.8 Light Distribution — The distribution of luminous intensity from a luminaire in various directions in space.
3.3.9 Symmetrical (Converse Asymmetrical) Distribution — A distribution of luminous intensity which is substantially symmetrical (conversely asymmetrical) about the vertical axis of the luminaire.
3.3.10 Axial (Converse Non-axial) Distribution — An asymmetrical distribution in which the directions of maximum luminous intensity lie (do not lie) in vertical planes substantially parallel to the axis of the carriageway.
3.3.11 Peak Intensity Ratio — The ratio of the maximum intensity to the mean hemispherical intensity of the light emitted below the horizontal.
3.3.12 Mean Hemispherical Intensity — The downward flux divided by 6.28 (2π) (this is the average intensity in the lower hemisphere).
3.3.13 Intensity Ratio (in a Particular Direction) — The ratio of an actual intensity from the luminaire (in a particular direction) to the mean hemispherical intensity.
3.3.14 Beam — The portion of the light output of the luminaire contained by the solid angle subtended at the effective centre of the luminaire containing the maximum intensity, but no intensity less than 90 percent of the maximum intensity.
3.3.15 Beam Centre — A direction midway between the directions for which the intensity is 90 percent of the maximum in a vertical plane through the maximum and on a conical surface through the maximum.
623
3.3.16 Isocandela Curve — A curve traced on an imaginary sphere with a source at its centre and joining all the points corresponding to those directions in which the luminous intensity is the same or a plane projection of this curve.
3.3.17 Isocandela Diagram — An array of Isocandela curves.
3.3.18 Polar Curve — Curve of light distribution using polar co-ordinates.
3.4 Terms Relating to Luminaires
3.4.1 Street Lighting Luminaire — A housing for a light source or sources, together with any refractor, reflector, dispersive surround or other enclosure which may be associated with the source in order to modify the light distribution in a desired manner and protect the light from weather conditions and insects and/or for the sake of appearance, brightness and other lighting characteristic the source.
3.4.2 Cut-off Luminaire — Luminaire employing the technique used for concealing lamps and surfaces of high luminance from direct view in order to reduce glare.
3.4.3 Semi-cut-off Luminaire — Luminaire employing the technique for concealing lamps and surfaces of high luminance from direct view in order to reduce glare but to a lesser degree than cut-off luminaire.
3.4.4 Integral Luminaire — Luminaire with all its accessories, such as ballasts, starters, igniters, capacitors, etc. However, integrally with the body of the luminaire.
3.4.5 Post Top Luminaire — Luminaire with arrangement for mounting the same symmetrically on the top of the column.
Semi-cut-off = 3.5
Semi-cut-off = 3.5
Non-cut-off = 4
NOTES
1 In Group A lighting, the level and uniformity of illumination shall be as high as possible and the glare strictly reduced.
2 In Group B lighting, greater tolerances on uniformity and glare are admitted, which may be justified by the character of the roads and by the presence of facades.
3 Mounting heights less than 7.5 m are undesirable except in special cases, such as lighting of residential roads or roads bordered by trees.
Table 7 Lighting Installations in Group D Roads
(Clause 8.2)
Sl No.
Description
Remarks
(1)
(2)
(3)
i)
A
Grade Separated Junctions
1 Lighting by conventional street lighting technique Complex junctions:
a) General principles
See IS 1944 (Parts 1 and 2)
b) Mounting height, m
10-12
c) Luminaire
cut-off
d) Light sources
LED or HPSV lamps
2 Lighting by high-mast lighting
a) Minimum service level value (lux)
30
b) Uniformity ratio (avg)
0.4
c) Height of masts, m
Not less than 20
d) Choice of luminaire
see IS 1944 (Parts 1 and 2)
ii)
B
Bridges
1 Short bridges (<60 m)
Normal street lighting techniques with minor adjustments [see IS 1944 (Part 5)]
2 Long bridges (>60 m)
See IS 1944 (Part 5)
3 Bridges of historical importance
Special considerations apply
4 Parapet lighting
a) Mounting height, m
Not greater than 1
b) Separation between rows of lighting, m
Not greater than 12
c) Choice of lamps
LED, HPSV lamps or other linear sources of luminance weatherproof, dustproof, vermin proof, robust
5 Footbridges
a) Illumination, lux
Not less than 6
iii)
C
Elevated Roads
a) General lighting
Like heavy traffic roads
b) Choice of luminaire
Cut-off
6.2.1 The layout with recommended arrangements, column heights and spacing for various road widths on flyover are given in the Table 3.
Fig. 2 Standard Layouts for Roads (Six Alternatives)
3A
End A
3B
ighting column provided in both sides of flyover – main roFree Standard provided by BIS via BSB Edge Private Limited to self-developer - bengaluru(shivaprasad.safare@tandemloop.in) 49.204.144.146.
3C
Fig. 3 Standard Layouts for Flyovers (Four Alternatives)
n frequency above the flyover maintained same, increasTable 3 Recommended Arrangement of Columns on Flyovers unction avoi(Clause 6.2.1)
Sl No.
Width of Carriage Way (m)
Group
Arrangement as in Fig.
ColumnHeight H¹⁾ (m)
Spacing S
(1)
(2)
(3)
(4)
(5)
(6)
i)
12
D
3C
9
2-2.5 H
ii)
D
3B
9
2 H
iii)
9
D
3A
9
2 H
¹⁾ Above the flyover road level.
6.2.2 The layouts with recommended arrangements, column heights and spacing for various road widths of low-level road are given in Table 4.
Table 4Recommended Arrangement of Columns on Flyovers (Low Level Roads)
(Sl No.
Width of Carriage Way (m)
Group
Arrangement as in Fig.
Column Height H¹⁾ (m)
Spacing S
(1)
(2)
(3)
(4)
(5)
(6)
i)
Over 20
D
3C
9
2.5 H
ii)
10 - 20
D
3D
14
1.5 H
iii)
Upto 10
D
3A
9
2.5 H
¹⁾ Above low-level road
6.3 Junctions
Spacing of columns at the junction should be 50 to 75 percent of the normal spacing of columns on the main roads. These columns may be installed on the traffic islands located at the junctions.
6.3.1 The level of illumination at the junction should be substantially higher than the nearby roads. The junctions may be lighted by either of the following methods:
a) Higher level of illumination — In case this scheme is adopted, the level of illuminations should be 150 percent of that of the roads.
b) Change in height of columns — The size of columns adopted at the junction should be higher than those adopted on roads. Recommended sizes are given in Table 5.
c) Change in the colour of the light source — In case the main road and the junction is lit by LED lamp then colour of light of these locations should differ from each other.
Table 5Recommended Variation in Height of Columns of Junctions [Clause 6.3.1 (b)]
Sl No.
Height of Columns on Roads
Recommended Height of Columns at Junctions
(1)
(2)
(3)
i)
7
9
ii)
9
14
iii)
14
High mast
6.3.2 The different types of junctions commonly encountered are discussed below in details as they require special consideration:
a) Simple two road junction — This type of junction should be illuminated by locating the columns in such configuration that the junction is noticed by fast moving traffic from considerably far away distance in order to manoeuvre the vehicle better. The design would depend upon existence of traffic islands at the junctions. Typical layouts of such junctions are shown in Fig. 4A to Fig. 4C.
b) Junction of two major roads — These junctions would generally be provided with traffic island at suitable locations to regulate flow of traffic. The lighting columns could be located in the islands to advantage. However, if the junctions are too wide or the islands do not permit planting of poles within the desired spacing, special considerations are required. Typical layouts of such junctions are shown in Fig. 5A to 5C.
c) Multiple road junctions — The lighting of multiple road junction would depend upon the geographical layout of the roads, the width of the various roads and most important, the traffic conditions. At such junctions invariably entry for traffic may not be permitted on all the roads. Similarly, the traffic islands design would change from location to location. Special consideration will have to be given to the design of lighting of such junction. Typical layouts of such junctions are shown in Fig. 6A to 6D.
Fig. 4 Simple Two Road Junctions (Three Alternatives)
o = Locations of Columns
Fig. 5 Junction of Two Major Roads (Three Alternatives)
Free Standard provided by BIS via BSB Edge Private Limited to self-developer - equ remen sbengaluru(shivaprasad.safare@tandemloop.in) 49.204.144.146.
Multiple road junctions with roundabouts are much easier to design as a definite central roundabout is available topose/present any danger due to confusion of navigated airborne objects. The following points locate the columns. Two types of roundabouts are discussed below:should, therefore, be kept in view while designing lighting sche
a) Islands which are clear or have only parking lots — The lighting of these could be advantageously achievedb) Lights mounted on the electric poles/pylons shall not cause an obstruction to the by use of high mast as given in Fig. 7A and 7B or semi-high mast lighting as in Fig. 7C and Fig. 7D.a) The light provided in the vicinity of an aerodrome shall be properly screened to avoid any arriving and departing aircraft from an aerodrome in terms of obstacle limitation specif
b) Islands which have gardens or other construction which would be obstruction to line of vision of traffic glare/upward luminance which may otherwise endanger safety of an aircraft arriving and by theairport authorities. The lighting of these could be either by semi-high mast as in Fig. 8A or conventional lighting as in Fig. 8Bdeparting from an aerodrome. and 8C.
7 C
Fig. 7 Use of High Mast, Semi-High — Mast Luminaires in Roundabouts (Four Alternate) (Continued)
SE OF HIGH MAST, SEMI-HIGH –MAST LUMINAIRES IN ROUNDABOUTS (Fig. 7 Use of High Mast, Semi-High — Mast Luminaires ALTERNATE)in Roundabouts (Four Alternate) (Concluded)
6.5 Road Lighting in the Vicinity of Aerodrome
6.5.1 General Requirements
When a proposed road lighting scheme is within 5 km of the boundary of an aerodrome it is essential that appropriate aviation authority is consulted regarding any restrictions and precautions to be observed that may be necessary.
6.5.2 The aviation authority may have a specific interest in the pattern of the layout, the mounting height, the colour and intensity, distribution of light emitted above the horizontal so that lighting installation appears distinctly different/dissimilar in light colour/pattern/placement in order not to pose/present any danger due to confusion of navigated airborne objects. The following points should, therefore, be kept in view while designing lighting scheme in the vicinity of the aerodromes:
a) The light provided in the vicinity of an aerodrome shall be properly screened to avoid any glare/upward luminance which may otherwise endanger safety of an aircraft arriving and departing from an aerodrome.
b) Lights mounted on the electric poles/pylons shall not cause an obstruction to the arriving and departing aircraft from an aerodrome in terms of obstacle limitation specified by theairport authorities.
c) It is particularly important to ensure that lighting of the road cannot ever be confused with the ground lighting of the flight paths by the pilots. Following conditions should be ensured:
In case roads are not parallel to landing strips:
i) Uniform design and spacing of columns is not recommended.
ii) Arrangement of mounting columns on opposite as in Fig. 2C, 2E is not recommended.
In case roads within airport boundaries are parallel to landing strips, no lighting should be provided on the stretch of such parallel road near the landing strip.
6.6 Road Lighting in Vicinity of Railways, Docks and Navigable Waterways
In lighting for roads in the vicinity of railways, docks and navigable waterways, because of the colour of the light source may interfere with the proper recognition of signal system, it is essential that this interference is avoided, but local conditions vary so widely that it is not possible to lay down any rigid code applicable to all circumstances.
6.6.1 Requirements
The following requirements are likely to apply in all places where roads are so located that their lighting installation may affect the operation of railways, docks and navigable waterways.
6.6.2 Consultations
It is essential that prior consultation is made with the appropriate authorities regarding any special provision that may be necessary. These provisions should be met in a way that is mutually acceptable so that they may be incorporated at the design stage.
Fig. 8 Use of Semi-Mast or Conventional Lighting in Roundabouts (Three Alternatives)
6.6.3 Colour
Where any form of road lighting is employed there is a risk of confusion with signal light. This may necessitate careful selection of light source, siting of luminaires or the use of appropriate screened luminaire at certain points and heights.
6.6.4 Glare and Masking
The position of individual light source on the road may fall in line with signal lights and even when fairly remote may mask them or make them difficult to recognise or may hamper the vision because of glare. If these cannot be avoided by re-siting, it may be necessary to employ screening to obviate the interference even though the colour of the light source is not objectionable.
6.6.5 Screening
In all cases where screening of a light source is required, this should preferably be achieved by means of properly designed luminaires and not by addition of unsightly screens to normal luminaires.
6.6.6 Siting
If the road is bordered by water (lake, river or canal) and if the lighting is single sided, it is recommended that the columns be sited, if possible, on the waterside.
6.6.7 Penetration
Selected luminaire should have high ability to penetrate the vicinity under lighting during rainy/stormy/dusty/ foggy/smoggy atmosphere at any time of day/night.
Though public lighting has to satisfy both drivers and pedestrians, it is in practice requirements of the drivers which are more stringent. The following principles are considered essential [see also IS 1944 (Parts 1 and 2)].
5.2.1 Requirements of Drivers
These are as follows:
a) Visibility of the whole of the road and its details, such as entry of side-roads, intersecting roads traffic signs, etc.;
b) Visual guidance on the alignment of the road;
625
c) Clear visibility of objects in time;
d) Good seeing condition by silhouette vision;
e) Continuity and uniformity of lighting; and
f) General or special lighting of signs.
5.2.2 Visual Field of the Driver
The visual field of the driver comprises, in order of decreasing importance:
a) The carriageway;
b) The surrounds around /along the road, including signs; and
c) The sky, including the bright luminaires.
5.2.3 Visibility
The phenomenon of visibility is directly related to contrast. Good contrast should always be produced:
a) Between the carriageway and all objects which indicate its boundaries; and
b) Between any obstacles which may be present and the background against which it appears; since the characteristics of the obstacles may vary over a very wide range, any factor which tends to increase contrast should be exploited.
5.2.4 Glare and Visual Comfort
Glare in public lighting is generally caused by the luminaires. Other factors that can lead to glare are presence of undesirable large surface of high reflection factor, specular surfaces, excessively bright shop windows, advertisement signs or road direction signs.
5.3 Criteria of Quality
The following four factors contribute to the fundamental criteria of quality of public lighting:
a) Level of luminance,
b) Uniformity of luminance,
c) Limitation of glare,
d) Optical guidance, and
e) Atmospheric pollution due to season/traffic.
5.3.1 Level of Luminance
The level of luminance should be adequate to provide visibility which guarantee for the user a maximum of safety and sufficient visual comfort. It is obvious that it is the road surface luminance rather than the illumination level which provides for an accurate measure of the effective light in a street lighting installation. However, with
the present state of technique and the knowledge of reflection properties of road surfaces, the calculation and measurement of luminance are likely to present difficulties. Reference may be made to 8.2 regarding illumination values to be provided on the road surfaces.
5.3.2 Uniformity of Luminance
This provides visual comfort for the driver.
5.3.3 Limitation of Glare
It is required to control the glare caused due to luminaires at a value which keeps the visual discomfort below an acceptable level.
5.3.4 Visual Guidance
A good visual guidance is required especially in long stretches of the road and even more on complicated intersections, roundabouts, etc. Most of the long-range guidance is offered by the luminaires.
2) Mounting height, m
10-15
ii)
Shopping streets/promenades
Special considerations
iii)
Pedestrian precincts
1) Average horizontal illuminance (footway level), lux
20
2) Average horizontal illuminance (under canopies), lux
50
3) Mounting height, m
5-6
4) Luminaires
Special considerations
iv)
Public car parks (above ground)
1) Average horizontal illuminance, lux
10
2) Luminaires preferred
Floodlight luminaries on high masts
v)
Pedestrian stairways/footbridges
1) Average level of illuminance (surface of footbridge), lux
6
2) Average level of illuminance (sub-ways), lux
10
9.2.3 In case of roads in groups A, B and D, the cables shall preferably be terminated into the column junction boxes by looping rather than ‘T’ joints using appropriate type of terminal block/connector strip with terminal protection shroud.
9.2.4 Underground cables of suitable sizes should be utilised for the purpose of control. The recommended sizes of the cables for various installations are shown in Table 9.
Table 9 Recommended Types and Sizes of Cables(Clause 9.2.4)
Sl No.
Round Group
Preferred Size of Cables (sq.mm.)
Type of Cables
Max. No. of Luminaries to be Looped per Circuit
Max Length of Cable per Circuit
(1)
(2)
(3)
(4)
(5)
(6)
i)
A1
4 to 25
3-phase, 4-core
The maximum no of luminaries and maximum length shall be selected subject to a maximum allowed voltage drop of 6 percent
ii)
A2
3-phase, 4-core
iii)
B1
3-phase, 4-core
iv)
B2
Up to 10 sq mm copper and higher sizes aluminum
1-phase/3-phase, 4-core
v)
C
1-phase/3-phase, 4-core
vi)
D
3-phase, 4-core
Special care shall be taken in Neutral conductor in order to avoid temporary over voltage due to loss of neutral. Up to 6/10 mm2 cables with copper conductor are recommended and higher sizes, cables with aluminium conductors are preferred.
9.2.5 The distribution board with suitable sized contactors with independent MCB’s shall be provided for each phase. The contactors shall be controlled by electrically operated switches mounted for external manual/local operation.
9.2.6 Safety against electrocution shall be ensured by installing protective device as:
a) Type and rating of MCB is selected considering, a fault at the final light shall ensure automatic disconnection of the MCB. The fault loop impedance shall be lower enough to enable automatic disconnection in case a TN network is used.
b) If this condition in Sl. No. (1) cannot be fulfilled, every circuit shall be protected by an RCBO with a residual current not larger than 30 mA.
9.2.7 Street lights in gardens, parks and inside housing colonies shall be supplied from RCBO with a residual current not larger than 30 mA.
9.3 Power Supply
The supply to the streetlights may be either through overhead wires or underground cables. The supply to lamps on roads under Groups A, B and D, should preferably be by underground cables laid specially for street lighting purposes. In case overhead wires are employed these should also be suitable for street lighting purposes.
The following power supply configurations is provided for information.
9.3.1 TN-S System with MCB of Suitable Rating and RCD Not Larger than 30 mA at Distribution Board (DB)
Safety is achieved by automatic disconnection of supply during fault. 3 phase, Neutral and earth conductor starts from the DB, runs up to the last light as shown in Fig. 9.
Fig. 9 Street Lighting Pillar - TN-S System
9.3.2 TN-C-S System with MCB of Suitable Rating and RCD Not Larger than 30 mA
Safety is achieved by automatic disconnection of supply during fault. 3 phase and combined neutral and protective earth conductor starts from the DB, runs up to the last light as shown in Fig. 10. No need of a separate earth conductor. However, neutral and earth shall be combined in the junction box as shown in Fig. 10. RCD’s at DB are not effective in this system. In case of any neutral disconnection, TOV will be limited in this system.
Since RCD’s at DB are not effective, the system shall be implemented with careful measurement of fault loop impedance and automatic disconnection. The outgoing MCB at the DB shall ensure automatic disconnection in case of a fault.
FIG. 10 STREET LIGHTING PILLAR - TN-C-S SYSTEMFig. 10 Street Lighting Pillar - Tn-C-S System
9.3.3 IT System
s u ea e . e a eu a co uc o a e co p e e y so a e o ea . ee g. . An isolation transformer is installed for the lightning circuit. Output side of the isolation transformer is unearthed. part to exposed conductive parts or to earth. Insulation monitoring devices are mandatory. Line and neutral conductor are completely isolated form earth. See Fig. 11. An insulation monitoring device. . Automatic disconnection during first fault is not necessary. However, the fault shall be rectified as shall be provided to indicate the occurrence of a first fault from a live part to exposed conductive parts or toAn isolation transformer is installed for the lightning circuit. Output side of the isolation transformer fast as possible. For further information on IT system, refer 4.2.11.6.3 of IS 732.earth. Insulation monitoring devices are mandatory. Automatic disconnection during first fault is not necessary.is unearthed. Line and neutral conductor are completely isolated form earth. See Fig. 11. An However, the fault shall be rectified as fast as possible. For further information on IT system, refer 4.2.11.6.3 ofpart to exposed conductive parts or to earth. Insulation monitoring devices are mandatory. IS 732.
tors may be provided with additional circuitry for remoteFig. 11 Street Lighting Pillar - IT System
street lighting. Special relFollowing schemes for remote c9.4 Control of Street Lighting Installations
con ac ors.a) Special Relay Control — This may be achieved by special control cables laid up to the 9.4.1 The contactors may be provided with additional circuitry for remote/automatic control. Following schemes suitable power sprovided. Thifor remote control are recommended:
contactors.a) Special Relay Control — This may be achieved by special control cables laid up to the street lighting. suitable power supply network and installing suitable sensors at control points.Special relays operated by normal supply or electronic impulses may be provided. This scheme enables return indication of the operation by auxiliary contacts of the contactors.
b) Ripple Control — This may be achieved by injecting audio frequency impulse through suitable power supply network and installing suitable sensors at control points.
9.4.2 Automatic Control
The contactors may, alternately, be controlled automatically by use of auto-control devices. The following controls are recommended:
a) Photoelectric Control — This may be achieved by installing suitably mounted photoelectric switches near the control points. The photoelectric switch shall be mounted so as to be free the glare caused by headlights of motor vehicles and protected from the weather.
b) Time Switches — The local electrically operated contractors may be controlled through time switches. The time switches may be manually spring would or electrically operated. In case of electrical operation, the time switches should be of electrically wound mechanically operated variety so as to prevent their being affected by variations in supply. However, these would need to be regulated from time to time due to seasonal variations.
c) Electronic Control Switches — It should be possible to install pre-programmed electronic micro-processors, with one-year seasonal variations. These could be installed for each individual lamp. With suitable design these could also be utilised to switch off unwanted lights after peak traffic hours are over.
d) Intelligent Digital Control Module — This may be achieved by introducing microprocessor based programmable control module wired /unwired (Sim card based) which can provide various control options depending on traffic density (Public/vehicle), natural light, on the spot atmospheric conditions, etc.
Typical street lighting 12A Typical street lighting
12B Inside layout12B Inside layout
12C Typical Contactor Wiring for Remote/Automatic
9.4.3 Black-out Control
Black-out control may be required to be adopted in case of war in vulnerable areas. This could be achieved by either of the following schemes:
a) Remote Control — Special control cables are laid (alternatively, use of telephone cables) to give control impulse to group control points. The control could then be utilised to switch off the lamps instantaneously on demand by civil defence authorities.
b) Ripple Control — In case special control cables are not available, ripple control equipment could be used with suitable sensing devices at the control points. When the need arises, the entire area could be switched off by ripple control impulse.
c) UHF Control — Electronic relays responding to pre-determined control frequency could be installed at each switching point. This could be programmed to switch off on demand by a pre- determined control frequency signal.
9.4.4 Brown-out Control
Brown-out control is necessary in vulnerable cities with heavy vehicular traffic at the time of war, where complete black-out is not practicable. Even in such cases, complete black-out would be necessary at the time of possible air raids. Following alternatives for brown-out control are recommended:
a) Voltage Control — This could be advantageously adopted in areas where the source of lighting is filament lamp. Applying reduced voltage to such lamps would automatically reduce the illumination to any desired level. In case of discharge lamps, this scheme would not be suitable.
b) Ripple Control — In case ripple control is adopted, it would be possible to programme alternate (or any other combination) lamps to respond to specified ripple control signals. In case of necessity, brown-out could be affected by switching off alternate lamps and complete black-out by switching off all the lamps.
c) Multiple Lamp Luminaires — On main roads, the luminaires adopted could have two or more lamps, each controlled either by different phase or by separate ripple control signals. In case of necessity, either one or two phases could be switched off, or alternately alternate lamps be switched off by suitable ripple control signals.
d) Replacement of Lamps — In case of prolonged brown-out operations, the wattage of the lamps could be reduced by replacing the same with lower wattage lamps. This, though could not be achieved on short notice is recommended in case of prolonged operations.
e) Microprocessor based intelligent wired/unwired (sim card based) control.
a) Nature and power of the source or sources;
b) Nature of the optical arrangements and the light distribution which they provide;
c) Light output ratio;
d) Whether the luminaire is open or closed type;
e) Resistance to heat, soiling, and corrosion;
f) Protection against collection of dust and insects;
g) Resistance to atmospheric conditions;
h) Ease of installation and maintenance;
j) Presence or absence of auxiliaries;
k) Fixing arrangements, the weight and area exposed to wind pressure; and
m) Ability to dissipate the heat generated by light source and control gear.
The influence of all these factors varies according to local circumstances and it is difficult to recommend one solution rather than another, but the attention of lighting designers may be drawn to the fact that the most economical installation can be achieved only by the choice of the most suitable luminaire, selected according to the relative importance of the above mentioned factors. There is, however, one essential characteristic of luminaires the choice of which directly influences the quality of the lighting, that is, the general form of its distribution curves of luminous intensity particularly in directions near the usual directions of vision.
7.2.1 The following general forms of light distribution are considered according to the degree of glare which is acceptable:
a) Post top integral luminaires,
b) Post top non-integral luminaires,
c) Cut-off integral luminaires,
d) Cut-off non-integral luminaires,
e) Semi-cut-off integral.
f) Non-cut-off tubular luminaires, and
g) Flood-lighting luminaires.
7.2.1.1 Cut-off luminaire
A luminaire whose light distribution is characterised by a rapid reduction of luminous intensity in the region between 80° and the horizontal. The intensity at the horizontal should not exceed 10 cd per 1 000 lm of flux from the light sources and the intensity at 80° is of the order of 30 cd per 1 000 lm. The direction of the maximum intensity may vary but should be below 65°. The principal advantage of the cut-off system is the reduction of glare and its use is favoured under the following conditions:
a) Matt carriageway surfaces;
b) Absence of buildings;
c) Presence of large trees;
d) Long straight sections;
e) Slight humps, bridges; and
f) Few intersections and obstructions.
7.2.1.2 Semi-cut-off luminaire
A luminaire whose light distribution is characterised by a less severe reduction in the intensity in the region 80° to 90°. The intensity at the horizontal should not exceed 50 cd per 1 000 lm of flux from the light sources (see Note) and the intensity at 80° is of the order of 1 000 cd per 1 000 lm. The direction of the maximum intensity may vary
SP 30 : 2023
but should be below 75°. The principal advantage of the semi-cut-off system is a greater flexibility in siting, and its use is favoured under the following conditions:
a) Smooth carriageway surfaces;
b) Buildings close to carriageway, especially those of architectural interest; and
c) Many intersections and obstructions.
NOTE — Subject to a maximum value of 1 000 cd whatever is the luminous flux emitted.
7.2.1.3 Non-cut-off luminaire
A luminaire whose luminous intensity in directions making an angle equal to or greater than 80° from the downward vertical is not reduced materially and the intensity of which at the horizontal may exceed the values specified for the semi-cut-off distribution, but should not nevertheless exceed 1 000 cd. Non-cut-off luminaires are permissible only when a certain amount of glare may be accepted and when the luminaires are of large size and of reduced brightness. In certain cases, they have some advantages in increasing the illumination of facades.
7.2.1.4 Inclination
Attention should be given to the inclination of luminaires. An upward inclination which is generally called for reasons of aesthetics should be employed with care. Too great an inclination of the luminaire may modify, particularly in certain directions, the cut off qualities of the luminaires and in certain situations (for example, when there are roads at several levels, bends, roundabouts, etc.) this inclination may lead to unexpected glare.
7.1.2.2 Means of emergency switching shall be provided so as to completely isolate the supply in case of emergency.
7.1.2.3 The enclosure or the distribution board in which the main switch is installed shall be such that the equipment within shall be unaffected by the environmental conditions (see 5.1). A double insulated installation with higher degree of Ingress protection shall be preferred.
7.1.2.4 The main switch on the installation shall be connected to the point of supply by means of an armoured cable or insulated wires and the termination of this cable shall be adequately protected from rainwater.
7.1.2.5 The main requiring handle for operation (generally above 100A) shall be located at a height not exceeding 1.5 m. To remain accessible during emergencies and for ease of operation. The main switch operated by toggle/rocker type action can be located up to 2 m of height. However, no switch should be located below 450 mm from floor/ground level in order to provide operational ease and to avert probable contact with splashing drops water/liquid bouncing repelling from ground / spread on floor for cleaning purpose/spillage.
7.1.2.6 The cable shall be laid either underground or supported in the air. Precautions shall be taken to ensure that this cable when laid underground is done so with the same meticulous care as is, done for a permanent installation. In case the cable passes underneath the passages, it shall be laid in whole or split pipes. When laid over ground, the cables shall either be cleated with saddles of proper size along the walls of a permanent structure if available, or alternatively, it shall be supported on rigid poles. The height of the cable shall not be less than 2 m when run inside the compound and at least 5 m when run along or across road. Crossing of the road shall preferably be avoided. An independent earthing shall be established inside the installation premises. In case overhead wires are used in the installation they should conform to the relevant Indian Standards mentioned in 7.1.1.
7.1.2.7 In selecting the equipment and cables, the ratings hall be decided taking the environmental conditions into account.
7.1.2.8 The supply intake point shall be placed outside the periphery of area which is accessible to the public.
7.1.2.9 In cities, towns, and thickly populated localities, it is advisable to wire up the installation with insulated wires including for main circuits in open compounds or running along or across roads. For main circuits, cables shall be used, preferably laid underground. Alternatively, they shall be cleated along the walls of structures with proper saddles. When laid underground, the cable shall be laid at a depth of 900 mm, covered with sand, bricks and earth for providing mechanical protection.
7.1.2.10 For temporary installations in cities and towns for purposes described under 4.1(b), (c) and (d), bare conductors shall not be used. Only in the case of load for purposes mentioned under 4.1(a) especially outside cities and town bare conductors are permitted.
7.1.2.11 In cities and towns, if the premises where temporary electric supply required is isolated, then:
a) Mixed wiring of insulated and bare conductor — overhead wiring, and
b) Mixed wiring partly underground and partly overhead may be used.
In such an event, the underground part of the installation and the overhead part of the installation shall separately conform to the requirements as mentioned in this Section.
7.1.2.12 TN-S type earthing shall be installed. For a three-phase application, a 5 wire system, where the 5th wire act as protective earth conductor shall be used from the main switch board up to the last electrical apparatus.
7.2 Control of Circuits
7.2.1 Main Circuit
7.2.1.1 A device shall be provided on the incoming cable to each supply unit and each distribution unit for switching and isolating. With this type of arrangement, it shall be possible to switch off the supply at the intake point or at the distribution point.
7.2.1.2 The main switch shall be adequately protected from ingress of water. The incoming and outgoing cable/wires of the main switch shall be firmly supported so that cable and wire ends connected to the main switch shall not be subjected to any mechanical force, transmitted to it from any portion of the cables and wires.
7.2.1.3 The main switch shall be installed on a firm and vertical surface, which can withstand the mechanical vibrations created at the installation site as well as the wind pressure at the location.
7.2.1.4 There shall be adequate ventilation in the room where main switches are installed and there shall be operational space around the switch in accordance with good practice. The switch room shall be accessible at any time of the day or night to authorised persons.
7.2.2 Sub-circuit
7.2.2.1 On large temporary installations like those on construction sites, at exhibitions, circuses, etc, the outgoing end of the main switch shall be connected to bus bar of adequate size and various sub-circuits shall be connected to this bus bar through double or triple pole switches, depending upon whether they are single phase or 3 phase circuits. The switches shall be mounted on a firm support and shall be at a height between 1 m and 2 m from the floor level. The sub circuit switch shall be so spaced that there shall be a minimum clear distance of 60 mm between the switches for ease of operation.
7.2.2.2 The outgoing wires from the sub-circuits witches inside the enclosure shall be cleated firmly on wooden battens or taken through conduits which are fixed by means of saddles to the masonry wall or wooden partition wall. The lead wires connected to the sub circuits switches shall be suitably supported on wall with clips and shall not be left hanging. Spans more than 2 m shall have guide wire support.
7.2.2.3 The distribution boards the sub-circuits shall be at an accessible height but not less than 1 m. The distribution boards shall be fixed on firm supports or on pole firmly planted in the ground.
7.2.2.4 Taped joints shall not be used at heights less than 3 m. The taped joints shall be properly supported and preferably clamped on either side of the joint so that the joint is not subject to a strain. For series lights used for decorative purposes, no taped joint shall be used.
7.2.2.5 A broken bulb of a lamp in a series circuit is a risk and therefore series lamps shall not be strung or hung at heights less than 3 m. A defective series lamp shall not be allowed to remain in its position and shall be immediately removed.
7.2.2.6 Installation at Construction Sites
The entire area where the temporary supply will be used, shall be indicated beforehand and in case the electric supply is required at construction site for pipelines, then a drawing may also be given to the electric supply authority. On this drawing, various points from where different appliances/equipment are intended to be used, may also be indicated. All switches, sockets and fixed appliances shall be protected from rain by enclosing these in cubicles. Sub-circuit distribution board shall be installed, at a place where it is safe from atmospheric conditions. If such a place is not available, the distribution board shall be placed in a cubicle. In a 3-phase circuit, the loads on the 3 phases shall be balanced. At the point of supply, the load on the neutral shall not be more than 20 percent of the computed value of the load in the phases.
7.2.3 Earthing
7.2.3.1 All appliances and equipment on temporary installation shall be connected to TN-S system consisting of 5 wires. The 5th wire shall be used the protective earth conductor. Wherever armoured cables are used, the armouring shall be connected to earthing arrangement of power supply Authority. All exposed and extraneous
conductive parts shall be earthed to the protective earth conductor in such a way that the maximum expected fault voltage is less than 32 volts.
7.2.3.2 For local earthing, the earth electrode shall be buried near the supply intake point. The earth continuity wire shall be bare round conductors/strips and shall be a single core insulated wire and shall be connected to the local earth plate and taken along the cable connecting the supply intake point and the main switch in the installation. The connection from this earth continuity wire shall be taken to various sub distribution boards and terminated on a bus bar. All appliances and equipment connected to sub distribution board shall get their duplicate earth connection from the earth continuity bus bar on the sub distribution board.
Annex A
(Clause 4.1) TYPES OF ROADS
Sl No.
Term
Description of Type of Road
(1)
(2)
(3)
i)
Road
A general term denoting any public way for purposes of vehicular traffic
ii)
Street
A road which has become partly or wholly defined by buildings along one or both frontages
iii)
Motorway
A road reserved for motor traffic, accessible only from interchanges and on which stopping, and parking are prohibited. Roads of this type should have two or several separate and one-way carriageways
iv)
Express road
A road like, but lacking some feature of a motorway, for example: a) not dual carriageway; b) not fully access-controlled; and c) not all intersections grade- separated.
v)
All-purpose road
Road usable by all traffic (including pedestrians and cyclists); Used to distinguish other roads from motorways
vi)
Trunk road/Major road
A main route in the through communication system of a country
vii)
Minor road
A road which has, or to which is assigned, a lesser traffic value than that of a major road
viii)
Ring road
A road round an urban area enabling traffic to avoid the urban center
ix)
Radial road
A road providing direct communication between the center of an urban area and the outer districts
x)
Commercial street
Street with frontages comprising a high proportion of commercial premises (usually unlit at night), and with a high proportion of heavy goods vehicles in the traffic stream
xi)
Shopping street
Street with frontages comprising a high proportion of shops or other premises which may be lit at night and with heavy pedestrian (and possibly pedal cycle) traffic
xii)
Resident street
Street with most frontages comprising private houses
xiii)
Collector road/Distributor road
A link between the radial or ring roads and the local access streets
xiv)
Local street
Street giving direct access to buildings and land with a minimum of through traffic
xv)
Service road
A subsidiary road between principle road and buildings or properties facing thereon or a parallel road to the principal road and giving access to the premises and connected only at selected points with the principle road
xvi)
Footway
That portion of a road reserved exclusively for pedestrians
xvii)
Cycle track
A way, or part of a road, reserved for use only by bicycles
Section 2 Temporary Outdoor Installations
Electrical installations are often required to be designed and erected for use for short periods of time ranging from a few hours to few months and are connected to the supply source in open ground. Such installations are generally unprotected from environmental hazards as compared to installations in buildings.
The major risks in the use of power in such installation arise from short circuit resulting in fire accidents and exposure to live wire resulting in shock. It is, therefore, imperative to lay down the necessary precautions to be observed for such installations from the point of view of safety.
Temporary installations covered in this section are enumerated in 5 and are classified based on the duration of their existence in use. It may be noted that this section basically intends to lay down additional safety measures to be adopted in the design of temporary installations, and the general guidelines for outdoor installations under heavy conditions from the point of view of selection and use of equipment given in Part 5/Sec 3 shall also be referred to.
1 SCOPE
This Section of the Code (Part 5/Sec 2) covers the requirements for outdoor electrical installations of temporary use.
2 REFERENCES
IS No./International Title Publications
3043 : 2018 Code of practice for earthing (second revision)
5613 (Part 1/Sec 1) : Code of practice for design, installation, and maintenance of overhead powerlines: 1985 Part 1 Lines up to and including 11 kV, Section 1 Design (first revision)
5613 (Part 1/Sec 2) : Code of practice for design, installation, and maintenance of overhead power lines: 1985 Part 1 Lines up to and including 11 kV, Section 2 Installation, and maintenance (first revision)
SP 7 : 2016 National Building Code of India
IS/IEC 60309-1 : 2002 Plugs, socket-outlets and couplers for Industrial purposes: Part 1 General requirements (first revision)
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for Industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tube accessories (first revision)
IS/IEC 61439 Low-Voltage Switchgear and Controlgear Assemblies
3 TERMINOLOGY
For the purpose of this Section 2, the following definitions in addition to those given in Part 1/Sec 2 of this Code shall apply.
3.1 Temporary Installations (Outdoor) — An electrical installation open to sky or partially covered, intended to be used for a temporary period not exceeding 6 months.
NOTE — In special cases, the guidelines specified in this Section shall be applicable for longer durations subject to fresh inspection and tests with the prior approval of the supply authority (see also 9.3).
SP 30 : 2023
4 CLASSIFICATION
5.1 Environment
The following environmental factors shall apply to temporary outdoor installations:
Sl No.
Environment
Characteristics
Remarks
(1)
(2)
(3)
(4)
i)
Presence of water
Possibility of splashes from any direction
External lighting fittings, construction site equipment, etc.
ii)
Possibility of jets of water in any direction partial or total covering by water
Temporary installations in parts
iii)
Presence of foreign solid bodies
Presence of small objects
iv)
Presence of dust in significant quantity
v)
Impact
High severity
Construction demolition sites
vi)
Vibrations
Medium severity
Constructions, demolitions sites
vii)
Presence of flora/mould growth
No harmful hazard
viii)
Presence of fauna
Hazard from fauna (insects, birds, small animals)
ix)
Solar radiation
Solar radiation of harmful intensity and/or duration
x)
Seismic effects
—
Depends on the location of the installation
xi)
Lightning
Hazard from exposure of equipment
Generally applicable for installations located outdoors
5.2 Utilization
The following factors of utilization apply:
Sl No.
Utilization
Characteristics
Remarks
(1)
(2)
(3)
(4)
i)
Capability of persons
Uninstructed persons
Majority of occupants say in an exhibition's circus fair
ii)
Instructed persons adequately advised or supervised by skilled persons
Applies to operating staff
iii)
Contact of persons with earth potential
Frequent
Construction sites
iv)
Conditions of evacuation during emergency
Low density occupation easy conditions of evacuation
Small gatherings, such as for marriages and similar functions
v)
High density occupation, difficult conditions of evacuation
Circus, large public gatherings inside an enclosure, etc.
vi)
Nature of processed
Fire risk
Shamianahs, tents
vii)
Construction of structure
Combustible
The nature of construction materials used in temporary installations may be combustible. Such as wooden cloth structures in tents
viii)
Structural design flexible or unstable
Structures which are weak or subject to movement, such as tents, removable partitions etc.
6 GENERAL REQUIREMENTS FOR TEMPORARY OUTDOOR INSTALLATIONS
6.1 Temporary installation shall in general conform to the requirements stipulated in the relevant Section of Part 1 of this Code, in respect wiring of circuits, location and installation of equipment, etc. Additional requirements are given in 7 (see also SP 7).
6.2 If the equipment used in temporary and provisional places of work in the open, such as building sites are similar to those used in surface mining applications, reference shall be made to the guidelines contained in Part 5/Sec 3 of this Code.
4.1 The temporary outdoor electrical installations covered in this Section are those intended for the following purposes:
a) Temporary installations for durations not exceeding 6 months — Outdoor installations open to sky or partially covered, erected in the vicinity of construction sites solely for the purposes of supplying the electrical needs of building construction work such as lighting and power loads.
1 Construction site installations for very long periods of times, where the equipments are quite similar to those in heavy conditions shall conform to the requirements in Part 5/Sec 3 of this Code.
2 Construction site installations are those which include sites where the following are carried out:
a) Construction of new building.
b) Works of repair, alternation, extension, or demolition of existing buildings; and
c) Public engineering works. The construction site installations are also characterised by frequent modifications.
b) Temporary installations for durations not exceeding 45 days — These include large loads such as for exhibitions, fairs, etc.
NOTE — Exhibition or fair site lighting installations of the permanent type shall conform to the requirements specified in Part 5/Section 1 of this Code.
c) Temporary installations for durations not exceeding 7 days — These include installations site of temporary nature intended for a weeklong public function or outdoor lighting installations of buildings and parts in view of festival and other reasons.
d) Temporary installations for durations not exceeding 24 h — These include temporary installations which cater to loads for the purposes of marriages, reception, religious and other public function, etc.
5 GENERAL CHARACTERISTICS OF TEMPORARY INSTALLATIONS
General guidelines on the assessment of characteristics of installations in buildings are given in Part 1/Sec 8 of this Code. For the purposes of installations falling under the scope of this section, the characteristics defined below generally apply.