1.1 This Part of the Code (Part 7) covers recommendations for electrical installations in chemical industries, petroleum refineries and other similar areas where hazards of explosion due to gases and vapours exist, and in which flammable gases and volatile liquids are processed, stored, loaded, unloaded or otherwise handled.
1.2 In addition to the recommendations given in this Part 7, the electrical installations in hazardous areas shall comply, with the requirements for industrial installation in non-hazardous areas laid down in Part 4 of this Code.
1.3 This Part does not apply to installations in hazardous areas having ignitable dusts and fibres. As distinct from the hazardous areas on the surface, environmental conditions in mines demand special consideration. This Part of the Code does not include provisions for installations in underground mines.
1.4 In any plant installation, irrespective of size, there may be numerous sources of ignition apart from those associated with electrical apparatus. Precautions may be necessary to ensure safety but guidance on this aspect is outside the scope of this Part.
NOTE — Some examples of industrial locations which require application of the guidelines in this Part are given in Annex A.