The following publication has also been referred to in the preparation of this Section:
Report on energy conservation in buildings, submitted to Department of Power, Ministry of Energy by Central Building Research Institute, Roorkee.
All standards, whether given herein above or cross-referred to in the main text of this Section, are subject to revision. The parties to agreement based on this Section are encouraged to investigate the possibility of applying the most recent editions of the standards.
1Scope
This Section covers requirements and methods for lighting and ventilation of buildings.
3Orientation of Building
3.1 The chief aim of orientation of buildings is to provide physically and psychologically comfortable living inside the building by creating conditions which suitably and successfully ward off the undesirable effects of severe weather to a considerable extent by judicious use of the recommendations and knowledge of climatic factors.
3.2 Basic Zones
3.2.1 For the purpose of design of buildings, the country may be divided into the major climatic zones as given in Table 2, which also gives the basis of this classification.
Table 2 Classification of Climate (Clause 3.2.1)
Sl Climatic Mean Monthly Mean Monthly No. Zone Maximum Relative Humidity Temperature (°C) Percentage(1) (2) (3) (4)
The climatic classification map of India is shown in Fig. 2.
3.2.2 Each climatic zone does not have same climate for the whole year; it has a particular season for more than six months and may experience other seasons for the remaining period. A climatic zone that does not have any season for more than six months may be called as composite zone.
3.3 Climatic Factors
From the point of view of lighting and ventilation, the following climatic factors influence the optimum orientation of the building:
a) solar radiation and temperature
b) relative humidity, and
c) prevailing winds.
Based upon Survey of India Outline Map printed in 1993.
The territorial waters of India extend into the sea to a distance of twelve nautical miles measured from the appropriate base line.
The boundary of Meghalaya shown on this map is as interpreted from the North-Eastern Areas (Reorganisation) Act, 1971, but has yet to be verified.
Responsibility for correctness of internal details shown on the map rests with the publisher.
The state boundaries between Uttaranchal & Uttar Pradesh, Bihar & Jharkhand and Chhatisgarh & Madhya Pradesh have not been verified by Governments concerned.
FIG. 2 MAP OF INDIA SHOWING CLIMATIC ZONE
3.4 Solar Radiation
3.4.1 The best orientation from solar point of view requires that the building as a whole should receive the maximum solar radiation in winter and the minimum in summer. For practical evaluation, it is necessary to know the duration of sunshine, and hourly solar intensity on the various external surfaces on representative days of the seasons. The total direct plus diffused diurnal solar loads per unit area on vertical surface facing different directions are given in Table 3 for two days in the year, that is, 22 June and 22 December, representative of summer and winter, for latitudes corresponding to some important cities all over India. From Table 3, the total heat intake can be calculated for all possible orientations of the building for these extreme days of summer and winter.
3.4.1.1 Except in cold climatic zone, suitable sunbreakers have to be provided to cut off the incursion of direct sunlight to prevent heat radiation and to avoid glare.
3.5 Relative Humidity and Prevailing Winds
3.5.1 The discomfort due to high relative humidity in air when temperatures are also high can be counteracted, to a great extent, by circulation of air with electric fans or by ventilation. In the past, simultaneously with heavy construction and surrounding VERANDAHS to counter the effect of sun’s radiation, there was also an over emphasis on prevailing winds to minimize the adverse effects of
high humidity with high temperatures. With the introduction of electric fan to effectively circulate air and owing to taking into account the rise in cost of construction of buildings, it would perhaps be better to shift the emphasis on protection from solar radiation where temperatures are very high. When, however, there is less diurnal variation between morning and mean maximum temperatures along with high humidity, as in coastal areas, the emphasis should be on prevailing winds.
3.5.1.1 For the purpose of orientation, it is necessary to study the velocity and direction of the wind at each hour and in each month instead of relying on generalizations of a month or a period or for the year as a whole. This helps to spot the right winds for a particular period of day or night.
3.5.1.2 It is generally found that variation up to 30° with respect to the prevalent wind direction does not materially affect indoor ventilation (average indoor air speed) inside the building.
3.5.2 In hot-dry climate, advantage can be taken of evaporative cooling in summer to cool the air before introducing it into the building. But in warm humid climate, it is desirable either to regulate the rate of air movement with the aid of electric fans or to take advantage of prevailing winds.
3.6 Aspects of Daylighting
Since the clear design sky concept for daylighting takes care of the worst possible situation, orientation is not
Table 3Total Solar Radiation (Direct plus Diffused) Incident on Various Surfaces of Buildings in W/m2/day for Summer and Winter Seasons (Clause 3.4.1)
Orientation
Latitude
(1)
(2)
9°N(3)
13°N(4)
17°N(5)
21°N(6)
25°N(7)
29°N(8)
North
Summer
1 494
1 251
2 102
1 775
2 173
1 927
Winter
873
859
840
825
802
765
North-East
Summer
2 836
2 717
3 144
3 092
3 294
3 189
Winter
1 240
1 158
1 068
1 001
912
835
East
Summer
3 344
3 361
3 475
3 598
3 703
3 794
Winter
2 800
2 673
2 525
2 409
2 211
2 055
South-East
Summer
2 492
2 660
2 393
2 629
2 586
2 735
Winter
3 936
3 980
3 980
3 995
3 892
3 818
South
Summer
1 009
1 185
1 035
1 117
1 112
1 350
Winter
4 674
4 847
4 958
5 059
4 942
4 981
South-West
Summer
2 492
2 660
2 393
2 629
2 586
2 735
Winter
3 936
3 980
3 980
3 995
3 892
3 818
West
Summer
3 341
3 361
3 475
3 598
3 703
3 794
Winter
2 800
2 673
2 525
2 409
3.7 Planting of Trees
Planting of trees in streets and in open spaces should be done carefully to take advantage of both shades and sunshine without handicapping the flow of natural winds. Their advantage in abating glare and in providing cool and/or warm pockets in developed areas should also be taken. Some trees shed leaves in winter while retaining thick foliage in summer. Such trees will be very advantageous, particularly where southern and western exposures are concerned, by allowing maximum sun during winter and effectively blocking it in summer.
3.8 For detailed information regarding orientation of buildings and recommendations for various climatic zones of country, reference may be made to good practice [8-1(1)].
4.2Daylighting
The primary source of lighting for daylighting is the sun. The light received by the earth from the sun consists of two parts, namely, direct solar illuminance and sky illuminance. For the purposes of daylighting design, direct solar illuminance shall not be considered and only sky illuminance shall be taken as contributing to illumination of the building interiors during the day.
4.2.1 The relative amount of sky illuminance depends on the position of the sun defined by its altitude, which in turn, varies with the latitude of the locality, the day of the year and the time of the day, as indicated in Table 5.
4.2.2 The external available horizontal sky illuminance (diffuse illuminance) values which are exceeded for about 90 percent of the daytime working hours may be taken as outdoor design illuminance values for ensuring adequacy of daylighting design. The outdoor design sky illuminance varies for different climatic regions of the country. The recommended design sky illuminance values are 6 800 lux for cold climate, 8 000 lux for composite climate, 9 000 lux for warm humid climate, 9 000 lux for temperate climate and 10 500 for hot-dry climate. For integration with the artificial lighting during daytime working hours an increase of 500 lux in the recommended sky design illuminance for daylighting is suggested.
4.2.3 The daylight factor is dependent on the sky luminance distribution, which varies with atmospheric conditions. A clear design sky with its non-uniform distribution of luminance is adopted for the purposes of design in this section.
Table 5 Solar-Altitudes (to the Nearest Degree) for Indian Latitudes(Clause 4.2.1)
Period of Year
22 June
21 March and 23 September
22 December
Hours of Day (Sun or Solar)
07 00
08 00
09 00
10 00
11 00
12 00
07 00
08 00
09 00
10 00
11 00
12 00
07 00
08 00
09 00
10 00
11 00
12 00
Latitude (1)
17 00(2)
16 00(3)
15 00(4)
14 00(5)
13 00(6)
—(7)
17 00(8)
16 00(9)
15 00(10)
14 00(11)
13 00(12)
—(13)
17 00(14)
16 00(15)
15 00(16)
14 00(17)
13 00(118)
—(19)
10°N
18
31
45
58
70
77
15
30
44
59
72
80
9
23
35
46
53
57
13°N
19
32
46
60
72
80
15
29
44
58
70
77
8
21
33
43
51
54
16°N
20
33
47
61
74
83
14
29
43
56
68
74
7
19
31
41
48
51
19°N
21
34
48
62
75
86
14
28
42
55
66
71
5
18
29
48
45
48
22°N
22
35
49
62
75
89
14
28
41
53
64
68
4
16
27
36
42
45
25°N
23
36
49
63
76
88
13
27
40
52
61
65
3
14
25
34
39
42
28°N
23
36
49
63
76
86
13
26
39
50
59
62
1
13
23
31
37
39
31°N
24
37
50
62
75
82
13
25
37
48
56
56
—
11
21
28
34
36
34°N
25
37
49
62
73
79
12
25
36
46
53
56
—
9
18
26
31
33
4.2.4 Components of Daylight Factor
Daylight factor is the sum of all the daylight reaching on an indoor reference point from the following sources:
a) The direct sky visible from the point,
b) External surfaces reflecting light directly (see Note 1) to the point, and
c) Internal surfaces reflecting and interreflecting light to the point.
NOTES
1 External surface reflection may be computed approximately only for points at the centre of the room, and for detailed analysis procedures are complicated and these may be ignored for actual calculations.
2 Each of the three components, when expressed as a ratio or percent of the simultaneous external illuminance on the horizontal plane, defines respectively the sky component (SC), the external reflected component (ERC) and the internal reflected component (IRC) of the daylight factor.
4.2.4.1 The daylight factors on the horizontal plane only are usually taken, as the working plane in a room is generally horizontal; however, the factors in vertical planes should also be considered when specifying daylighting values for special cases, such as daylighting on class-rooms, blackboards, pictures and paintings hung on walls.
4.2.5 Sky Component (SC)
Sky component for a window of any size is computed by the use of the appropriate table of Annex A.
a) The recommended sky component level should be ensured generally on the working plane at the following positions:
at a distance of 3 m to 3.75 m from the window along the central line perpendicular to the window,
at the centre of the room if more appropriate, and
at fixed locations, such as school desks, black-boards and office tables.
b) The daylight area of the prescribed sky component should not normally be less than half the total area of the room.
4.2.5.1 The values obtainable from the tables are for rectangular, open unglazed windows, with no external obstructions. The values shall be corrected for the presence of window bars, glazing and external obstructions, if any. This assumes the maintenance of a regular cleaning schedule.
4.2.5.2 Corrections for window bars
The corrections for window bars shall be made by multiplying the values read from tables in Annex A
by a factor equal to the ratio of the clear opening to the overall opening.
4.2.5.3 Correction for glazing
Where windows are glazed, the sky components obtained from Annex A shall be reduced by 10 to 20 percent, provided the panes are of clear and clean glass. Where glass is of the frosted (ground) type, the sky components read from Annex A may be reduced by 15 to 30 percent. In case of tinted or reflective glass the reduction is about 50 percent. Higher indicated correction corresponds to larger windows and/or near reference points. In the case of openings and glazings which are not vertical, suitable correction shall be taken into account.
4.2.5.4 Correction for external obstructions
There is no separate correction, except that the values from tables in Annex A shall be read only for the unobstructed portions of the window.
4.2.6 External Reflected Component (ERC)
The value of the sky component corresponding to the portion of the window obstructed by the external obstructions may be found by the use of methods described in Annex B of good practice [8-1(3)].
These values when multiplied by the correction factors, corresponding to the mean elevation of obstruction from the point in question as given in Table 6, can be taken as the external reflected components for that point.
4.2.6.1 For method of calculating ERC, reference may be made to accepted standard (see Examples 10 and 11 given in Annex B of good practice [8-1(3)].
4.2.7 Internal Reflected Component (IRC)
The component of daylight factor contributed by reflection from the inside surfaces varies directly as the window area and inversely as the total area of internal surfaces, and depends on the reflection factor of the floor, wall and roof surfaces inside and of the
ground outside. For rooms white-washed on walls and ceiling and windows of normal sizes, the IRC will have sizeable value even at points far away from the window. External obstructions, when present, will proportionately reduce IRC. Where accurate values of IRC are desired, the same may be done in accordance with the good practice [8-1(3)].
4.2.8 General Principles of Openings to Afford Good Lighting
4.2.8.1 Generally, while taller openings give greater penetrations, broader openings give better distribution of light. It is preferable that some area of the sky at an altitude of 20° to 25° should light up the working plane.
4.2.8.2 Broader openings may also be equally or more efficient, provided their sills are raised by 300 mm to 600 mm above the working plane.
NOTE — It is to be noted that while placing window with a high sill level might help natural lighting, this is likely to reduce ventilation at work levels. While designing the opening for ventilation also, a compromise may be made by providing the sill level about 150 mm below the head level of workers.
4.2.8.3 For a given penetration, a number of small openings properly positioned along the same, adjacent or opposite walls will give better distribution of illumination than a single large opening. The sky component at any point, due to a number of openings may be easily determined from the corresponding sky component contour charts appropriately superposed. The sum of the individual sky component for each opening at the point gives the overall component due to all the openings. The same charts may also facilitate easy drawing of sky component contours due to multiple openings.
4.2.8.4 Unilateral lighting from side openings will, in general, be unsatisfactory if the effective width of the room is more than 2 to 2.5 times the distance from the floor to the top of the opening. In such cases provision of light shelves is always advantageous.
4.2.8.5 Openings on two opposite sides will give greater uniformity of internal daylight illumination, especially when the room is 7 m or more across. They also minimize glare by illuminating the wall surrounding each of the opposing openings. Side openings on one side and clerestory openings on the opposite side may be provided where the situation so requires.
4.2.8.6 Cross-lighting with openings on adjacent walls tends to increase the diffused lighting within a room.
4.2.8.7 Openings in deep reveals tend to minimize glare effects.
4.2.8.8 Openings shall be provided with CHAJJAHS, louvers, baffles or other shading devices to exclude,
as far as possible, direct sunlight entering the room. CHAJJAHS, louvers, etc, reduce the effective height of the opening for which due allowance shall be made. Broad and low openings are, in general, much easier to shade against sunlight entry. Direct sunlight, when it enters, increases the inside illuminance very considerably. Glare will result if it falls on walls at low angles, more so than when it falls on floors, especially when the floors are dark coloured or less reflective.
4.2.9 Availability of Daylight in Multi-storeyed Block
Proper planning and layout of building can add appreciably to daylighting illumination inside. Certain dispositions of building masses offer much less mutual obstruction to daylight than others and have a significant relevance, especially when intensive site planning is undertaken. The relative availability of daylight in multi-storeyed blocks of different relative orientations are given in Table 7.
Table 7Relative Availability of Daylight on the Window Plane at Ground Level in a Four-Storeyed Building Blocks (Clear Design-Sky as Basis, Daylight Availability Taken as Unity on an Unobstructed Façade, Values are for the Centre of the Blocks) (Clause 4.2.9)
Distance of Infinitely Parallel Blocks Parallel Blocks Separation Long Facing Each Facing Gaps Between Parallel Other Between Opposite Blocks Blocks (Length = Blocks (Length = 2 × Height) 2 × Height)(1) (2) (3) (4)
4.2.10 For specified requirements for daylighting of special occupancies and areas, reference may be made to good practice [8-1(4)].
4.3Artificial Lighting
4.3.1 Artificial lighting may have to be provided
a) where the recommended illumination levels have to be obtained by artificial lighting only,
b) to supplement daylighting when the level of illumination falls below the recommended value, and
c) where visual task may demand a higher level of illumination.
4.3.2 Artificial Lighting Design for Interiors
For general lighting purposes, the recommended practice is to design for a level of illumination on the working plane on the basis of the recommended levels for visual tasks given in Table 4 by a method called ‘Lumen method’. In order to make the necessary detailed calculations concerning the type and quantity of lighting equipment necessary, advance information on the surface reflectances of walls, ceilings and floors is required. Similarly, calculations concerning the brightness ratio in the interior call for details of the interior décor and furnishing. Stepwise guidance regarding designing the interior lighting systems for a building using the ‘Lumen method’ is given in 4.3.2.1 to 4.3.2.4.
4.3.2.1 Determination of the illumination level
Recommended value of illumination shall be taken from Table 4, depending upon the type of work to be carried out in the location in question and the visual tasks involved.
4.3.2.2 Selection of the light sources and luminaires
The selection of light sources and luminaires depends on the choice of lighting system, namely, general lighting, directional lighting and localized or local lighting.
4.3.2.3 Determination of the luminous flux
a) The luminous flux (φ) reaching the working plane depends upon the following:
lumen output of the lamps,
type of luminaire,
proportion of the room (room index) (k ),
reflectance of internal surfaces of the room,
depreciation in the lumen output of the lamps after burning their rated life, and
depreciation due to dirt collection on luminaires and room suface.
b) Coefficient of Utilization or Utilization Factor
The compilation of tables for the utilization factor requires a considerable
amount of calculations, especially if these tables have to cover a wide range of lighting practices. For every luminaire, the exact light distribution has to be measured in the laboratory and their efficiencies have to be calculated and measured exactly. These measurements comprise:
i) the luminous flux radiated by the luminaires directly to the measuring surface,
ii) the luminous flux reflected and rereflected by the ceiling and the walls to the measuring surface, and
iii) the inter-reflections between the ceiling and wall which result in the measuring surface receiving additional luminous flux.
All these measurements have to be made for different reflection factors of the ceiling and the walls for all necessary room indices. These tables have also to indicate the maintenance factor to be taken for the luminous flux depreciation throughout the life of an installation due to ageing of the lamp and owing to the deposition of dirt on the lamps and luminaires and room surfaces.
The values of the reflection factor of the ceiling and of the wall are as follows:
White and very light colours 0.7
Light colours 0.5
Middle tints 0.3
Dark colours 0.1
For the walls, taking into account the influence of the windows without curtains, shelves, almirahs and doors with different colours, etc, should be estimated.
c) Calculation for determining the luminous flux
Eav=Aμϕ
or, φ = E a v A µ for new condition
and φ = E a v A µ d for working condition
where
φ = Total luminous flux of the light sources installed in the room inlumens;
E = Average illumination level required on the working plane inlux;
A = Area of the working plane in m2;
= the utilization factor in new conditions; and d = maintenance factor.
In practice, it is easier to calculate straightaway the number of lamps or luminaires from:
Nlamp=μdϕlampE
Nluminaires=μdϕluminairesE
where
ϕlamp=Luminous flux of each lamp in lumens,
ϕluminaires=Luminous flux of each luminaire inlumens,
Nlamp=Total number of lamps, and
N luminaires = Total number of luminaires.
4.3.2.4 Arrangement of the luminaires
This is done to achieve better uniformly distributed illumination. The location of the luminaires has an important effect on the utilization factor.
a) In general, luminaires are spaced " a " metre apart in either direction, while the distance of the end luminaire from the wall is ` / 2 a / ′ metre. The distance ° a ′ is more or less equal to the mounting height ° H m between the luminaire and the working plane. The utilization factor tables are calculated for this arrangement of luminaires.
b) For small rooms where the room index (k ) is less than 1, the distance ° a ′ should always be less than H m since otherwise luminaires cannot be properly located. In most cases of such rooms, four or two luminaires are placed for good general lighting. If, however, in such rooms only one luminaire is installed in the middle, higher utilization factors are obtained, but the uniformity of distribution is poor. For such cases, references should be made to the additional tables for k _ r = 0 . 6 to 1.25 for luminaires located centrally.
4.3.3 Artificial Lighting to Supplement Daylighting
4.3.3.1 The need for general supplementary artificial lighting arises due to diminution of daylighting beyond design hours, that is, for solar altitude below 1 5 ° or when dark cloudy conditions occur.
4.3.3.2 The need may also arise for providing artificial lighting during the day in the innermost parts of the building which cannot be adequately provided with daylighting, or when the outside windows are not of adequate size or when there are unavoidable external obstructions to the incoming daylighting.
4.3.3.3 The need for supplementary lighting during the day arises, particularly when the daylighting on the working plane falls below 100 lux and the surrounding luminance drops below 19 cd/m2.
4.3.3.4 The requirement of supplementary artificial lighting increases with the decrease in daylighting availability. Therefore, conditions near sunset or sunrise or equivalent conditions due to clouds or obstructions, etc, represent the worst conditions when the supplementary lighting is most needed.
4.3.3.5 The requirement of supplementary artificial lighting when daylighting availability becomes poor may be determined from Fig. 3 for an assumed ceiling height of 3.0 m, depending upon floor area, fenestration percentage and room surface reflectance. Cool daylight fluorescent tubes are recommended with semi-direct luminaires. To ensure a good distribution of illumination, the mounting height should be between 1.5 m and 2.0 m above the work plane for a separation of 2.0 m to 3.0 m between the luminaires. Also the number of lamps should preferably be more in the rear half of the room than in the vicinity of windows. The following steps may be followed for using Fig. 3 for determining the number of fluorescent tubes required for supplementary daylighting.
a) Determine fenestration percentage of the floor area, that is,
Floor Area
4.4Energy Conservation in Lighting
4.4.1 A substantial portion of the energy consumed on lighting may be saved by utilization of daylight and rational design of supplementary artificial lights.
FIG. 3 SUPPLEMENTARY ARTIFICIAL LIGHTING FOR 40W FLUORESCENT TUBES
4.4.2 Daytime use of artificial lights may be minimized by proper design of windows for adequate daylight indoors. Daylighting design should be according to 4.2.
4.4.3 Fenestration expressed as percentage of floor area required for satisfactory visual performance of a few tasks for different separation to height (S/H) ratio of external obstructions such as opposite buildings may be obtained from the design nomograph (Fig. 4). The obstructions at a distance of three times their height or more (S/H > 3) from a window façade are not significant and a window facing such an obstruction may be regarded as a case of unobstructed window.
4.4.3.1 The nomograph consists of horizontal lines indicating fenestration percentage of floor area and vertical lines indicating the separation to height ratio of external obstructions such as opposite buildings. Any vertical line for separation to height ratio other than already shown in the nomograph (1.0, 2.0 and 3.0) may be drawn by designer, if required. For cases where there is no obstruction, the ordinate corresponding to the value 3.0 may be used. The value of percentage fenestration and separation to height ratio are marked on left hand ordinate and abscissa respectively. The illumination levels are marked on the right hand ordinate. The values given within brackets are the illumination levels on the work plane at centre and rear of the room. The wattage of fluorescent tubes required per square metre of the floor area for different illumination levels is shown on each curve.
4.4.3.2 Following assumptions have been made in the construction of the nomograph:
a) An average interior finish with ceiling white, walls off white and floor grey has been assumed.
b) Ceiling height of 3 m and room depths up to 10 m and floor area between 30 m2 and 50 m2 have been assumed. For floor area beyond 50 m2 and less than 30 m2, the values of percent fenestration as well as wattage per m2 should be multiplied by a factor of 0.85 and 1.15 respectively.
c) It is assumed that windows are of metallic sashes with louvers of width up to 600 mm or a CHHAJJA (balcony projection) at ceiling level of width up to 2.0 m. For wooden sashes, the window area should be increased by a factor of about 1.1.
d) Luminaires emanating more light in the downward direction than upward direction (such as reflectors with or without diffusing plastics) and mounted at a height of 1.5 m to 2.0 m above the workplane have been considered.
4.4.3.3 Method of use
The following steps shall be followed for the use of nomograph:
a) Step 1 — Decide the desired illumination level depending upon the task illumination requirement in the proposed room and read the value of watts per square metre on the curve corresponding to the required illumination level.
FIG. 4 NOMOGRAPH FOR DAYLIGHTING AND SUPPLEMENTAL LIGHTING DESIGN OF BUILDING
b) Step 2 — Fix the vertical line corresponding to the given separation to height ratio of opposite buildings on the abscissa. From the point of intersection of this vertical line and the above curve move along horizontal, and read the value of fenestration percent on the left hand ordinate.
c) Step 3 — If the floor area is greater than 50 m2 and less than 30 m2, the value of watts per square metre as well as fenestration percent may be easily determined for adequate daylighting and supplemental artificial lighting for design purposes. However, if the fenestration provided is less than the required value, the wattage of supplementary artificial
lights should be increased proportionately to make up for the deficiency of natural illumination.
4.4.4 For good distribution of day light on the working plane in a room, window height, window width and height of sill should be chosen in accordance with the following recommendations:
a) In office buildings windows of height 1.2 m or more in the center of a bay with sill level at 1.0 to 1.2 m above floor and in residential buildings windows of height 1.0 m to 1.1 m with sill height as 0.9 m to 0.7 m above floor are recommended for good distribution of daylight indoors. Window width can
accordingly be adjusted depending upon the required fenestration percentage of the floor area.
b) If the room depth is more than 10 m, windows should be provided on opposite sides for bilateral lighting.
c) It is desirable to have a white finish for ceiling and off white (light colour) to white for walls. There is about 7 percent improvement in lighting levels in changing the finish of walls from moderate to white.
4.4.5 For good distribution and integration of daylight with artificial lights the following guidelines are recommended:
a) Employ cool daylight fluorescent tubes for supplementary artificial lighting.
b) Distribute luminaries with a separation of 2 m to 3 m in each bay of 3 m to 4 m width.
c) Provide more supplementary lights such as twin tube luminaries in work areas where daylight is expected to be poor for example in the rear region of a room having single window and in the central region of a room having windows on opposite walls. In the vicinity of windows only single tube luminaries should be provided.
4.4.6 Artificial Lighting
Energy conservation in lighting is effected by reducing wastage and using energy effective lamps and luminaires without sacrificing lighting quality. Measures to be followed comprise utilization of daylight, energy effective artificial lighting design by providing required illumination where needed, turning off artificial lights when not needed, maintaining lighter finishes of ceiling, walls and furnishings, and implementing periodic schedule for cleaning of luminaires and group replacement of lamps at suitable intervals. Choice of light sources with higher luminous efficacy and luminaires with appropriate light distribution is the most effective means of energy saving in lighting. However, choice of light sources also depends on the other lighting quality parameters like colour rendering index and colour temperature or appearance. For example, high pressure sodium vapour lamps, which have very high luminous efficacy, are not suitable for commercial interiors because of poor colour rendering index and colour appearance, but are highly desirable in heavy industries. Also the choice of light sources depends on the mounting height in the interiors. For example, fluorescent lamps are not preferred for mounting beyond 7 m height, when high pressure gas discharge lamps are preferred because of better optical control due to their compact size.
4.4.6.1 Efficient artificial light sources and luminaires
Luminous efficacy of some of the lamps used in lighting of buildings are given in Table 8 along with average life in burning hours, Colour Rendering Index and Colour Temperature.
Following recommendations may be followed in the choice of light sources for different locations:
a) For supplementary artificial lighting of work area in office building care should be taken to use fluorescent lamps, which match with colour temperature of the daylight.
b) For residential buildings fluorescent lamps and/or CFLs of proper CRI and CCT are recommended to match with the colours and interior design of the room.
c) For commercial interiors, depending on the mounting heights and interior design, fluorescent lamps, CFLs and low wattage metal halilde lamps are recommended. For highlighting the displays in show windows, hotels, etc, low wattage tubular or dichroic reflector type halogen lamps can be used.
d) For industrial lighting, depending on the mounting height and colour consideration fluorescent lamps, high pressure mercury vappour lamps or high pressure sodium vapour lamps are recommended.
4.4.6.2 For the same lumen output, it is possible to save 75 to 80 percent energy if GLS lamps are replaced with CFL and 65 to 70 percent if replaced with fluorescent lamps. Similar energy effective solutions are to be chosen for every application area.
Similarly with white fluorescent tubes recommended for corridors and staircases, the electrical consumption reduces to 1/4.5 of the energy consumption with incandescent lamps.
4.4.7 Cleaning Schedule for Window Panes and Luminaires
Adequate schedule for cleaning of window panes and luminaries will result in significant advantage of enhanced daylight and lumen output from luminaries. This will tend to reduce the duration over which artificial lights will be used and minimize the wastage of energy. Depending upon the location of the building a minimum of three to six months interval for periodic cleaning of luminaries and window panes is recommended for maximum utilization of daylight and artificial lights.
4.4.8 Photocontrols for Artificial Lights
There is a considerable wastage of electrical energy in lighting of buildings due to carelessness in switching
off lights even when sufficient daylight is available indoors. In offices and commercial buildings, occupants may switch on lights in the morning and keep them on throughout the day. When sufficient daylight is available inside, suitable photo controls can be employed to switch off the artificial lights and thus prevent the wastage of energy.
4.4.9 Solar Photovoltaic Systems (SPV)
Solar photovoltaic system enables direct conversion of sunlight into electricity and is viable option for lighting purpose in remote nongrid areas. The common SPV lighting systems are:
a) Solar lantern,
b) Fixed type solar home lighting system, and
c) Street lighting system.
4.4.9.1 SPV lighting system should preferably be provided with CFL for energy efficiency.
4.4.9.2 Invertors used in buildings for supplying electricity during the power cut period should be charged through SPV system.
4.4.9.3 Regular maintenance of SPV system is necessary for its satisfactory functioning.
5Ventilation
5.1 General
Ventilation of buildings is required to supply fresh air for respiration of occupants, to dilute inside air to prevent vitiation by body odours and to remove any products of combustion or other contaminants in air and to provide such thermal environments as will assist in the maintenance of heat balance of the body in order to prevent discomfort and injury to health of the occupants.
4Lighting
4.1 Principles of Lighting
4.1.1 Aims of Good Lighting
Good lighting is necessary for all buildings and has three primary aims. The first aim is to promote work and other activities carried out within the building; the second aim is to promote the safety of the people using the building; and the third aim is to create, in conjunction with the structure and decoration, a pleasing environment conducive to interest of the occupants and a sense of their well-being.
4.1.1.1 Realization of these aims involves:
a) careful planning of the brightness and colour pattern within both the working areas and the surroundings so that attention is drawn naturally to the important areas, detail is seen quickly and accurately and the room is free from any sense of gloom or monotony (see 4.1.3);
b) using directional lighting where appropriate to assist perception of task detail and to give good modeling;
c) controlling direct and reflected glare from light sources to eliminate visual discomfort;
d) in artificial lighting installations, minimizing flicker from certain types of lamps and paying attention to the colour rendering properties of the light;
e) correlating lighting throughout the building to prevent excessive differences between adjacent areas so as to reduce the risk of accidents; and
f) installation of emergency lighting systems, where necessary.
4.1.2 Planning the Brightness Pattern
The brightness pattern seen within an interior may be considered as composed of three main parts — the task itself, immediate background of the task and the general surroundings of walls, ceiling, floor, equipment and furnishings.
4.1.2.1 In occupations where the visual demands are small, the levels of illumination derived from a criterion of visual performance alone may be too low to satisfy the other requirements. For such situations, therefore, illuminance recommendations are based on standards of welfare, safety and amenity judged appropriate to the occupations; they are also sufficient to give these tasks brightness which ensured that the visual performance exceeds the specified minimum. Unless there are special circumstances associated with the occupation, it is recommended that the illuminance of all working areas within a building should generally be 150 lux, even though the visual demands of the occupation might be satisfied by lower values.
5.3Methods of Ventilation
General ventilation involves providing a building with relatively large quantities of outside air in order to improve general environment of the building. This may be achieved in one of the following ways:
a) Natural supply and natural exhaust of air;
b) Natural supply and mechanical exhaust of air;
c) Mechanical supply and natural exhaust of air; and
d) Mechanical supply and mechanical exhaust of air.
5.3.1 Control of Heat
Although it is recognized that general ventilation is one of the most effective methods of improving thermal environmental conditions in factories, in many situations, the application of ventilation should be preceded by and considered along with some of the following other methods of control. This would facilitate better design of buildings for general ventilation, either natural or mechanical or both, and also reduce their cost.
5.3.1.1 Isolation
Sometimes it is possible to locate heat producing equipment, such as furnaces in such a position as would expose only a small number of workers to hot environment. As far as practicable, such sources of heat in factories should be isolated.
In situations where relatively few people are exposed to severe heat stress and their activities are confined to limited areas as in the case of rolling mill operators and crane operators, it may be possible to enclose the work areas and provide spot cooling or supply conditioned air to such enclosures.
5.3.1.2 Insulation
A considerable portion of heat in many factories is due to the solar radiation falling on the roof surfaces, which, in turn, radiate heat inside the building. In such situations, insulations of the roof or providing a false ceiling or double roofing would be very effective in controlling heat. Some reduction can also be achieved by painting the roof in heat reflective shades.
Hot surfaces of equipment, such as pipes, vessels, etc, in the building should also be insulated to reduce their surface temperature.
5.3.1.3 Substitution
Sometimes, it is possible to substitute a hot process by a method that involves application of localized or more efficiently controlled method of heating. Examples include induction hardening instead of conventional heat treatment, cold riveting or spot welding instead of hot riveting, etc.
5.4Natural Ventilation
The rate of ventilation by natural means through windows or other openings depends on:
a) direction and velocity of wind outside and sizes and disposition of openings (wind action), and
b) convection effects arising from temperature of vapour pressure difference (or both) between inside and outside the room and the difference of height between the outlet and inlet openings (stack effect).
5.4.1 Ventilation of Non-industrial Buildings
Ventilation in non-industrial buildings due to stack effect, unless there is a significant internal load, could be neglected, except in cold regions, and wind action may be assumed to be predominant.
5.4.1.1 In hot dry regions, the main problem in summer is to provide protection from sun’s heat so as to keep the indoor temperature lower than those outside under the sun. For this purpose windows and other openings
are generally kept closed during day time and only minimum ventilation is provided for the control of odours or for removal of products of combustion.
5.4.1.2 In warm humid regions, the problem in the design of non-industrial buildings is to provide free passage of air to keep the indoor temperature as near to those outside in the shade as possible, and for this purpose the buildings are oriented to face the direction of prevailing winds and windows and other openings are kept open on both windward and leeward sides.
5.4.1.3 In winter months in cold regions, the windows and other openings are generally kept shut, particularly during night; and ventilation necessary for the control of odours and for the removal of products of combustion can be achieved either by stack action or by some infilteration of outside air due to wind action.
5.4.2 Ventilation of Industrial Buildings
In providing natural ventilation of all industrial buildings having significant internal heat loads due to manufacturing process, proper consideration should be given to the size and distribution of windows and other inlet openings in relation to outlet openings so as to give, with due regard to orientation, prevailing winds, size and configuration of the building and manufacturing processes carried on, maximum possible control of thermal environment.
5.4.2.1 In the case of industrial buildings wider than 30 m, the ventilation through windows may be augmented by roof ventilation.
5.4.3 Design Guidelines for Natural Ventilation
A-1.6.2Example
It is desired to calculate the sky component due to a vertical window ABCDwith width 1.8m and height 1.5 m at a point P on a horizontal plane 3.0 m from the window wall located as shown in Fig. 7. Foot of the perpendicular N is 0.6 m below the sill and 0.9 m to the left of AD.
Consider ABCD extended to NB' CD'
For NB′CD′
l / d = (1.8 + 0.9) / 3 = 0.9
h / d = (1.5 + 0.6) / 3 = 0.7
F₁ = 5.708 percent (from Table 15)
For NA′DD′
l / d = 0.9 / 3 = 0.3
h / d = (1.5 + 0.6) / 3 = 0.7
F₂ = 2.441 percent (from Table 15)
For NB′BA′
l / d = (1.8 + 0.9) / 3 = 0.9
h / d = 0.6 / 3 = 0.2
F₃ = 0.878 percent (from Table 15)
For NA′AA′
l / d = 0.9 / 3 = 0.3
h / d = 0.6 / 3 = 0.2
F₄ = 0.403 percent (from Table 15)
Since A B C D = N B ′ C D ′ - N A ′ D D ′ - N B ′ B A ′ + N A ′ A A ′
43
2Terminology
2.0 For the purpose of this Section, the following definitions shall apply.
2.1 Lighting
2.1.1 Altitude (θ) — The angular distance of any point of celestial sphere, measured from the horizon, on the great circle passing through the body and the zenith (see Fig. 1).
2.1.2 Azimuth (φ) — The angle measured between meridians passing through the north point and the point in question (point C in Fig. 1).
CELESTIAL BODY
FIG. 1 ALTITUDE AND AZIMUTH OF A
5
2.1.3 Brightness Ratio or Contrast — The variations or contrast in brightness of the details of a visual task, such as white print on blackboard.
2.1.4 Candela (cd) — The SI unit of luminous intensity.
Candela = 1 lumen per steradian
2.1.5 Central Field — The area of circle round the point of fixation and its diameter, subtending an angle of about 2 ° at the eye. Objects within this area are most critically seen in both their details and colour.
2.1.6 Clear Design Sky — The distribution of luminance of such a sky is non-uniform; the horizon is brighter than the zenith, and when L z is the brightness at zenith, the brightness at an altitude (θ) in the region away from the sun, is given by the expression:
L
5.6Determining Rate of Ventilation
5.6.1 Natural Ventilation
This is difficult to measure as it varies from time-to-time. The amount of outside air through windows and other openings depends on the direction and velocity of wind outside (wind action) and/or convection effects arising from temperature or vapour pressure differences (or both) between inside and outside of the building (stack effect).
5.6.1.1 Wind action
For determining the rate of ventilation based on wind action the wind may be assumed to come from any direction within 45° of the direction of prevailing wind. Ventilation due to external wind is given by the following formula:
Q = K A V
where
Q = Rate of air flow in m3/h;
K = Coefficient of effectiveness, which may be taken as 0.6 for wind perpendicular to openings and 0.3 for wind at an angle less than 45° 4 5 ° to the openings;
A = Free area of inlet openings in m2; and
V = Wind speed in m/h.
NOTE — For wind data at a place, the local Meteorological Department may be consulted.
5.6.1.2 Stack effect
Ventilation due to convection effects arising from temperature difference between inside and outside is given by:
Q = 7. 0 A √ h (tr - to)
where
Q = Rate of air flow in m ³ / h;
A = Free area of inlet openings in m2;
h = Vertical distance between inlets and outlets in m;
r l t ~ r ~ & = A verage temperature of indoor air at height h i n ° C; and r l t 0 & = Temperature of outdoor air in °C, NOTE — The equation is based on 0.65 effectiveness of openings. This should be reduced to 0.50 if conditions are not favourable. 5.6.1.3 When areas of inlet and outlet openings are unequal, the value of A may be calculated using the equation
\frac {2}{A ^ {2}} = \frac {1}{A _ {\text {inlet}} ^ {2}} + \frac {1}{A _ {\text {outlet}} ^ {2}}
5.7Energy Conservation in Ventilation System
5.7.1 Maximum possible use should be made of wind induced natural ventilation. This may be accomplished by following the design guidelines given in 5.7.1.1.
5.7.1.1 Adequate number of circulating fans should be installed to serve all interior working areas during summer months in the hot dry and warm humid regions to provide necessary air movement at times when ventilation due to wind action alone does not afford sufficient relief.
5.7.1.1.1 The capacity of a ceiling fan to meet the requirement of a room with the longer dimension D metres should be about 55 D m3/min.
5.7.1.1.2 The height of fan blades above the floor should be (3H + W)/4, where H is the height of the room, and W is the height of work plane.
5.7.1.1.3 The minimum distance between fan blades and the ceiling should be about 0.3 metre.
5.7.2 Electronic regulators should be used instead of resistance type regulators for controlling the speed of fans.
5.7.3 When actual ventilated zone does not cover the entire room area, then optimum size of ceiling fan should be chosen based on the actual usable area of room, rather than the total floor area of the room. Thus smaller size of fan can be employed and energy saving could be achieved.
5.7.4 Power consumption by larger fans is obviously higher, but their power consumption per square metre of floor area is less and service value higher. Evidently, improper use of fans irrespective of the rooms dimensions is likely to result in higher power consumption. From the point of view of energy consumption, the number of fans and the optimum sizes for rooms of different dimensions are given in Table 13.
Table 13Optimum Size/Number of Fans for Rooms of Different Sizes (Clause 5.7.4)
Room Widthm(1)
Room Length
4 m(2)
5 m(3)
6 m(4)
7 m(5)
8 m(6)
9 m(7)
10 m(8)
11 m(9)
12 m(10)
14 m(11)
16 m(12)
3
1 200/1
1 400/1
1 500/1
1 050/2
Annex ASKY Component Tables
A-1 Description of Tables
A-1.1 The three sky component tables are as given below:
Table 14 Percentage sky components on the horizontal plane due to a vertical rectangular opening for the clear design sky
Table 15 Percentage sky components on the vertical plane perpendicular to a vertical rectangular opening for the clear design sky
Table 16 Percentage sky components on the vertical plane parallel to a vertical rectangular opening for the clear design sky
A-1.2 All the tables are for an unglazed opening illuminated by the clear design sky.
A-1.3 The values tabulated are the components at a point P distant from the opening on a line perpendicular to the plane of the opening through one of its lower corners,and land h are the width and height respectively of the rectangular opening (see Fig. 6).
A-1.4Sky component for different h/d and l/d values are tabulated, that is, for windows of different size and for different distances of the point P from the window.
A-1.5By suitable combination of the values obtained from the three tables, for a given point for a given window, the sky component in any plane passing through the point may be obtained.
A-1.6 Method of Using the Tables
A-1.6.1 Method of using the Tables to get the sky
component at given point is explained with help of the following example.
2 211
2 055
North-West
Summer
2 836
2 717
3 144
3 092
3 294
3 189
Winter
1 240
1 158
1 068
1 001
912
835
Horizontal
Summer
8 107
8 139
8 379
8 553
8 817
8 863
Winter
6 409
6 040
5 615
5 231
4 748
4 281
a major problem for daylighting in buildings, except that direct sunshine and glare should be avoided. However, due allowance should be given to the mutual shading effects of opposite facades.
4.2.8.9 Light control media, such as translucent glass panes (opal or matt) surfaced by grinding, etching or sandblasting, configurated or corrugated glass, certain types of prismatic glass, tinted glass and glass blasts are often used. They should be provided, either fixed or movable outside or inside, especially in the upper portions of the openings. The lower portions are usually left clear to afford desirable view. The chief purpose of such fixtures is to reflect part of the light on to the roof and thereby increase the diffuse lighting within, light up the farther areas in the room and thereby produce a more uniform illumination throughout. They will also prevent the opening causing serious glare discomfort to the occupants but will provide some glare when illuminated by direct sunlight.
av
A
av
A
Window Area
×
100
b) In Fig. 3, refer to the curve corresponding to the percent fenestration determined above and the set of reflectances of ceiling, walls and floor actually provided.
c) For the referred curve of Fig. 3 read, along the ordinate, the number of 40 W fluorescent tubes required, corresponding to the given floor area on the abscissa.
4.3.4 For detailed information on the design aspects and principles of artificial lighting, reference may be made to good practice [8-1(2)].
4.3.5 For specific requirements for lighting of special occupancies and areas, reference may be made to good practice [8-1(5)].
4.3.6 Electrical installation aspect for artificial lighting shall be in accordance with Part 8 ‘Building Services, Section 2 Electrical and Allied Installations’.
4.4.6.3 Efficient luminaire also plays an important role for energy conservation in lighting. The choice of a luminaire should be such that it is efficient not only initially but also throughout its life. Following luminaries are recommended for different locations:
a) For offices semi-direct type of luminaries are recommended so that both the work plane illumination and surround luminance can be effectively enhanced.
b) For corridors and staircases direct type of luminaries with wide spread of light distributions are recommended.
c) In residential buildings, bare fluorescent tubes are recommended. Wherever the incandescent lamps are employed, they should be provided
Table 8 Luminous Efficacy, Life, CRI and CCT of Light Sources(Clause 4.4.6.1)
Sl No.
Light Source
Efficacy lm/W
Average Life h
CRI
CCT K
(1)
(2)
(3)
(4)
(5)
(6)
i)
Incandescent lamps GLS 25 W-1 000 W
8-18
1 000
100
2 800
ii)
Tungsten halogen incandescent lamps Mains-voltage types: 60 W-2 000 W
10% higher than comparable GLS lamp
2 000
100
2 800-3 200
Low-voltage types with reflector have lower wattages
iii)
Fluorescent lamps (FTL)
a) Standard lamps 38 mm (T12)
20 W-65 W
26 mm (T 8)
18 W-58 W
Cool daylight
61
5 000
72
6 500
Warm white
67
5 000
57
3 500
b) Tri-Phosper lamps 38 mm (T12)
20 W-65 W
88-104
12 000-18 000
85-95
2 700-6 500
26 mm (T 8)
18 W-58 W
iv)
Compact Fluorescent Lamps (CFL) 5 W-25 W
40-80
8 000
Similar to FTL
v)
High pressure mercury vapour lamps 80 W-400 W
36-60
5 000
45
4 000
vi)
Blended — Light lamps MLL 100 W-500 W
11-26
5 000
61
3 600
vii)
High Pressure Sodium Vapour Lamps 50 W-1 000 W
69-130
10 000-15 000
23
2 000
viii)
Metal halide lamps 35 W-2 000 W
69-83
10 000
68-92
3 000-5 600
NOTES
1 The table includes lamps and wattages currently in use in buildings in India.
2 Luminous efficacy varies with the wattage of the lamp.
3 Average life values are from available Indian Standards. Where Indian Standard is not available, values given are only indicative.
4 CRI and CCT values are only indicative.
5 For exact values, it is advisable to contact manufacturers.
with white enamelled conical reflectors at an inclination of about 45° from vertical.
4.1.2.2 Where work takes place over the whole utilizable area of room, the illumination over that area should be reasonably uniform and it is recommended that the uniformity ratio (minimum illuminance divided by average illuminance levels) should be not less than 0.7 for the working area.
4.1.2.3 When the task brightness appropriate to an occupation has been determined, the brightness of the other parts of the room should be planned to give a proper emphasis to visual comfort and interest.
A general guide for the brightness relationship within the normal field of vision should be as follows:
a) For high task brightness Maximum (above 100 cd/m2)
Between the visual task 3 to 1 and the adjacent areas like table tops
Between the visual task 10 to 1 and the remote areas of the room
b) For low and medium task brightness (below 100 cd/m2): The task should be brighter than both the background and the surroundings; the lower the task brightness, the less critical is the relationship.
4.1.3 Recommended Values of Illuminance
Table 4 gives recommended values of illuminance commensurate with the general standards of lighting
described in this section and related to many occupations and buildings; These are valid under most of the conditions whether the illumination is by daylighting, artificial lighting or a combination of the two. The great variety of visual tasks makes it impossible to list them all and those given should be regarded as representing types of task.
4.1.3.1 The different locations and tasks are grouped within the following four sections:
a) Industrial buildings and process;
b) Offices, schools and public buildings;
c) Surgeries and hospitals; and
d) Hotels, restaurants, shops and homes.
4.1.3.2 The illumination levels recommended in Table 4 are those to be maintained at all time on the task. As circumstances may be significantly different for different interiors used for the same application or for different conditions for the same kind of activity, a range of illuminances is recommended for each type of interior or activity instead of a single value of illuminance. Each range consists of three sucessive steps of the recommended scale of illuminances. For working interiors the middle value of each range represents the recommended service illuminance that would be used unless one or more of the factors mentioned below apply.
4.1.3.2.1 The higher value of the range should be used when:
a) unusually low reflectances or contrasts are present in the task;
b) errors are costly to rectify;
c) visual work is critical;
d) accuracy or higher productivity is of great importance; and
e) the visual capacity of the worker makes it ncessary.
4.1.3.2.2 The lower value of the range may be used when:
a) reflectances or contrast are unusually high;
b) speed and accuracy is not important; and
c) the task is executed only occasionally.
4.1.3.3 Where a visual task is required to be carried out throughout an interior, general illumination level to the recommended value on the working plane is necessary; where the precise height and location of the task are not known or cannot be easily specified, the recommended value is that on horizontal plane 850 mm above floor level.
NOTE — For an industrial task, working plane for the purpose of general illumination levels is that on a work place which is
generally 750 mm above the floor level. For certain purposes, such as viewing the objects of arts, the illumination levels recommended are for the vertical plane at which the art pieces are placed.
4.1.3.4 Where the task is localized, the recommended value is that for the task only; it need not, and sometimes should not, be the general level of illumination used throughout the interior. Some processes, such as industrial inspection process, call for lighting of specialized design, in which case the level of illumination is only one of the several factors to be taken into account.
4.1.4 Glare
Excessive contrast or abrupt and large changes in brightness produce the effect of glare. When glare is present, the efficiency of vision is reduced and small details or subtle changes in scene cannot be perceived. It may be
a) direct glare due to light sources within the field of vision,
b) reflected glare due to reflections from light sources or surfaces of excessive brightness, and
c) veiling glare where the peripheral field is comparatively very bright.
4.1.4.1 An example of glare sources in daylighting is the view of the bright sky through a window or skylight, especially when the surrounding wall or ceiling is comparatively dark or weakly illuminated. Glare can be minimized in this case either by shielding the open sky from direct sight by louvers, external hoods or deep reveals, curtains or other shading devices or by cross lighting the surroundings to a comparable level. A gradual transition of brightness from one portion to the other within the field of vision always avoids or minimizes the glare discomfort.
4.1.5 Lighting for Movement about a Building
Most buildings are complexes of working areas and other areas, such as passages, corridors, stairways, lobbies and entrances. The lighting of all these areas should be properly correlated to give safe movement within the building at all times.
4.1.5.1 Corridors, passages and stairways
Accidents may result if people leave a well-lighted working area and pass immediately into corridors or on to stairways where the lighting is inadequate, as the time needed for adaptation to the lower level may be too long to permit obstacles or the treads of stairs to be seen sufficiently quickly. For the same reason, it is desirable that the illumination level of rooms which open off a working area should be fairly high even though the rooms may be used only occasionally.
Table 4Recommended Values of Illuminance (Clauses 4.1.3, 4.1.3.2, 4.3.2 and 4.3.2.1)
Sl No.
Type of Interior or Activity
Range of Service Illuminance in Lux
Quality Class of Direct Glare Limitation
Remarks
(1)
(2)
(3)
(4)
(5)
1
AGRICULTURE AND HORTICULTURE
1.1
Inspection of Farm Produce where Colour is Important
300-500-750
1
Local lighting may be appropriate
Other Important Tasks
200-300-500
2
Local lighting may be appropriate
1.2
Farm Workshops
1.2.1
General
50-100-150
3
1.2.2
Workbench or machine
200-300-500
2
Local or portable lighting may be appropriate
1.3
Milk Premises
50-100-150
3
1.4
Sick Animal Pets, Calf Nurseries
30-50-100
3
1.5
Other Firm and Horticultural Buildings
20-30-50
3
2
COAL MINING (SURFACE BUILDINGS)
2.1
Coal Preparation Plant
2.1.1
Walkways, floors under conveyors
30-50-100
3
2.1.2
Wagon loading, bunkers
30-50-100
3
2.1.3
Elevators, chute transfer pits, washbox area
50-100-150
3
2.1.4
Drum filters, screen, rotating shafts
100-150-200
3
2.1.5
Picking belts
150-200-300
3
Directional and colour properties of lighting may be important for easy recognition of coal and rock
2.2
Lamp Rooms
2.2.1
Repair section
200-300-500
2
2.2.2
Other areas
100-150-200
3
2.3
Weight Cabins, Fan Houses
100-150-200
3
2.4
Winding Houses
100-150-200
3
3
ELECTRICITY GENERATION, TRANSMISSION AND DISTRIBUTION
3.1
General Plant
3.1.1
Turbine houses (operating floor)
150-200-300
2
3.1.2
Boiler and turbine house basements
50-100-150
3
3.1.3
Boiler houses, platforms, areas around burners
50-100-150
3
3.1.4
Switch rooms, meter rooms, oil plant rooms, HV substations (indoor)
100-150-200
2
3.1.5
Control rooms
200-300-500
1
Localized lighting of control display and the control desks may be appropriate
3.1.6
Relay and telecommunication rooms
200-300-500
2
3.1.7
Diesel generator rooms, compressor rooms
100-150-200
3
3.1.8
Pump houses, water treatment plant houses
100-150-200
3
3.1.9
Battery rooms, chargers, rectifiers
50-100-150
3
3.1.10
Precipitator chambers, platforms, etc
50-100-150
3
3.1.11
Cable tunnels and basements, circulating water culverts and screen chambers, storage tanks (indoor), operating areas and filling points at outdoor tanks
Coarse work, for example, using go/no-go gauges, inspection of large sub-assemblies
300-500-750
2
Local or localized lighting may be appropriate
7.7.2
Medium work, for example, inspection of painted surfaces
500-750-1000
1
Local or localized lighting may be appropriate
7.7.3
Fine work, for example, using calibrated scales, inspection of precision mechanisms
750-1000-1500
1
Local or localized lighting may be appropriate
7.7.4
Very fine work, for example, inspection of small intricate parts
1000-1500-2000
1
Local lighting and optical aids are desirable
7.7.5
Minute work, for example, inspection of very small instruments
2000
1
Local lighting and optical aids are desirable
7.8
Points Shops and Spray Booths
7.8.1
Dipping, rough spraying
200-300-500
3
7.8.2
Preparation, ordinary painting, spraying and finishing
200-500-750
2
7.8.3
Fine painting, spraying and finishing
500-750-1000
2
7.8.4
Inspection, re-touching and matching
750-1000-1500
2
7.9
Plating Shops
7.9.1
Vats and baths
200-300-500
3
7.9.2
Buffing, polishing burnishing
300-500-750
2
7.9.3
Final buffing and polishing
500-750-1000
2
7.9.4
Inspection
—
—
Special light to reveal fault in the surface of the material will be required
Table 4Continued
(1)
(2)
(3)
(4)
(5)
9.2.2
Preparation
300-500-750
3
9.2.3
Canned and bottled goods
9.2.3.1
Retorts
200-300-500
3
9.2.3.2
Automatic processes
150-200-300
3
9.2.3.3
Labelling and packaging
200-300-500
3
9.2.4
Frozen foods
9.2.4.1
Process area
200-300-500
3
9.2.4.2
Packaging and storage
200-300-500
3
9.3
Bottling, Brewing and Distilling
9.3.1
Keg washing and handling, bottle washing
150-200-300
3
9.3.2
Keg inspection
200-300-500
3
9.3.3
Bottle inspection
—
—
Special lighting will be required
9.3.4
Process areas
200-300-500
3
9.3.5
Bottle filling
500-750-1000
3
9.4
Edible Oils and Fats Processing
9.4.1
Refining and blending
200-300-500
3
9.4.2
Production
300-500-750
2
9.5
Mills-Milling, Filtering and Packing
200-300-500
3
9.6
Bakeries
9.6.1
General
200-300-500
2
9.6.2
Hand decorating, icing
300-500-750
2
9.7
Chocolate and Confectionery Manufacture
9.7.1
General
200-300-500
3
9.7.2
Automatic processes
150-200-300
3
9.7.3
Hand decoration, inspection, wrapping and packing
300-500-750
Table 4Continued
(1)
(2)
(3)
(4)
(5)
11
LEATHER INDUSTRY
11.1
Leather Manufacture
11.1.1
Cleaning, tanning and stretching, vats, cutting, fleshing, stuffing
200-300-500
3
11.1.2
Finishing, scarfing
300-500-750
2
11.2
Leather Working
11.2.1
General
200-300-500
3
11.2.2
Pressing, glazing
300-500-750
2
11.2.3
Cutting, splitting, scarfing, sewing
500-750-1000
2
Directional lighting may be useful.
11.2.4
Grading, matching
2
Local lighting may be appropriate
12
CLOTHING AND FOOTWEAR
12.1
Clothing Manufacture
12.1.1
Preparation of cloth
200-300-500
2
12.1.2
Cutting
500-750-1000
1
12.1.3
Matching
500-750-1000
1
12.1.4
Sewing
750-1000-1500
1
12.1.5
Pressing
300-500-750
2
12.1.6
Inspection
1000-1500-2000
1
Local lighting may be appropriate
12.1.7
Hand tailoring
1000-1500-2000
1
Local lighting may be appropriate
12.2
Hosiery and Knitwear Manufacture
12.2.1
Flat bed knitting machines
300-500-750
2
12.2.2
Circular knitting machines
500-750-1000
2
12.2.3
Lockstitch and overlocking machine
750-1000-1500
1
12.2.4
Linking or running on
750-1000-1500
1
12.2.5
Mending, hand finishing
Table 4Continued
(1)
(2)
(3)
(4)
(5)
13.2.2
Sizing, planning, sanding, medium machining and bench work
300-500-750
2
13.2.3
Fine bench and machine work, fine sanding, finishing
500-750-1000
2
Localized lighting may be appropriate
13.3
Furniture Manufacture
13.3.1
Raw material stores
50-100-150
3
13.3.2
Finished goods stores
100-150-200
3
13.3.3
Wood matching and assembly, rough sawing, cutting
200-300-500
2
13.3.4
Machining, sanding and assembly, polishing
300-500-750
2
Localized lighting may be appropriate
13.3.5
Tool room
300-500-750
2
13.3.6
Spray booths
13.3.6.1
Colour finishing
300-500-750
2
13.3.6.2
Clear finishing
200-300-500
2
13.3.7
Cabinet making
13.3.7.1
Vaneer sorting and grading
750-1000-1500
1
13.3.7.2
Marquetry, pressing, patching and fitting
300-500-750
1
13.3.7.3
Final inspection
500-750-1000
1
Special lighting will be required
13.4
Upholstery Manufacture
13.4.1
Cloth inspection
1000-1500-2000
1
Special lighting will be required
13.4.2
Filling, covering
300-500-750
2
13.4.3
Slipping, cutting, sewing
500-750-1000
2
13.4.4
Mattress making
13.4.5
Assembly
300-500-750
2
13.4.6
Tape edging
750-1000-1500
2
Local lighting may be appropriate
Table 4Continued
(1)
(2)
(3)
(4)
(5)
15.1.1.1
Without manual control
30-50-100
3
15.1.1.2
With occasional manual control
50-100-150
3
15.1.1.3
With continuous manual control
200-300-500
3
15.1.1.4
Control rooms
200-300-500
1
15.1.1.5
Control platforms
200-300-500
2
Local lighting may be appropriate
15.1.2
Non-automatic plant
15.1.2.1
Mixing, calendaring, extrusion, injection, compression and blow moulding, sheet fabrication
200-300-500
3
15.1.2.2
Trimming, cutting, polishing, cementing
300-500-750
2
15.1.2.3
Printing, inspection
750-1000-1500
1
15.2
Rubber Products
15.2.1
Stock preparation — plasticizing, milling
150-200-300
3
15.2.2
Calendaring, fabric preparation, stock-cutting
300-500-750
3
15.2.3
Extruding, moulding
300-500-750
2
15.2.4
Inspection
750-1000-1500
—
16
DISTRIBUTION AND STORAGE
16.1
Work Stores
100-150-200
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.1
Unpacking, sorting
150-200-300
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.2
Large item storage
50-100-150
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.3
Small item rack storage
200-300-500
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.4
Issue counter, records, storeman's desk
300-500-750
2
Local or localized lighting may be appropriate
Table 4Continued
(1)
(2)
(3)
(4)
(5)
18.1.2
General repairs, servicing, washing, polishing
200-300-500
2
18.1.3
Workbench
300-500-750
1
Local or localized lighting may be appropriate
18.1.4
Spray booths
300-500-750
1
18.1.5
External apron
18.1.5.1
General
30-50-100
—
Care should be taken to avoid glare to drivers and neighbouring residents
18.1.5.2
Pump area (retail sales)
200-300-500
—
See ‘Retailing’
18.2
Appliance servicing
18.2.1
Workshop
18.2.1.1
General
200-300-500
2
18.2.1.2
Workbench
300-500-750
2
Localized lighting may be appropriate
18.2.1.3
Counter
200-300-500
2
Localized lighting may be appropriate
18.2.1.4
Stores
200-300-500
3
18.3
Laundries
18.3.1
Commercial laundries
18.3.2
Receiving, sorting, washing, drying, ironing, despatch, dry-cleaning, bulk machine work
200-300-500
3
18.3.3
Head ironing, pressing, mending, spotting, inspection
300-500-750
3
18.3.4
Launderettes
200-300-500
3
18.4
Sewage Treatment Works
18.4.1
Walkways
30-50-100
3
18.4.2
Process areas
50-100-150
3
19
RETAILING
19.1
Small Shops with Counters
300-500-750
1
The service illuminance should be provided on the horizontal plane of the counter. Where wall displays are used, a similar illuminance on the walls is desirable
The lighting should be designed to create an appropriate atmosphere
20.5.4
Cloak rooms, baggage rooms
50-100-150
3
20.5.5
Bed rooms
30-50-100
—
Supplementary local lighting at the bed head, writing table should be provided
20.5.6
Bathroom
50-100-150
Supplementary local lighting near the mirror is desirable
20.5.7
Food preparation and stores, cellars, lifts and corridors
—
—
See 'General Building Areas'
20.6
Libraries
20.6.1
Lending library
20.6.1.1
General
200-300-500
1
20.6.1.2
Counters
300-500-750
1
Localized lighting may be appropriate
20.6.1.3
Bookshelves
100-150-200
2
The service illuminance should be provided on the vertical face at the bottom of the bookstack
20.6.1.4
Reading rooms
200-300-500
1
20.6.1.5
Reading tables
200-300-500
1
Localized lighting may be appropriate
Table 4Continued
(1)
(2)
(3)
(4)
(5)
Multi-purpose sports halls
300-750
—
This lighting system should be sufficiently flexible to provide lighting suitable for the variety of sports and activities that take place in sports halls. Higher illuminance of 1000-2000 lux would be required for television coverage
21
EDUCATION
21.1
Assembly Halls
21.1.1
General
200-300-500
3
21.1.2
Platform and stage
—
—
Special lighting to provide emphasis and to facilitate the use of the platform/ stage is desirable
21.2
Teaching Spaces
General
200-300-500
1
21.3
Lecture Theatres
21.3.1
General
200-300-500
1
21.3.2
Demonstration benches
300-500-750
1
Localized lighting may be appropriate
21.4
Seminar Rooms
300-500-750
1
21.5
Art Rooms
300-500-750
1
21.6
Needlework Rooms
300-500-750
1
21.7
Laboratories
300-500-750
1
21.8
Libraries
200-300-500
1
21.9
Music Rooms
200-300-500
1
21.10
Sports Halls
200-300-500
1
21.11
Workshops
200-300-500
1
22
TRANSPORT
22.1
Airports
22.1.1
Ticket counters, checking desks, and information desks
300-500-750
2
Localized lighting may be appropriate
22.1.2
Departure lounges, other waiting areas
150-200-300
2
22.1.3
Baggage reclaim
150-200-300
Table 4Concluded
(1)
(2)
(3)
(4)
(5)
22.3.1
Ticket offices
300-500-750
2
Localized lighting over the counter may be appropriate
22.3.2
Information offices
300-500-750
2
Localized lighting over the counter may be appropriate
22.3.3
Left luggage office
22.3.3.1
General
50-100-150
3
22.3.3.2
Counter
150-200-300
3
Localized lighting is appropriate
22.3.4
Waiting rooms
150-200-300
2
22.3.5
Concourse
150-200-300
2
22.3.6
Time tables
150-200-300
2
Local lighting is appropriate
22.3.7
Loading areas
100-150-200
3
23
GENERAL BUILDING AREAS
23.1
Entrance
23.1.1
Entrance halls, lobbies, waiting rooms
150-200-300
2
23.1.2
Enquiry desks
300-500-750
2
Localized lighting may be appropriate
23.1.3
Gatehouses
150-200-300
2
23.2
Circulation Areas
23.2.1
Lifts
50-100-150
—
23.2.2
Corridors, passageways, stairs
50-100-150
2
23.2.3
Escalators, travellers
100-150-200
—
23.3
Medical and First Aid Centres
23.3.1
Consulting rooms, treatment rooms
300-500-750
1
23.3.2
Rest rooms
100-150-200
1
23.3.3
Medical stores
100-150-200
2
23.4
Staff Rooms
23.4.1
Changing, locker and cleaners rooms, cloakrooms, lavatories
It is important, when lighting stairways, to prevent disability from glare caused by direct sight of bright sources to emphasize the edges of the treads and to avoid confusing shadows. The same precautions should be taken in the lighting of cat-walks and stairways on outdoor industrial plants.
4.1.5.2 Entrances
The problems of correctly grading the lighting within a building to allow adequate time for adaptation when passing from one area to another area are particularly acute at building entrances. These are given below:
a) By day, people entering a building will be adapted to the very high levels of brightness usually present outdoors and there is risk of accident if entrance areas, particularly any steps, are poorly lighted. This problem may often be overcome by arranging windows to give adequate natural lighting at the immediate entrance, grading to lower levels further inside the entrance area. Where this cannot be done, supplementary artificial lighting should be installed to raise the level of illumination to an appropriate value.
b) At night it is desirable to light entrance halls and lobbies so that the illumination level reduces towards the exit and so that no bright fittings are in the line of sight of people leaving the building. Any entrance steps to the building should be well-lighted by correctly screened fittings.
4.1.6 For detailed information regarding principles of good lighting, reference may be made to good practice [8-1(2)].
5.3.1.4 Radiant shielding
Hot surfaces, such as layers of molten metal emanate radiant heat, which can best be controlled by placing a shield having a highly reflecting surface between the source of heat and the worker, so that a major portion of the heat falling on the shield is reflected back to the
source. Surfaces such as of tin and aluminium have been used as materials for shields. The efficiency of the shield does not depend on its thickness, but on the reflectivity and emissivity of its surface. Care should be taken to see that the shield is not heated up by conduction and for this purpose adequate provision should be made for the free flow upwards of the heated air between the hot surface and the shield by leaving the necessary air space and providing opening at the top and the bottom of the sides.
5.3.2 Volume of Air Required
The volume of air required shall be calculated by using both the sensible heat or latent heat gain as the basis. The larger of the two figures obtained should be used in actual practice.
5.3.2.1 Volume of air required for removing sensible heat
When the amount of sensible heat given off by different sources, namely, the sun, the manufacturing processes, machinery, occupants and other sources, is known and a suitable value for the allowable temperature rise is assumed, the volume of outside air to be provided for removing the sensible heat may be calculated from:
Q1=t2.9768Ks
where
Q ₁ = Quantity of air in m ³ / h,
K s = Sensible heat gained in W, and
t= Allowable temperature rise in ∘C.
5.3.2.2 Temperature rise refers mainly to the difference between the air temperatures at the outlet (roof exit) and at the inlet openings for outside air. As very little data exist on allowable temperature rise values for supply of outside air in summer months, the values given in Table 12 related to industrial buildings may be used for general guidance.
Table 12Allowable Temperature Rise Values (Clause 5.3.2.2)
Height of Outlet Opening Temperature Rise(1) (2)
6 3 to 4.5 9 4.5 to 6.5 12 6.5 to 11 NOTES 1 The conditions are limited to light or medium heavy manufacturing processes, freedom from radiant heat and inlet openings not more than 3 to 4.5 m above floor level. 2 At the working zone between floor level and 1.5 m above floor level, the recommended maximum allowable temperature rise for air is 2°C to 3°C above the air temperature at the inlet openings.
5.3.2.3 Volume of air required for removing latent heat
If the latent heat gained from the manufacturing processes and occupants is also known and a suitable value for the allowable rise in the vapour pressure is assumed:
Q2=h4127.26×K1
5.4.3.1 By wind action
i) A building need not necessarily be oriented perpendicular to the prevailing outdoor wind; it may be oriented at any convenient angle between 0° and 30° without loosing any beneficial aspect of the breeze. If the prevailing wind is from East or West, building may be oriented at 45° to the incident wind so as to diminish the solar heat without much reduction in air motion indoors.
ii) Inlet openings in the buildings should be well distributed and should be located on the windward side at a low level, and outlet openings should be located on the leeward side. Inlet and outlet openings at high levels may only clear the top air at that level without producing air movement at the level of occupancy.
iii) Maximum air movement at a particular plane is achieved by keeping the sill height of the opening at 85 percent of the critical height (such as head level) for the following
iv)
v)
vi)
vii)
recommended levels of occupancy:
For sitting on chair 0.75 m,
For sitting on bed 0.60 m, and
For sitting on floor 0.40 m.
Inlet openings should not as far as possible be obstructed by adjoining buildings, trees, sign boards or other obstructions or by partitions inside in the path of air flow.
In rooms of normal size having identical windows on opposite walls the average indoor air speed increases rapidly by increasing the width of window up to two-third of the wall width; beyond that the increase is in much smaller proportion than the increase of the window width. The air motion in the working zone is maximum when window height is 1.1 m. Further increase in window height promotes air motion at higher level of window, but does not contribute additional benefits as regards air motion in the occupancy zones in buildings.
Greatest flow per unit area of openings is obtained by using inlet and outlet openings of nearby equal areas at the same level.
For a total area of openings (inlet and outlet) of 20 percent to 30 percent of floor area, the average indoor wind velocity is around 30 percent of outdoor velocity. Further increase in window size increases the available velocity but not in the same proportion. In fact, even under most favourable conditions the maximum average indoor wind speed does not exceed 40 percent of outdoor velocity.
viii) Where the direction of wind is quite constant and dependable, the size of the inlet should be kept within 30 to 50 percent of the total area of openings and the building should be oriented perpendicular to the incident wind. Where direction of the wind is quite variable the openings may be arranged so that as far as possible there is approximately equal area on all sides. Thus no matter what the wind direction be, there would be some openings directly exposed to wind pressure and others to air suction and effective air movement through the building would be assured.
ix) Windows of living rooms should open directly to an open space. In places where building sites are restricted, open space may have to be created in the buildings by providing adequate courtyards.
x) In the case of rooms with only one wall exposed to outside, provision of two windows
on that wall is preferred to that of a single window.
xi) Windows located diagonally opposite to each other with the windward window near the upstream corner give better performance than other window arrangements for most of the building orientations.
xii) Horizontal louvers, that is a sunshade, atop a window deflects the incident wind upward and reduces air motion in the zone of occupancy. A horizontal slot between the wall and horizontal louver prevents upward deflection of air in the interior of rooms. Provision of inverted L type ( Γ) louver increases the room air motion provided that the vertical projection does not obstruct the incident wind.
xiii) Provision of horizontal sashes inclined at an angle of 45° in appropriate direction helps to promote the indoor air motion. Sashes projecting outward are more effective than projecting inward.
xiv) Air motion at working plane 0.4 m above the floor can be enhanced by 30 percent using a pelmet type wind deflector.
xv) Roof overhangs help promoting air motion in the working zone inside buildings.
xvi) VERANDAH open on three sides is to be preferred since it causes an increase in the room air motion for most of the orientations of the building with respect to the outdoor wind.
xvii) A partition placed parallel to the incident wind has little influence on the pattern of the air flow, but when located perpendicular to the main flow, the same partition creates a wind shadow. Provision of a partition with spacing of 0.3 m underneath, helps augmenting air motion near floor level in the leeward compartment of wide span buildings.
xviii) Air motion in a building unit having windows tangential to the incident wind is accelerated when another unit is located at end-on position on down stream side.
xix) Air motion in two wings oriented parallel to the prevailing breeze is promoted by connecting them with a block on downstream side.
xx) Air motion in a building is not affected by constructing another building of equal or smaller height on the leeward side; but it is slightly reduced if the leeward building is taller than the windward block.
xxi) Air motion in a shielded building is less than
xxii)
that in an unobstructed building. To minimize shielding effect, the distances between two rows should be 8 H for semi-detached houses and 10 H for long rows houses. However, for smaller spacing the shielding effect is also diminished by raising the height of the shielded building.
Hedges and shrubs defect the air away from the inlet openings and cause a reduction in indoor air motion. These elements should not be planted at a distance of about 8 m from the building because the induced air motion is reduced to minimum in that case. However, air motion in the leeward part of the building can be enhanced by planting a low hedge at a distance of 2 m from the building.
xxiii) Trees with large foliage mass having trunk bare of branches up to the top level of window, deflect the outdoor wind downwards and promotes air motion in the leeward portion of buildings.
xxiv) Ventilation conditions indoors can be ameliorated by constructing buildings on earth mound having a slant surface with a slope of 10° on upstream side.
xxv) In case of industrial buildings the window height should be about 1.6 m and width about two-third of wall width. These should be located at a height of 1.1 m above the floor. In addition to this, openings around 0.9 m high should be provided over two-third length of the glazed area in the roof lights.
xxvi) Height of industrial buildings, although determined by the requirements of industrial processes involved, generally kept large enough to protect the workers against hot stagnant air below the ceiling as also to dilute the concentration of contaminant inside. However, if high level openings in roof or walls are provided, building height can be reduced to 4 m without in any way impairing the ventilation performance.
NOTE — For data on outdoor wind speeds at a place, reference may be made to ‘The Climatic Data Handbook prepared by Central Building Research Institute, Roorkee, 1999’.
5.4.3.2 By stack effect
Natural ventilation by stack effect occurs when air inside a building is at a different temperature than air outside. Thus in heated buildings or in buildings wherein hot processes are carried on and in ordinary buildings during summer nights and during premonsoon periods, the inside temperature is higher than that of outside, cool outside air will tend to enter
through openings at low level and warm air will tend to leave through openings at high level. It would, therefore, be advantageous to provide ventilators as close to ceilings as possible. Ventilators can also be provided in roofs as, for example, cowl, ventpipe, covered roof and ridge vent.
5.5 Mechanical Ventilation
The requirements of mechanical ventilation shall be in accordance with Part 8 ‘Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation’.
Table 14 Percentage Sky Components on the Horizontal Plane Due to a Vertical Rectangular Opening for the Clear Design Sky (Clause A-1.5)
Rectandular Opening for the Clear D Table15Percentage Sky Components on the Vertical Plane Perpendicular to a
l/dh/d
0. 1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1 .0
1 . 1
1 .2
1 .3
1 .4
1 .5
1 .6
1 .7
1 .8
1 .9
2.0
3.0
4.0
5.0
1 0.0
INF
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(1 0)
(1 1)
(12)
(1 3)
(14)
(1 5)
(1 6)
(1 7)
(1 8)
(1 9)
(20)
(2 1)
(22)
(23)
(24)
(25)
(26)
0. 1
0.036
0. 141
0.303
0.506
0.734
0.97 1
1 .207
1 .432
1 .643
2.836
1 .0 1 1
2. 1 68
2.308
2.433
2.544
2.642
2.730
2.808
2.878
2.940
3.309
3.46 1
3.536
3.641
3.678
0.2
0.07 1
0.277
0.594
0.993
1 .442
1 .9 1 0
2.374
2.820
3.236
3.6 1 8
3.964
4.276
4.554
4.802
5.022
5.2 1 9
5.393
5.549
5.688
5.8 12
6.547
6.850
7.000
7.2 1 1
7.284
0.3
0. 1 03
0.401
0.863
1 .445
2. 1 00
2.793
3.475
4. 1 80
4.743
5.306
5.8 1 8
6.278
6.690
7.058
7.385
7.677
7.936
8. 1 68
8.375
8.560
9.657
1 0. 1 1 0
1 0.335
1 0.65 1
1 0.760
0.4
0. 126
0.49 1
1 .059
1 .779
2.597
3.460
4.326
5. 1 66
5.958
6.69 1
7.359
7.967
8.507
8.900
9.420
9.804
1 0. 146
1 0.45 1
1 0.724
1 0.968
12.42 1
1 3.024
1 3.323
1 3.743
1 3.889
0.5
0. 142
0.554
1 . 1 97
2.01 5
2.947
3.937
4.938
5.9 14
6.842
7.707
8.503
9.228
9.883
1 0.472
1 0.999
1 1 .476
1 1 .897
12.273
12.6 1 0
12.9 12
14.7 12
1 5.462
1 5.835
1 6.360
1 6.542
0.6
0. 1 54
0.600
1 .298
2. 1 87
3.204
4.288
5.389
6.468
7.498
8.464
9.358
1 0. 1 77
1 0.922
1 1 .596
12.204
12.752
1 3.244
1 3.686
14.084
14.441
1 6.583
1 7.478
1 7.924
1 8.552
1 8.77 1
0.7
0. 1 62
0.634
1 .372
2.3 1 6
3.397
4.552
5.729
6.887
7.997
9.042
1 0.01 3
1 0.907
1 1 .723
12.465
1 3. 1 38
1 3.746
14.296
14.793
1 5.241
1 5.646
1 8. 1 1 1
1 9. 148
1 9.665
20.397
20.653
0.8
0. 1 69
0.660
1 .429
2.41 3
3.543
4.754
5.990
7.209
8.382
9.490
1 0.523
1 1 .476
12.350
1 3. 147
1 3.873
14.53 1
1 5. 129
1 5.670
1 6. 1 6 1
1 6.606
1 9.36 1
20.538
2 1 . 127
2 1 .96 1
22.253
0.9
0. 1 74
0.680
1 .472
2.487
3.655
4.909
6. 1 92
7.460
8.683
9.841
1 0.924
1 1 .926
12.847
1 3.690
14.459
1 5. 1 59
1 5.796
1 6.375
1 6.902
1 7.38 1
20.387
2 1 .701
22.360
23.397
23.625
1 .0
0. 1 78
0.695
1 .505
2.545
3.743
5.030
6.350
7.657
8.92 1
1 0. 120
1 1 .243
12.284
1 3.245
14. 126
14.93 1
1 5.666
1 6.337
1 6.948
1 7.504
1 8.012
2 1 .237
22.680
23.408
24.446
24.8 1 0
1 . 1
0. 1 8 1
0.707
1 .532
2.59 1
3.8 12
5. 126
6.475
7.8 14
9. 1 1 0
1 0.342
1 1 .498
12.573
1 3.356
14.478
1 5.3 14
1 6.079
1 6.778
1 7.41 6
1 7.999
1 8.53 1
2 1 .946
23.508
24.303
25.441
25.841
1 .2
0. 1 83
0.7 1 6
1 .552
2.626
3.866
5.202
6.575
7.939
9.26 1
1 0.52 1
1 1 .705
12.807
1 3.827
14.766
1 5.628
1 6.41 8
1 7. 141
1 7.802
1 8.407
1 8.96 1
22.543
24.208
25.072
26.309
26.745
1 .3
0. 1 85
0.723
1 .568
2.655
3.9 1 0
5.263
6.655
8.040
9.384
1 0.666
1 1 .873
12.998
14.041
1 5.003
1 5.887
1 6.698
1 7.442
1 8. 123
1 8.747
1 9.320
23.049
24.809
25.735
27.070
27.542
1 .4
0. 1 86
0.729
1 .582
2.678
3.945
5.3 12
6.720
8. 122
9.484
1 0.785
12.01 1
1 3. 1 55
14.2 1 7
1 5. 1 98
1 6. 1 01
1 6.93 1
1 7.692
1 8.39 1
1 9.032
1 9.62 1
23.480
25.326
26.308
27.441
28.249
1 .5
0. 1 88
0.734
1 .592
2.697
3.973
5.352
6.773
8. 1 89
9.566
1 0.883
12. 124
1 3.285
14.364
1 5.36 1
1 6.280
1 7. 125
1 7.902
1 8.6 1 6
1 9.272
1 9.875
23.850
25.772
26.808
28.336
28.880
1 .6
0. 1 89
0.738
1 .601
2.7 12
3.996
5.385
6.8 1 6
8.244
9.634
1 0.963
12.2 1 9
1 3.394
14.486
1 5.497
1 6.430
1 7.289
1 8.079
1 8.806
1 9.475
20.090
24. 1 69
26. 1 6 1
27.245
28.866
29.445
1 .7
0. 1 89
0.741
1 .608
2.724
4.01 6
5.412
6.852
8.290
9.690
1 1 .03 1
12.298
1 3.484
14.589
1 5.5 1 1
1 6.556
1 7.427
1 8.229
1 8.968
1 9.648
20.274
24.444
26.501
27.629
29.340
29.955
1 .8
0. 1 90
0.744
1 .6 14
2.735
4.032
5.434
6.882
8.328
9.737
1 1 .087
12.364
1 3.56 1
14.675
1 5.708
1 6.663
1 7.545
1 8.357
1 9. 1 05
1 9.795
20.43 1
24.684
26.799
27.969
29.765
30.41 6
1 .9
0. 1 9 1
0.746
1 .6 1 9
2.743
4.045
5.453
6.908
8.360
9.777
1 1 . 1 35
12.420
1 3.625
14.749
1 5.79 1
1 6.755
1 7.645
1 8.466
1 9.224
1 9.922
20.567
24.893
27.062
28.270
30. 149
30.835
2.0
0. 1 9 1
0.748
1 .623
2.75 1
4.056
5.469
6.929
8.387
9.8 1 1
1 1 . 1 75
12.468
1 3.680
14.8 1 1
1 5.86 1
1 6.833
1 7.73 1
1 8.560
1 9.325
20.03 1
20.684
25.077
27.294
28.537
30.496
3 1 .2 1 7
3.0
0. 1 93
0.756
1 .642
2.785
4. 1 09
5.544
7.030
8.5 1 7
9.972
1 1 .37 1
12.699
1 3.950
1 5. 120
1 6.2 1 1
1 7.224
1 8. 1 64
1 9.036
1 9.844
20.594
2 1 .289
26.082
28.6 1 9
30. 1 08
32.676
32.742
4.0
0. 1 94
0.759
1 .648
2.794
4. 124
5.566
7.058
8.540
1 0.01 8
1 1 .427
12.767
14.029
1 5.2 12
1 6.3 1 6
1 7.343
1 8.298
1 9. 1 85
20.008
20.772
2 1 .483
26.439
29. 128
30.745
33.687
35.064
5.0
0. 1 94
0.760
1 .650
2.798
4. 129
5.574
7.069
8.568
1 0.036
1 1 .449
12.793
14.060
1 5.248
1 6.357
1 7.390
1 8.35 1
1 9.243
20.073
20.844
2 1 .562
26.592
29.359
3 1 .049
34.232
35.872
1 0.0
0. 1 94
0.76 1
1 .652
2.801
4. 1 35
5.58 1
7.080
8.582
1 0.053
1 1 .470
12.8 1 8
14.095
1 5.283
1 6.398
1 7.436
1 8.403
1 9.302
20. 1 38
20.9 1 7
2 1 .641
26.758
29.624
3 1 .41 9
35.049
37.5 1 3
INF
0. 1 94
0.76 1
1 .652
2.802
4. 1 36
5.582
7.08 1
8.584
1 0.056
1 1 .473
12.822
14.095
1 5.288
1 6.404
1 7.443
1 8.41 1
1 9.3 1 1
20. 148
20.928
2 1 .654
26.785
29.672
3 1 .490
35.274
39. 1 72
Rectandular Opening for the Clear D Table16Percentage Sky Components on the Vertical Plane Parallel to a
0.1
0.728
1.429
2.078
2.600
3.167
3.660
3.964
4.265
4.513
4.717
4.883
5.020
5.132
5.225
5.301
5.365
5.418
5.463
5.501
5.533
5.687
5.733
5.749
5.765
5.766
0.2
1.429
2.803
4.007
5.221
6.220
7.073
7.790
8.385
8.876
9.278
9.609
9.880
10.103
10.286
10.439
10.565
10.671
10.760
10.835
10.899
11.207
11.296
11.330
11.362
11.365
0.3
2.068
4.061
5.913
7.580
9.040
10.285
11.337
12.212
12.934
13.528
14.016
14.417
14.747
15.020
15.246
15.434
15.591
15.724
15.836
15.931
16.390
16.523
16.574
16.623
16.627
0.4
2.529
4.970
7.249
9.312
11.133
12.707
14.042
15.164
16.097
16.870
17.507
18.025
18.458
18.816
19.113
19.360
19.568
19.742
19.890
20.015
20.624
20.801
20.868
20.933
20.939
0.5
2.852
5.608
8.186
10.529
12.606
14.401
15.952
17.256
18.350
19.262
20.021
20.652
21.177
21.613
21.978
22.275
22.530
22.746
22.923
23.082
23.836
24.056
24.140
24.222
24.229
0.6
3.086
6.070
8.867
11.415
13.681
15.656
17.353
18.793
20.008
21.027
21.879
22.592
23.189
23.689
24.109
24.462
24.761
25.014
25.229
25.412
26.229
26.561
26.662
26.759
26.768
0.7
3.259
6.413
9.373
12.074
14.482
16.588
18.402
19.949
21.257
22.359
23.285
24.063
24.716
25.267
25.731
26.124
26.458
26.742
26.984
27.192
28.214
28.517
28.634
28.748
28.758
0.8
3.389
6.672
9.755
12.573
15.090
17.296
19.201
20.830
22.212
23.380
24.365
25.195
25.895
26.486
26.987
27.412
27.775
28.084
28.350
28.578
29.720
30.065
30.198
30.327
30.339
0.9
3.489
6.869
10.046
12.955
15.556
17.840
19.817
21.511
22.952
24.173
25.206
26.078
26.816
27.441
27.972
28.424
28.810
29.141
29.426
29.672
30.927
31.303
31.451
31.596
31.610
1.0
3.565
7.024
10.272
13.250
15.917
18.263
20.297
22.043
23.531
24.795
25.866
26.773
27.542
28.196
28.572
29.226
29.633
29.982
30.283
30.544
31.889
32.302
32.467
32.627
32.643
1.1
3.625
7.139
10.447
13.481
16.200
18.594
20.674
22.462
23.989
25.288
26.391
27.326
28.121
28.798
29.375
29.869
30.293
30.658
30.973
31.246
32.670
33.117
33.297
33.473
33.491
1.2
3.672
7.233
10.586
13.663
16.423
18.857
20.973
22.795
24.353
25.681
26.810
27.770
28.587
29.283
29.878
30.388
30.826
31.204
31.532
31.816
33.309
33.796
33.981
34.173
34.193
1.3
3.709
7.307
10.696
13.807
16.602
19.067
21.213
23.062
24.646
25.998
27.148
28.128
28.963
29.676
30.286
30.810
31.261
31.651
31.989
32.283
33.836
34.350
34.550
34.756
34.779
1.4
3.739
7.366
10.784
13.924
16.745
19.236
21.406
23.278
24.884
26.255
27.424
28.420
29.271
29.998
30.621
31.157
31.618
32.018
32.365
32.667
34.374
34.813
35.035
35.247
35.271
1.5
3.763
7.414
10.856
14.018
16.861
19.373
21.563
23.454
25.077
26.465
27.649
28.660
29.523
30.262
30.897
31.443
31.914
32.322
32.677
32.986
34.641
35.202
35.436
35.663
35.689
1.6
3.783
7.453
10.914
14.095
16.956
19.485
21.692
23.599
25.236
26.638
27.835
28.857
29.732
30.482
31.226
31.680
32.160
32.575
32.937
33.253
34.950
35.532
35.776
36.017
36.046
1.7
3.799
7.485
10.962
14.158
17.034
19.578
21.798
23.718
25.368
26.781
27.989
29.022
29.906
30.665
31.317
31.879
32.366
32.888
33.156
33.477
35.211
35.812
36.067
36.321
36.352
1.8
3.812
7.512
11.002
14.211
17.099
19.655
21.886
23.817
25.478
26.900
28.118
29.160
30.052
30.818
31.477
32.046
32.539
32.967
33.340
33.666
35.435
36.052
36.316
36.584
36.617
1.9
3.824
7.534
11.035
14.254
17.153
19.719
21.960
23.900
25.570
27.001
28.226
26.276
30.175
30.948
31.613
32.188
32.686
33.119
33.497
33.828
35.626
35.259
36.532
36.812
36.847
2.0
3.833
7.553
11.062
14.291
17.199
19.773
22.022
23.970
25.647
27.086
28.318
29.374
31.279
31.058
31.728
32.308
32.811
33.249
33.631
33.965
35.791
36.438
36.719
37.011
37.048
3.0
3.876
7.639
11.192
14.463
17.412
20.027
22.316
24.302
26.016
27.491
28.757
29.846
30.783
31.592
32.291
32.898
33.427
33.889
34.294
34.551
36.640
37.380
37.715
38.107
38.157
4.0
3.888
7.663
11.228
14.511
17.471
20.098
22.398
24.398
26.121
27.606
28.884
29.983
30.930
31.748
32.457
33.074
33.611
34.082
34.496
34.860
36.915
37.699
38.063
38.510
38.579
5.0
3.893
7.672
11.241
14.529
17.494
20.125
22.430
24.432
26.161
27.650
28.932
30.035
30.986
31.808
32.521
33.142
33.683
34.157
34.574
34.943
37.028
37.834
38.214
38.696
38.781
10.0
3.897
7681
11.254
14.546
17.515
20.150
22.459
24.466
26.199
27.693
28.978
30.085
31.041
31.867
32.584
33.208
33.753
34.231
34.652
35.024
37.144
37.978.
38.382
38.927
39.057
INF
3.898
7.682
11.256
44.548
17.518
20.154
22.464
24.471
26.205
27.699
28.985
30.093
31.049
31.876
32.593
33.218
33.764
34.243
34.664
35.037
37.162
38.003
38.411
38.978
39.172
LIST OF STANDARDS
The following list records those standards which are acceptable as ‘good practice’ and ‘accepted standards in the fulfillment of the requirements of the Code. The latest version of a standard shall be adopted at the time of enforcement of the Code. The standards listed may be used by the Authority as a guide in conformance with the requirements of the referred clauses in the Code.
IS No. Title
(1) 7662 Recommendations for (Part 1) : 1974 orientation of buildings: Part 1 Non-industrial buildings
(2) 3646 Code of practice for interior (Part 1) : 1992 illumination: Part 1 General requirements and recommendations for building interiors (first revision)
(3) 2440 : 1975 Guide for daylighting of buildings (second revision)
(4) 6060 : 1971 Code of practice for daylighting of factory buildings
IS No.
Title
7942 : 1976
Code of practice for daylighting of educational buildings
(5) 1944(Parts 1 & 2): 1970
Code of practice for lighting of public thoroughfares: Parts 1 and 2 For main and secondary roads (Group A and B) (first revision)
2672 : 1966
Code of practice for library lighting
4347 : 1967
Code of practice for hospital lighting
6665 : 1972
Code of practice for industrial lighting
10894 : 1984
Code of practice for lighting of educational institutions
10947 : 1984
Code of practice for lighting for ports and harbours
(6) 3362 : 1977
Code of practice for natural ventilation of residential buildings (first revision)
PART 8 BUILDING SERVICES
Section 2 Electrical and Allied Installations
BUREAU OF INDIAN STANDARDS
FOREWORD
... 3
1 SCOPE
... 5
2 TERMINOLOGY AND CONVENTIONAL SYMBOLS
... 5
3 GENERAL REQUIREMENTS
... 9
4 PLANNING OF ELECTRICAL INSTALLATIONS
... 9
5 DISTRIBUTION OF SUPPLY AND CABLING
... 16
6 WIRING
... 28
7 FITTINGS AND ACCESSORIES
... 36
8 EARTHING
... 39
9 INSPECTION AND TESTING OF INSTALLATION
... 43
10 TELECOMMUNICATION AND OTHER MISCELLANEOUS SERVICES
... 48
11 LIGHTNING PROTECTION OF BUILDINGS
... 49
ANNEX A DRAWING SYMBOLS FOR ELECTRICAL INSTALLATION IN BUILDING
... 56
ANNEX B EXTRACTS FROM INDIAN ELECTRICITY RULES, 1956
... 58
ANNEX C AREA REQUIRED FOR TRANSFORMER ROOM AND SUBSTATION FOR DIFFERENT CAPACITIES
... 63
ANNEX D ADDITIONAL AREA REQUIRED FOR GENERATOR IN ELECTRIC SUBSTATION
... 63
ANNEX E FORM OF COMPLETION CERTIFICATE
... 64
LIST OF STANDARDS
... 65
National Building Code Sectional Committee, CED 46
This Section covers essential requirements for electrical and allied installations in buildings.
This Section was first published in 1970 and was subsequently revised in 1983. In the first revision, general guidance for electrical wiring installation in industrial location where voltage supply normally exceeds 650 V was included. This Section was also updated based on the existing version of the Indian Standards. The importance of pre-planning and exchange of information among all concerned agencies from the earlier stages of building work was emphasized.
As a result of experience gained in implementation of 1983 version of the Code and feedback received as well as revision of some of the relevant standards based on which this Section was prepared, a need to revise this part was felt. This revision has, therefore, been prepared to take care of these developments. The title of this Section has been modified from the erstwhile ‘electrical installations’ to ‘electrical and allied installations’ to reflect the provisions now being included on certain allied installations. The significant changes incorporated in this revision include:
a) The risk assessment procedure for lightening has been thoroughly changed apart from some other changes in the provision of lightning protection of building.
b) Some of the provisions of wiring have now been aligned with the latest practices.
c) Many existing definitions have been modified in line with current terminologies used at national and international level. Some new definitions have been added.
d) Provisions on installation of distribution transformer inside the multi-storeyed building have been incorporated.
e) Concept of energy conservation in lighting has been introduced.
f) Concept of various types of earthing in building installation has been incorporated.
This Section has to be read together with Part 8 ‘Building Services, Section 1 Lighting and Ventilation’ for making provision for the desired levels of illumination as well as ventilation for different locations in different occupancies. Utmost importance should be given in the installation of electrical wiring to prevent short circuiting and the hazards associated therewith.
Notwithstanding the provisions given in this Section and the National Electrical Code, the provisions of the Indian Electricity Act, 2003 and the Rules and Regulations framed thereunder have to be necessarily complied with.
The information contained in this Section is largely based on the following Indian Standards/Special Publication:
IS 732 : 1989 Code of practice for electrical wiring installations (third revision)
IS 12032 Specification for graphical symbols for diagrams in the field of electrotechnology:
(Part 11) : 1987 Part 11 Architectural and topographical installation plan and diagrams
IS 4648 : 1968 Guide for electrical layout in residential buildings
IS 2309 : 1989 Protection of building and allied structures against lightning — Code of practice (second revision)
SP 30 : 1984 National Electrical Code, 1985
All standards, whether given herein above or cross-referred to in the main text of this Section, are subject to revision. The parties to agreement based on this Section are encouraged to investigate the possibility of applying the most recent editions of the standards.
θ
=
Lzsecθ
when θ lies between 1 5 ° and 9 0 ° , and L e is constant when θ lies between 0 ° and 1 5 ° ,
2.1.7 Colour Rendering Index (CRI) — Measure of the degree to which the psychophysical colour of an object illuminated by the test illuminant conforms to that of the same object illuminated by the reference illuminant, suitable allowance having been made for the state of chromatic adaptation.
2.1.8 Correlated Colour Temperature (CCT) (Unit: K) — The temperature of the Planckian radiator whose perceived colour most closely resembles that of a given stimulus at the same brightness and under specified viewing conditions.
2.1.9 Daylight Area — The superficial area on the working plane illuminated to not less than a specified daylight factor, that is, the area within the relevant contour.
2.1.10 Daylight Factor — The measure of total daylight illuminance at a point on a given plane expressed as the ratio (or percentage) which the illuminance at the point on the given plane bears to the simultaneous illuminance on a horizontal plane due to clear design sky at an exterior point open to the whole sky vault, direct sunlight being excluded.
2.1.11 Daylight Penetration — The maximum distance to which a given daylight factor contour penetrates into a room.
2.1.12 Direct Solar Illuminance — The illuminance from the sun without taking into account the light from the sky.
2.1.13 External Reflected Component (ERC) — The ratio (or percentage) of that part of the daylight illuminance at a point on a given plane which is received by direct reflection from external surfaces as compared to the simultaneous exterior illuminance on a horizontal plane from the entire hemisphere of an unobstructed clear design sky.
2.1.14 Glare — A condition of vision in which there is discomfort or a reduction in the ability to see
significant objects or both due to an unsuitable distribution or range of luminance or due to extreme contrasts in space and time.
2.1.15 Illuminance — At a point on a surface, the ratio of the luminous flux incident on an infinitesimal element of the surface containing the point under consideration to the area of the element.
NOTE — The unit of illuminance (the measurement of illumination) is lux which is 1 lumen per square metre.
2.1.16 Internal Reflected Component (IRC) — The ratio (or percentage) of that part of the daylight illuminance at a point in a given plane which is received by direct reflection or inter-reflection from the internal surfaces as compared to the simultaneous exterior illuminance on a horizontal plane due to the entire hemisphere of an unobstructed clear design sky.
2.1.17 Light Output Ratio (LOR) or Efficiency (η ) — The ratio of the luminous flux emitted from the luminaire to that emitted from the lamp(s) (nominal luminous flux). It is expressed in percent.
2.1.18 Lumen (lm) — SI unit of luminous flux. The luminous flux emitted within unit solid angle (one steradian) by a point source having a uniform intensity of one candela.
2.1.19 Luminance (At a point of a Surface in a Given Direction) (Brightness) — The quotient of the luminous intensity in the given direction of an infinitesimal element of the surface containing the point under consideration by the orthogonally projected area of the element on a plane perpendicular to the given direction. The unit is candela per square metre (cd/m2).
2.1.20 Luminous Flux (φ) — The quantity characteristic of radiant flux which expresses its capacity to produce visual sensation evaluated according to the values of relative luminous efficiency for the light adapted eye:
a) Effective luminous flux (φ ) — Total luminous flux which reaches the working plane.
b) Nominal luminous flux (φ ) — Total luminous flux of the light sources in the interior.
2.1.21 Maintenance Factor (d) — The ratio of the average illuminance on the working plane after a certain period of use of a lighting installation to the average illuminance obtained under the same conditions for a new installation.
2.1.22 Meridian — It is the great circle passing through the zenith and nadir for a given point of observation.
2.1.23 North and South Points — The point in the respective directions where the meridian cuts the horizon.
2.1.24 Orientation of Buildings — In the case of non-square buildings, orientation refers to the direction of the normal to the long axis. For example, if the length of the building is east-west, its orientation is northsouth.
2.1.25 Peripheral Field — It is the rest of the visual field which enables the observer to be aware of the spatial framework surrounding the object seen.
NOTE — A central part of the peripheral field, subtending an angle of about 30° on either side of the point of fixation, is chiefly involved in the perception of glare.
2.1.26 Reflected Glare — The variety of ill effects on visual efficiency and comfort produced by unwanted reflections in and around the task area.
2.1.27 Reflection Factor (Reflectance) — The ratio of the luminous flux reflected by a body (with or without diffusion) to the flux it receives. Some symbols used for reflection factor are:
r c = Reflection factor of ceiling.
r w = Reflection factor of parts of the wall between the working surface and the luminaires.
r f = Reflection factor of floor.
2.1.28 Reveal — The side of an opening for a window.
2.1.29 Room Index ( k r ) — An index relating to the shape of a rectangular interior, according to the formula:
kr=(L+W)HmL.W
where L and W are the length and width respectively of the interior, and H m is the mounting height, that is, height of the fittings above the working plane.
NOTES
1 For rooms where the length exceeds 5 times the width, L shall be taken as L = 5W.
2 If the reflection factor of the upper stretch of the walls is less than half the reflection factor of the ceiling, for indirect or for the greater part of indirect lighting, the value H m is measured between the ceiling and the working plane.
2.1.30 Sky Component (SC) — The ratio (or percentage) of that part of the daylight illuminance at a point on a given plane which is received directly from the sky as compared to the simultaneous exterior illuminance on a horizontal plane from the entire hemisphere of an unobstructed clear design sky.
2.1.31 Solar Load — The amount of heat received into a building due to solar radiation which is affected by orientation, materials of construction and reflection of external finishes and colour.
2.1.32 Utilization Factor (Coefficient of Utilizaiton) ( μ ) — The ratio of the total luminous flux which reaches the working plane (effective luminous
flux, n ) to the total luminous flux of the light sources in the interior (nominal luminous flux, φ ).
2.1.33 Visual Field — The visual field in the binocular which includes an area approximately 120° vertically and 160° horizontally centering on the point to which the eyes are directed. The line joining the point of fixation and the centre of the pupil of each eye is called its primary line of sight.
2.1.34 Working Plane — A horizontal plane at a level at which work will normally be done (see 4.1.3.3 and 4.1.3.4).
5.6.1.4 When both forces (wind and thermal) act together in the same direction, even without interference, the resulting air flow is not equal to the two flows estimated separately. Flow through any opening is proportional to the square root of the sum of the two heads acting on that opening.
Wind velocity and direction, outdoor temperature, and indoor distribution can not be predicted with certainty, and refinement in calculation is not justified. A simple method is calculate the sum of the flows produced by each force separately. Then using the ratio of the flow produced by thermal forces to the aforementioned sum, the actual flow due to the combined forces can be approximated from Fig. 5. When the two flows are equal, the actual flow is about 30 percent greater than the flow caused by either force acting independently (see Fig. 5).

FLOW DUE TO TEMPERATURE DIFFERENCE AS PERCENT OF TOTAL
FIG. 5 DETERMINATION OF FLOW CAUSED BY COMBINED FORCES OF WIND AND TEMPERATURE DIFFERENCE
Judgement is necessary for proper location of openings in a building specially in the roof, where heat, smoke and fumes are to be removed. Usually, windward monitor openings should be closed, but if wind is so
slight that temperature head can overcome it, all openings may be opened.
5.6.1.5 For method for determining the rate of ventilation based on probable indoor wind speed with typical illustrative example for residential building, reference may be made to good practice [8-1(6)].
### 5.6.2 Mechanical Ventilation
The determination of rate of ventilation in case of mechanical ventilation shall be done in accordance with Part 8 ‘Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation’.
### 5.6.3 Combined Effect of Different Methods of Ventilation
When combination of two or more methods of general ventilation is used, the total rate of ventilation shall be reckoned as the highest of the following three, and this rule shall be followed until an exact formula is established by research:
a) 1.25 times the rate of natural ventilation,
b) Rate of positive ventilation, and
c) Rate of exhaust of air.
### 5.6.4 Air Movement
The rate of air movement of turbulent type at the working zone shall be measured either with a Kata thermometer (dry silvered type) or heated thermometer or properly calibrated thermocouple anemometer. Whereas anemometer gives the air velocity directly, the Kata thermometer and heated thermometer give cooling power of air and the rate of air movement is found by reference to a suitable nomogram using the ambient temperature.
1 200/2
1 400/2
1 400/2
1 400/2
1 200/3
1 400/3
1 400/3
4
1 200/1
1 400/1
1 200/2
1 200/2
1 200/2
1 400/2
1 400/2
1 500/2
1 200/3
1 400/3
1 500/3
5
1 400/1
1 400/1
1 400/2
1 400/2
1 400/2
1 400/2
1 400/2
1 500/2
1 400/3
1 400/3
1 500/3
6
1 200/2
1 400/2
900/4
1 050/4
1 200/4
1 400/4
1 400/4
1 500/4
1 200/6
1 400/6
1 500/6
7
1 200/2
1 400/2
1 050/4
1 050/4
1 200/4
1 400/4
1 400/4
1 500/4
1 200/6
1 400/6
1 500/6
8
1 200/2
1 400/2
1 200/4
1 200/4
1 200/4
1 400/4
1 400/4
1 500/4
1 200/6
1 400/6
1 500/6
9
1 400/2
1 400/2
1 400/4
1 400/4
1 400/4
1 400/4
1 400/4
1 500/4
1 400/6
1 400/6
1 500/6
10
1 400/2
1 400/2
1 400/4
1 400/4
1 400/4
1 400/4
1 400/4
1 500/4
1 400/6
1 400/6
1 500/6
11
1 500/2
1 500/2
1 500/4
1 500/4
1 500/4
1 500/4
1 500/4
1 500/4
1 500/6
1 500/6
1 500/6
12
1 200/3
1 400/3
1 200/6
1 200/6
1 200/6
1 400/6
1 400/6
1 500/6
1 200/7
1 400/9
1 400/9
13
1 400/3
1 400/3
1 200/6
1 200/6
1 200/6
1 400/6
1 400/6
1 500/6
1 400/9
1 400/9
1 500/9
14
1 400/3
1 400/3
1 400/6
1 400/6
1 400/6
1 400/6
1 400/6
1 500/6
1 400/9
1 400/9
1 500/9
3
4.4.1.2
With occasional manual operation
100-150-200
3
4.4.1.3
With continuous manual operation
150-200-300
3
4.4.1.4
Control room
200-300-500
1
Localized lighting of the control display and the control desks may be appropriate
Supplementary lighting may be necessary for maintenance work
14.1.2.3
Inspection, sorting
300-500-750
1
14.1.3
Paper converting processes
14.1.3.1
General
200-300-500
3
14.1.3.2
Associated printing
300-500-750
2
14.2
Printing Works
14.2.1
Type foundries
14.2.1.1
Matrix making, dressing type, hand and machine coating
200-300-500
3
14.2.1.2
Front assembly, sorting
500-750-1000
2
14.2.2
Composing rooms
14.2.2.1
Hand composing, imposition and distribution
500-750-1000
1
14.2.2.2
Hot metal keyboard
500-750-1000
1
14.2.2.3
Hot metal casting
200-300-500
2
14.2.2.4
Photo composing keyboard or setters
300-500-750
1
14.2.2.5
Paste up
500-750-1000
1
14.2.2.6
Illuminated tables — general lighting
200-300-500
—
Dimming may be required
14.2.2.7
Proof presses
300-500-750
2
14.2.2.8
Proof reading
500-750-1000
1
14.2.3
Graphic reproduction
14.2.3.1
General
300-500-750
2
14.2.3.2
Precision proofing, retouching, etching
750-1000-1500
1
Local lighting may be appropriate
14.2.3.3
Colour reproduction and inspection
750-1000-1500
1
14.2.4
Printing machine room
14.2.4.1
Presses
300-500-750
2
14.2.4.2
Premake ready
300-500-750
2
14.2.4.3
Printed sheet inspection
750-1000-1500
1
14.2.5
Binding
14.2.5.1
Folding, pasting, punching and stitching
300-500-750
2
14.2.5.2
Cutting, assembling, embossing
500-750-1000
2
15
PLASTIC AND RUBBER
15.1
Plastic Products
15.1.1
Automatic plant
16.2
Warehouses and Bulk Stores
16.2.1
Storage of goods where indentification requires only limited preparation of detail
50-100-150
3
16.2.2
Storage of goods where identification requires perception of detail
100-150-200
3
16.2.3
Automatic high bay rack stores
16.2.3.1
Gangway
20
—
16.2.3.2
Control station
150-200-300
3
16.2.3.3
Packing and dispatch
200-300-500
3
16.2.3.4
Loading bays
100-150-200
3
Avoid glare to drivers of vehicles approaching the loading bay
16.3
Cold Stores
16.3.1
General
200-300-500
3
16.3.2
Breakdown, make-up and dispatch
200-300-500
3
16.3.3
Loading bays
100-150-200
3
Avoid glare to drivers of vehicles approaching the loading bay
17
COMMERCE
17.1
Offices
17.1.1
General offices
300-500-750
1
17.1.2
Deep plan general offices
500-750-1000
1
17.1.3
Computer work stations
300-500-750
1
17.1.4
Conference rooms, executive offices
300-500-750
1
17.1.5
Computer and data preparation rooms
300-500-750
1
171.6
Filing rooms
200-300-500
1
17.2
Drawing Offices
17.2.1
General
300-500-750
1
17.2.2
Drawing boards
500-750-1000
1
17.2.3
Computer aided design and drafting
—
—
Special lighting is required
17.2.4
Print rooms
200-300-500
1
17.3
Banks and Building Societies
17.3.1
Counter, office area
300-500-750
1
17.3.2
Public area
200-300-500
1
18
SERVICES
18.1
Garages
18.1.1
Interior parking areas
20-30-50
3
19.2
Small Self-Service Shops with Island Displays
300-500-750
1
19.3
Supper Markets, Hyper-Markets
19.3.1
General
300-500-750
2
19.3.2
Checkout
300-500-750
2
19.3.3
Showroom for large objects, for example, cars, furnitures
300-500-750
1
19.3.4
Shopping precincts and arcades
100-150-200
2
20
PLACES OF PUBLIC ASSEMBLY
20.1
Public Rooms, Village Halls, Worship Halls
200-300-500
1
20.2
Concert Halls, Cinemas and Theatres
20.2.1
Foyer
150-200-300
—
20.2.2
Booking office
200-300-500
—
Local or localized lighting may be appropriate
20.2.3
Auditorium
50-100-150
—
Dimming facilities will be necessary. Special lighting of the aisles is desirable
20.2.4
Dressing rooms
200-300-500
—
Special mirror lighting for make-up may be required
20.2.5
Projection room
100-150-200
—
20.3
Churches
20.3.1
Body of church
100-150-200
2
20.3.2
Pulpit, lectern
200-300-500
2
Use local lighting
20.3.3
Choir stalls
200-300-500
2
Local lighting may be appropriate
20.3.4
Alter, communion table, chancel
100-150-200
2
Additional lighting to provide emphasis is desirable
20.3.5
Vestries
100-150-200
2
20.3.6
Organ
200-300-500
—
20.4
Hospitals
20.4.1
Anaesthetic rooms
General
200-300-500
—
20.4.8.2
Examination
300-500-750
—
20.4.9
Nurses' stations
20.4.9.1
Morning/day/evening
200-300-500
—
20.4.9.2
Night desks
30
—
20.4.9.3
Night, medical trolleys
50-100-150
—
20.4.10
Operating theatres
20.4.10.1
General
300-500-750
—
20.4.10.2
Local
10 000 to 50 000
—
Special operating lights are used
20.4.11
Pathology departments
20.4.11.1
General
200-300-500
—
20.4.11.2
Examination
300-500-750
—
20.4.11.3
Pharmacies
200-300-500
—
20.4.11.4
Reception/enquiry
200-300-500
—
20.4.11.5
Recovery rooms
200-300-500
—
20.4.12
Ward-circulation
20.4.12.1
Day
50-100-150
—
20.4.12.2
Morning/Evening
50-100-150
—
20.4.12.3
Night
3-5
—
20.4.13
Ward-bed head
20.4.13.1
Morning/Evening
30-50
20.4.13.2
Reading
100-150-200
20.4.14
Night
20.4.14.1
Adult
0.1-1
20.4.14.2
Pediatric
1
20.4.14.3
Psychiatric
1-5
20.4.14.4
Watch
5
20.4.15
X-Ray areas
20.4.15.1
General
150-200-300
20.4.15.2
Diagnostic
150-200-300
20.4.15.3
Operative
200-300-500
20.4.15.4
Process dark room
50
20.4.16
Surgeries
20.4.16.1
General
200-300-500
—
20.4.16.2
Waiting rooms
100-150-200
—
20.4.17
Dental surgeries
20.4.17.1
Chair
Special lighting
20.6.2
Catalogues
20.6.2.1
Card
100-150-200
2
20.6.2.2
Microfiche/Visual display units
100-150-200
2
20.6.3
Reference libraries
20.6.3.1
General
200-300-500
1
20.6.3.2
Counters
300-500-750
1
Localized lighting may be appropriate
20.6.3.3
Bookshelves
100-150-200
2
The service illuminance should be provided on a vertical surface at the foot of the bookshelves
20.6.3.4
Study tables, carrels
300-500-750
1
20.6.3.5
Map room
200-300-500
1
20.6.4
Display and exhibition areas
20.6.4.1
Exhibits insensitive to light
200-300-500
—
20.6.4.2
Exhibit sensitive to light, for example, pictures, prints, rare books in archives
50 to 150
—
20.6.5
Library workrooms
20.6.5.1
Book repair and binding
300-500-750
2
20.6.5.2
Catalogue and sorting
300-500-750
2
20.6.5.3
Remote book stores
100-150-200
3
20.7
Museums and Art Galleries
20.7.1
Exhibits insensitive to light
200-300-500
—
20.7.2
Light sensitive exhibits, for example, oil and temper paints, undyed leather, bone, ivory, wood, etc
150
—
This is a maximum illuminance to be provided on the principal plane of the exhibit
20.7.3
Extremely light sensitive exhibits, for example, textiles, water colours, prints and drawings, skins, botanical specimens, etc
50
—
This is the maximum illuminance to be provided on the principal plane of the object
20.7.4
Conservation studies and workshops
300-500-750
1
20.8
Sports Facilities
2
22.1.4
Baggage handling
50-100-150
2
22.1.5
Customs and immigration halls
300-500-750
2
22.1.6
Concourse
150-200-300
2
22.2
Railway Stations
22.2.1
Ticket office
300-500-750
2
Localized lighting may be appropriate
22.2.2
Information office
300-500-750
2
Localized lighting over the counter may be appropriate
22.2.3
Parcels office, left
22.2.4
Luggage office
22.2.4.1
General
50-100-150
2
22.2.4.2
Counter
150-200-300
2
22.2.5
Waiting rooms
150-200-300
2
22.2.6
Concourse
150-200-300
2
22.2.7
Time table
150-200-300
2
Localized lighting may be appropriate
22.2.8
Ticket barriers
150-200-300
2
Localized lighting may be appropriate
22.2.9
Platforms (covered)
30-50-100
2
Care should be taken to light and mark the edge of the platform clearly
22.2.10
Platforms (open)
20
—
Care should be taken to light and mark the edge of the platform clearly
22.3
Coach Stations
50-100-150
—
23.4.2
Rest rooms
100-150-200
1
23.5
Staff Restaurants
23.5.1
Canteens, cafeterias, dining rooms, mess rooms
150-200-300
2
23.5.2
Servery, vegetable preparation, washing-up area
200-300-500
2
23.5.3
Food preparation and cooking
300-500-750
2
23.5.4
Food stores, cellars
100-150-200
2
23.6
Communications
23.6.1
Switchboard rooms
200-300-500
2
23.6.2
Telephone apparatus rooms
100-150-200
2
23.6.3
Telex room, post room
300-500-750
2
23.6.4
Reprographic room
200-300-500
2
23.7
Building Services
23.7.1
Boiler houses
23.7.1.1
General
50-100-150
3
23.7.1.2
Boiler front
100-150-200
3
23.7.1.3
Boiler control room
200-300-500
2
Localized lighting of the control display and the control desk may be appropriate
23.7.1.4
Control rooms
200-300-500
2
Localized lighting of the control display and the control desk may be appropriate
23.7.1.5
Mechanical plant room
100-150-200
2
23.7.1.6
Electrical power supply and distribution rooms
100-150-200
2
23.7.1.7
Store rooms
50-100-150
3
23.8
Car Parks
23.8.1
Covered car parks
23.8.1.1
Floors
5-20
—
23.8.1.2
Ramps and corners
30
—
23.8.1.3
Enterances and exits
50-100-150
—
23.8.1.4
Control booths
150-200-300
—
23.8.1.5
Outdoor car parks
5-20
—
where
Q ₂ = Quantity of air in m ³ / h,
K ₁ = Latent heat gained in W, and
h=Allowable vapour pressure difference in mmof mercury.
NOTE — In majority of the cases, the sensible heat gain will far exceed the latent heat gain, so that the amount of outside air to be drawn by ventilating equipment can be calculated in most cases on the basis of the equation given in 5.3.2.1.
5.3.2.4 Ventilation is also expressed as m3/h per m2 of floor area. This relationship fails to evaluate the actual heat relief provided by a ventilation system, but it does give a relationship which is independent of building height. This is a more rational approach, because, with the same internal load, the same amount of ventilation air, properly applied to the work zone with adequate velocity, will provide the desired heat relief quite independently of the ceiling height of the space, with few exceptions. Ventilation rates of 30 to 60 m3/h per m2 have been found to give good results in many plants.