(a) A satisfactory supply of water exclusively for the purpose of fire fighting shall always be available in the form of underground static storage tank/ Overhead tank with capacity specified in NBC 2016 with arrangements of replenishment by town’s main or alternative source of supply @
1000 litres per minute. The static storage water supply required for the above-mentioned purpose shall entirely be accessible to the fire tenders of the local fire service. Provision of suitable number of manholes shall be made available for inspection repairs and insertion of suction hose etc. The covering slab shall be able to withstand the vehicular load of 45 tons in case of high rise and 22 tons in case of low rise buildings. A draw off connection shall be provided. The slab need not strengthened if the static tank is not located in mandatory driveway required around the building.
(b) To prevent stagnation of water in the static water tank the suction tank of the domestic water supply shall be fed only through an over flow arrangement to maintain the level therein at the minimum specified capacity; and
(c) The static water storage tank shall be provided with a fire brigade inlet of 63mm dia. instantaneous male inlets arranged in a valve box with a suitable fixed pipe not less than 15 cm dia. to discharge water into the tank. Number of inlets shall be as specified in NBC. This arrangement is not required where down comer is provided.
12.21 Automatic sprinklers.- Automatic sprinkler system shall be installed in the following buildings:
(a) All buildings of 24m and above in height, except group housing and 45m and above in case of apartment /group housing society building.
(b) Hotels below 15m in height and above 1000Sq.m built up area at each floor and or if basement is existing.
(c) All hotels, mercantile and institutional buildings above15m.
(d) Underground Shopping Complex.
(e) Underground car / scooter parking /enclosed car parking.
(f) Any special hazards where the Chief Fire Officer considers it necessary.
(g) For buildings, up to 24m in height where automatic sprinkler system is not mandatory as per these Bye-Laws, if provided with sprinkler installation following relaxation may be considered.
(i) Automatic heat/smoke detection system and M.C.P. need not be insisted upon.
(ii) The number of Fire Extinguisher required shall be reduced by half.
12.22 Fixed Carbon di-oxide /Foam/DCO water spray extinguishing system.- Fixed extinguishing installations shall be provided as per the relevant specifications in the premises where use of above extinguishing media is considered necessary by the Chief Fire Officer.
12.23 Fire alarm system.- All buildings of 15m and above in height shall be equipped with fire alarm system, and also residential buildings (Dwelling House, Boarding House and Hostels) above 24 m height.
(1) All residential buildings like dwelling houses (including flats) boarding houses and hostels shall be equipped with manually operated electrical fire alarm system with one or more call boxes located at each floor. The location of the call boxes shall be decided after taking into consideration their floor without having to travel more than the distance specified in NBC 2016.
(2) The call boxes shall be of the break glass type without any moving parts, where the call is transmitted automatically to the control room without any other action on the part of the person operating the call boxes.
(3) All call boxes shall be wired in a closed circuit to a control panel in a control room, located as per Bye-Laws so that the floor number from where the callbox is actuated is clearly indicated on the control panel. The circuit shall also include one or more batteries with a capacity of 48 hours normal working at full load. The battery shall be arranged to be a continuously trickle charged from the electric mains.
(4) The call boxes shall be arranged to sound one or more sounders so as to ensure that all occupants of the floor shall be warned whenever any call box is actuated.
(5) The call boxes shall be so installed that they do not obstruct the exit ways and yet their location can easily be noticed from either direction. The base of the call box shall be at a height of 1.5m from the floor level.
(6) All buildings other than as indicated above shall, in addition to the manually operated electrical fire alarm system, be equipped with an automatic fire alarm system.
(7) Automatic detection system shall be installed in accordance with the relevant standard specifications. In buildings where automatic sprinkler system is provided, the automatic detection system may not be insisted upon unless decided otherwise by the Chief Fire Officer
Note: The installation of Fire Alarm Systems shall be carried out in conformity with the local fire regulations and rules, there under whenever they are in force and the provisions in local byelaws, if any. Several types of fire detectors are available in the market but the application of each type is
limited and has to be carefully considered in relation to the type of risk and the structural features of the building where they are to be installed.
12.24 Control Room.- There shall be a control room on the entrance floor of the building with communication system (suitable public-address system) to all floors and facilities for receiving the message from different floors. Details of all floor plans along with the details of fire fighting equipment and installation shall be maintained in the Control Room. The Control Room shall also have facility to detect the fire on any floor through indicator boards connecting fire detection and alarm system on all floors. The staff in charge of the Control Room shall be responsible for the maintenance of the various services and fire fighting equipment and installation. The Control Room shall be manned round the clock by trained fire fighting staff.
12.25 Fire drills and fire orders.- The guidelines for fire drill and evacuation etc. for highrise building may be seen in NBC 2016 part 4. All such buildings shall prepare the fire orders duly approved by the Chief Fire Officer.
A qualified fire officer and trained staff shall be appointed for the following buildings:
a) All high-rise buildings above 30m in height where covered area of one floor exceeds 1000 Sq.m except apartments / group housing;
b) All hotels, identified under classification 3 star and above category by Tourism Department and all hotels above 15m in height with 150 beds capacity or more without star category;
c) All hospital building of 15m and above or having number of beds exceeding100;
d) Underground shopping complex where covered area exceeds 1000Sq.m;
e) All high hazard industries; and
f) Any other risk which Chief Fire Officer considers necessary.
The lightening protection warning light (red) for high-rise buildings shall be provided in accordance with the relevant standard. The same shall be checked by electrical department.