(1) Air-conditioning As provided in these Rules. [See Chapter VI]
(2) Alternate Source of Electric Supply
(3) Boiler Room As provided in these Rules. [See Chapter VI]
(4) Electrical Services
As provided in these Rules. [See Chapter VI]
(5) Gas supply
(a) Town Gas/L.P. Gas Supply Pipes – Where gas pipes are run in buildings, the same shall be run in separate shafts exclusively for this purpose and these shall be on external walls, away from the staircases. There shall be no interconnection of this shaft with the rest of the floors.
(b) LPG distribution pipes shall always be below the false ceiling. The length of these pipes shall be as short as possible. In the case of kitchen cooking range area, apart from providing hood, covering the entire cooking range, the exhaust system should be designed to take care of 30cu.m per minute per sq. m of hood protected area. It should have grease filters using metallic grill to trip oil vapors escaping into the fume hood.
Note: For detailed information on gas pipe installations, reference may be made to Para.9 ‘Plumbing Services, Section 3 Gas Supply’, of National Building Code of India.
(c)For large/commercial kitchens all wiring in fume hoods shall be of fiberglass insulation. Thermal detectors shall be installed into fume hoods of large kitchens for hotels, hospitals and similar areas located in high rise
buildings. Arrangements shall be made for automatic tripping of the exhaust fan in case of fire.
(d) If LPG is used, the same shall be shut off. The voltage shall be of 24 V or 100 V DC operated with the external rectifier. The valve shall be of the hand re-set type and shall be located in an area segregated from cooking ranges. Valves shall be easily accessible. The hood shall have manual facility for steam or carbon dioxide gas injection, depending on duty condition; and Gas meters shall be housed in a suitably constructed metal cupboard located in a well-ventilated space, keeping in view the fact that LPG is heavier than air and town gas is lighter than air.
(6) Helipad
As provided in these Rules. [See Chapter VI]
(7) Staircase and Corridor Lighting As provided in these Rules. [See Chapter VI]
(a) If transformers are housed in the building below the ground level it shall be necessarily in the first basement in separate fire resistance room of 4 hours rating.
(b) Transformer shall be dry type and shall be kept in an enclosure with walls, doors and cut-outs having fire resistance rating of 4 hour.
(c)The room shall necessarily be at the periphery of the basement having separate and direct access from open area at ground floor through a fire escape staircase.
(d) The entrance to the room shall be provided with a steel door of 2 hours fire rating. A curb of a suitable height shall be provided at the entrance in order to prevent the flow of oil from ruptured, transformer into other parts of the basement.
(e) The switchgears shall be housed in a separate room separated from the transformer bays by a fire-resisting wall with fire resistance not less than 4 hours.
(f) The transformer shall be protected by an automatic foam sprinkler system. When housed at ground floor level it/they shall be cut-off from the other portion of premises by Fire Resisting Walls of 4 hours rating.
(g) A tank of RCC construction of adequate capacity shall be provided at lower basement level, to collect the oil from the catch pit in case of emergency. The pipe connecting the catch-pit to the tank shall be of non-combustible construction and shall be provided with a flame-arrester.
(h) The electric sub-station shall be located in a separate building in accordance to I.E. Rules 68(I) and 64(I) (a).
(i) If this is not possible due to site conditions, the sub-station shall be located on the ground floor.
(j) As far as possible sub-station shall not be installed in a basement, for such situations special provisions like mechanical ventilation, wherever required, cable ducting, cable trays, top/bottom entry of HV/LV cable,
hooks on Transformer(s) & HV panels, adequate fire detection and firefighting arrangement, adequate drainage, effective measures to prevent flooding etc. shall be provided.
(k) Adequate precautions shall also be taken for water proofing to prevent seepage of water.
(l) A ramp shall also be provided with a slope, not steeper than 1 in 7, for easy movement of equipment to and from sub-station.
(m) Fire regulations – The installations shall be carried out in conformity with the local regulations and rules there under wherever they are in force. At other places NBC guidelines shall be followed.
(9) Fire Safety / Disaster Management
Refer Chapter-VI [Fire Protection & Fire Safety Requirements of these Rules.
(10) Structural Safety
Refer Chapter-V [Provisions for Structural Safety] of these Rules.
(11) Sustainable Environment and Buildings
Refer Chapter-X-5 [Green Buildings] of these Rules.
(12) General
(a) Architectural elements such as louvers, pergolas, other sunshine materials should be free from FAR.
(b) Any architectural roof top structures would also be permitted out of FAR if not used for habitable or commercial purposes.
(c)Building elements such as sky bridges and landscape terraces which are meant for community purposes only shall be permitted free of FAR
(d) Services can be permitted on roofs with adequate screening for the same.
(e) Atrium/ Atria at any floor will be counted only once in the FAR. Atrium may be enclosed by light roofing or R.C.C.
(f) Scissor staircase would be permitted provided all travel distance and fire norms are adhered to.
(g) Stilts in high-rise will not be restricted to height of 2.4m as long as it is used for parking.
(h) Multilevel car parking with car lifts would be permitted with adequate fire safety.