(i) Corridor walls shall be effective in limiting the transfer of smoke and shall be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke.
(ii) The walls shall be 1 hour barrier fire resistance rated in buildings provided with full automatic sprinkler protection.
(iii)Sleeping Suites - The size limit on sleeping suites shall not exceed an area of 460 m2.
Exception: The area shall be permitted not to exceed 700 m2 when the following conditions are met:
Direct visual supervision is provided from a normally attended location within the suite, and,
The patient sleeping room is provided with a total coverage smoke detection system per NFPA 101 Sections 9.6.2.8 and 18.3.4
Non-Sleeping Suites – The size limit shall not exceed 930 m2.
(f) Doors
See section on Exit Corridors – Doors herein.
(g)Miscellaneous Openings
In other than smoke compartments containing patient bedrooms, miscellaneous openings, such as mail slots, pharmacy pass-through windows, laboratory pass-through windows, and cashier pass-through windows, shall be permitted to be installed in vision panels or doors without special protection, provided that both of the following criteria are met:
(1) The aggregate area of openings per room does not exceed 80 in.2 (0.05 m2).
(2) The openings are installed at or below half the distance from the floor to the room ceiling.
(h)Transfer Grilles
Transfer grilles are not permitted in walls or doors of suites, regardless of whether or not they are protected by fusible link-operated dampers.
Exception: Doors to toilet rooms, bathrooms, shower rooms, sink closets, and similar auxiliary spaces that do not contain flammable or combustible materials shall be permitted to have ventilating louvers or to be undercut.