28.1. The provision of the regulations are not intended to prevent the use of any material or method of design or construction not specifically prescribed by the regulations, provided any such alternative has been approved.
28.1.1. The provision of these regulations is also not intended to prevent the adoption for architectural planning and layout conceived as an integrated development scheme.
28.2. The authority may approve any such alternative provided it is found that the proposed alternative is satisfactory and conforms to the provisions of relevant parts regarding material, design, and construction and that material, method or work offered is, for the purpose intended, at least equivalent to that prescribed in the rules in quality, strength, compatibility, effectiveness, fire rating and resistance, durability and safety.
28.3 Tests: Whenever there is insufficient evidence of compliance with the provisions of the regulations of evidence that any material or method of design or construction does not conform to the requirements of the rules or in order to substantiate claims for alternative materials, design or methods of construction, the Authority may require tests sufficient in advance as proof of compliance. These tests shall be made by an approved agency at the expense of the owner.
7 (可.何.y.)----84
HER T, - , T , 3 3-, R0/ R-, T 30
28.3.1 Test method shall be as specified by the regulations for the materials or design or construction in question. If there are no appropriate test methods specified in the regulations, the Authority shall determine the test procedure. For methods of tests for building materials; reference may be made to relevant Indian standards as given in the National Building Code of India published by the Bureau of Indian Standards. The latest version of the National building Code of India shall be taken into account at the time of enforcement of these rules.
28.3.2 Copies of the results of all such tests shall be retained by the authority for a period of not less than two years after the acceptance of the alternative material.
29.0 BUILDING SERVICES
29.1. The planning, design and installation of electrical installations, air-conditioning and heating works shall be carried out in accordance with Part 8 - Building Services, Section 2- Electrical and allied Installations, Section 3 - Air Conditioning, heating and mechanical ventilation of National building Code of India, amended from time to time.
29.2. The planning design including the number of lifts, type of lifts, capacity of lifts depending on occupancy of building; population on each floor based on occupant load, height of building shall be in accordance with Section - 5 installation of Lifts and Escalators of National Building Code of India, amended from time to time. In existing buildings, in case of proposal for one additional floor, existing lift may not be raised to the additional floor.
29.2.1 Maintenance of Lift in working order: The lifts shall be maintained in working order.
30.0 WATER SUPPLY, DRAINAGE AND SANITARY REQUIREMENTS.
30.1. The planning, design, construction and installation of water supply, drainage and sanitation and gas supply systems shall be in accordance with the provisions of Part 9 - Plumbing Services - Section 1 Water Supply, Drainage and Sanitation, Section 2 – Gas supply of National Building Code of India as amended from time to time.
30.2. Requirements of water supply in building.
The total requirements of water supply shall be calculated based on the population as given in Table 20 below:
| Occupancy | Basis |
|---|---|
| Residential Building | 5 persons per tenement |
| Other Buildings | No. of persons on occupant load and area of floors given in Error! Reference source not found. |
30.2.1 The requirements of water supply for various occupancies shall be as given in Table 21 to Table 23 or as specified by the Authority from time to time.
| Sr. No. | Type of Occupancy | Consumption per head per day (in liters) |
| 1 | Residential: | |
| (a) in living units | 135 | |
| (b) Hotels with lodging accommodation (per bed) | 180 | |
R , , T , 3 3-, 2/ -, 3
| Sr. No. | Type of Occupancy | Consumption per head per day (in liters) |
| 2 | Educational: | |
| (a) Day Schools | 45 | |
| (b) Boarding Schools | 135 | |
| 3 | Institutional (Medical Hospitals): | |
| (a) No. of beds not exceeding 100 | 340 | |
| (b) No. of beds exceeding 100 | 450 | |
| (c) Medical quarters and hostels | 135 | |
| 4 | Assembly-Cinema theatres, auditorium etc. (per seat of accommodation) | 15 |
| 5 | Government and Semi-public business | 45 |
| 6 | Mercantile (Commercial): | |
| (a) Restaurants (per seat) | 70 | |
| (b) Other business buildings | 45 | |
| 7 | Industrial: | |
| (a) Factories where bathrooms are to be provided | 45 | |
| (b) Factories where no bath-rooms are required to be provided | 30 | |
| 8 | Storage (including warehousing) | 30 |
| 9 | Hazardous | 30 |
| 10 | Intermediate / Stations (excluding mail and express stops) | 45 (25)* |
| 11 | Junction Stations | 70 (45)* |
| 12 | Terminal / Stations | 45 |
| 13 | International and domestic Airports | 70 |
(i) * The value in parenthesis is for stations where bathing facilities are not provided.
(ii) The number of persons for Sr. No. (10) to (13) shall be determined by the average number of passengers handled by the station daily. Due consideration may be given to the staff and workers likely to use the facilities
| Sr. No. | Classification of building | Storage capacity |
|---|---|---|
| (1) | (2) | (3) |
| 1 | Tenements having common convenience | 900 liters per W.C. seat |
| 2 | Residential premises other than tenements having common convenience | 270 liters for one W.C. seat and 180 liters for each additional seat in the same flat |
| 3 | Factories and Workshops | 900 liters per W.C. seat and 180 liters per urinal seat |
| 4 | Cinemas, public assembly halls, etc. | 900 liters per W.C. seat and 350 liters per urinal seat |
(可..-843
HER T, - , T , 3 3-, R0/ R-, T 30
| Sr. No. | No. of Floors | Storage Capacity | Remarks |
| (1) | (2) | (3) | (4) |
| For premises occupied as tenements with common conveniences | |||
| 1 | Floor (Ground) | NIL | Provided no down take fittings are installed |
| 2 | Floors 1, 2, 3, 4, 5 and upper floors | 500* liters per tenement | |
| For premises occupied as Flats or blocks | |||
| 1 | Floor (Ground) | NIL | Provided no down take fittings are installed |
| 2 | Floors 1, 2, 3, 4, 5 and upper floors | 500* liters | |
Subject to provisions of water supply and drainage rules.
NOTE 1: If the premises are situated at a place higher than the road level in the front of the premises, storage at ground level shall be provided on the same line as on floor 1.
NOTE 2: The above storage may be permitted to be installed provided that the total domestic storage calculated on the above basis is not less than the storage calculation on the number of down take fittings according to the scales given below:
Down take taps - 70 liters each
Bathtubs - 200 liters each