This Code (Part 8/Section 1) covers requirements and methods for lighting and natural ventilation of buildings.
Illumination levels for different tasks are recommended to be achieved either by daylighting or artificial lighting or a combination of both. This Section, read together with Part 8 ‘Building Services, Section 2 Electrical and Allied Installations’ of the Code, adequately covers the illumination levels required and methods of achieving the same.
Ventilation requirements to maintain air quality and control body odours in terms of air changes per hour and to ensure thermal comfort and heat balance of body are laid for different occupancies and the methods of achieving the same by natural means are covered in this Section. The provisions on mechanical ventilation are covered in Part 8 ‘Building Services, Section 3 Air conditioning, Heating and Mechanical Ventilation’ of the Code.
Climatic factors which normally help in deciding the orientation of the buildings to get desirable benefits of lighting and natural ventilation inside the buildings are also covered in this Section.
This Section was first published in 1970. The first revision of the Section was brought out in 1983. In the second revision, some provisions were updated based on the information given in the SP 41:1987 'Handbook on functional requirements of buildings (other than industrial buildings)'; other major changes in the last revision included rationalization of definitions and inclusion of definitions for some more terms; inclusion of climatic classification map of India based on a new criteria; updating of data on total solar radiations incident on various surfaces of buildings for summer and winter seasons; inclusion of design guidelines for natural ventilation; reference to Part 8 'Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation' of the Code for guidelines on mechanical ventilation, was made, where these provisions were covered exhaustively; inclusion of rationalized method for estimation of desired capacity of ceiling fans and their optimum height above the floor for rooms of different sizes; incorporation of design sky illuminance values for different climatic zones of India, etc. Energy efficiency was another important aspect which was taken care of in the last revision of the Code. Accordingly, the relevant requirements for energy efficient system for lighting and natural ventilation were duly included in the concerned provisions under the Section.
As a result of experience gained on implementation of 2005 version of the Code and feedback data received, a need was felt to revise this Section. This draft revision has, therefore, been formulated to take care of these. The significant changes incorporated in this revision are:
a) Calculation for solar load has been elaborated, and a detailed 'Method of Calculating Solar Load on Vertical Surfaces in Different Orientation' has been added in Annex A, supporting the relevant provisions.
b) Detailed provisions on sky component calculation procedure have been included along with examples in Annex B supporting the relevant clauses.
c) Reference to SP 41 : 1987 for obtaining coefficient utilization for determination of luminous flux has been included.
d) Provisions relating to efficient artificial light source and luminaires have been updated.
e) Modern lighting techniques such as LED and induction light have been included vis-à-vis their energy consumption.
f) Provisions relating to photocontrols for artificial lights have been updated.
g) Definitions and enabling provision for lighting shelves and light pipes have been included.
h) Provisions related to thermal comfort clause have been elaborated including therein indices such as effective temperature, adaptive thermal comfort along with elaborations on tropical summer index.
j) Design guidelines for natural ventilation have been elaborated with illustrations.
k) Provisions related to determination of rate of ventilation, particularly on combined effect of wind and thermal actions, have been elaborated.
m) Provision on colour rendering has been included in line with that in SP 72 : 2010 ‘National Lighting Code 2010’.
n) Various other existing provisions have been updated based on the latest technical developments in the field.
The provisions of this Section are without prejudice to the various acts, rules and regulations including the Factories Act, 1948 and rules and regulations framed thereunder.
The information contained in this Section is largely based on the following Indian Standards/Special Publications:
IS 2440 : 1975 Guide for daylighting of buildings (second revision)
IS 3103 : 1975 Code of practice for industrial ventilation (first revision)
IS 3362 : 1977 Code of practice for natural ventilation of residential buildings (first revision)
IS 3646 (Part 1): 1992 Code of practice for interior illumination: Part 1 General requirements and recommendations for working interiors (first revision)
IS 7662 (Part 1) : 1974 Recommendations for orientation of buildings : Part 1 Non-industrial buildings
IS 11907 : 1986 Recommendations for calculation of solar radiation on buildings
SP 32 : 1986 Handbook on functional requirements of industrial buildings (lighting and ventilation)
SP 41 : 1987 Handbook on functional requirements of buildings other than industrial buildings
Provisions given in National Lighting Code, ‘SP 72 : 2010’ may also be referred.
The following publication has also been referred to in the formulation of this Section:
Report on energy conservation in buildings, submitted to Department of Power, Ministry of Energy by CSIR-Central Building Research Institute, Roorkee.
All standards, whether given herein above or cross-referred to in the main text of this Section, are subject to revision. The parties to agreement based on this Section are encouraged to investigate the possibility of applying the most recent editions of the standards.
1Scope
1.1 This Code (Part 8/Section 1) covers requirements and methods for lighting and natural ventilation of buildings.
1.2 The provisions in respect of lighting and ventilation in sustainable buildings are covered in Part 11 ‘Approach to Sustainability’ of the Code which shall be used in conjunction with this Section.
1.3 For all buildings and facilities open to and used by the public, including all forms of public housing by the government/civic bodies and private developers, adequate lighting and ventilation for barrier free access and movement within and around buildings by elderly and persons with disabilities shall be ensured in accordance with 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
2.2Ventilation
2.2.1 Air Change per Hour — The amount of air leakage into or out of a building or room in terms of the number of times the building volume or room volume exchanged.
2.2.2 Axial Flow Fan — A fan having a casing in which the air enters and leaves the impeller in a direction substantially parallel to its axis.
2.2.3 Centrifugal Fan — A fan in which the air leaves the impeller in a direction substantially at right angles to its axis.
2.2.4 Contaminants — Dusts, fumes, gases, mists, vapours and such other substances present in air that are likely to be injurious or offensive to the occupants.
2.2.5 Dilution Ventilation — Supply of outside air to reduce the airborne concentration of contaminants in the building.
2.2.6 Dry Bulb Temperature — The temperature of the air, read on a thermometer, taken in such a way so as to avoid errors due to radiation.
2.2.7 Effective Temperature (ET) — An arbitrary index which combines into a single value the effect of temperature, humidity and air movement on the sensation of warmth or cold felt by the human body and its numerical value is that of the temperature of still saturated air which would induce an identical sensation.
2.2.8 Exhaust of Air — Removal of air from a building or a room and its disposal outside by means of a mechanical device, such as a fan.
2.2.9 Fresh Air or Outside Air — Air of that quality, which meets the criteria of Table 1 and in addition shall be such that the concentration of any contaminant in the air is limited to within one-tenth the threshold limit value (TLV) of that contaminant.
1 Where it is reasonably believed that the air of quality is not expected as indicated above, sampling and analysis shall be carried out by a competent authority having jurisdiction and if the outside air of the specified quality is not available, filtration and other treatment devices shall be used to bring its quality to or above the levels mentioned in Table 1.
Odour is to be essentially unobjectionable.
2 The above list of contaminants is not exhaustive and available special literature may be referred for data on other contaminants.
Table 1Maximum Allowable Contaminant Concentrations for Ventilation Air (Clause 2.2.9)
Sl No.
Contaminants
2Terminology
For the purpose of this Section, the definitions given below shall apply.
2.1 Lighting
2.1.1 Altitude ( θ ) — The angular distance of any point of celestial sphere, measured from the horizon, on the great circle passing through the body and the zenith (see Fig. 1).
2.1.2 Azimuth (Φ) — The angle measured between meridians passing through the north point and the point in question (point C in Fig. 1).
2.1.3 Brightness Ratio or Contrast — The variations or contrast in brightness of the details of a visual task, such as white print on blackboard.
2.1.4 Candela (cd) — The SI unit of luminous intensity.
Candela = 1 lumen per steradian
2.1.5 Central Field — The area of circle around the point of fixation and its diameter, subtending an angle of about 2° at the eye. Objects within this area are most critically seen in both their details and colour.
2.1.6 Clear Design Sky — The distribution of luminance of such a sky is non-uniform; the horizon is brighter than the zenith, and when Lz is the brightness at zenith, the brightness at an altitude ( θ ) in the region away from the sun, is given by the expression:
L
4Lighting
4.1 Principles of Lighting
4.1.1 Aims of Good Lighting
Good lighting is necessary for all buildings and has three primary aims. The first aim is to promote work and other activities carried out within the building; the second aim is to promote the safety of the people using the building; and the third aim is to create, in conjunction with the structure and decoration, a pleasing environment conducive to interest of the occupants and a sense of their well-being.
4.1.1.1 Realization of these aims involves the following:
a) Careful planning of the brightness and colour pattern within both the working areas and the surroundings so that attention is drawn naturally to the important areas, detail is seen quickly and accurately and the room is free from any sense of gloom or monotony (see 4.1.4);
b) Using directional lighting, where appropriate, to assist perception of task detail and to give good modeling;
c) Controlling direct and reflected glare from light sources to eliminate visual discomfort;
d) In artificial lighting installations, minimizing flicker from certain types of lamps and paying attention to the colour rendering properties of the light;
e) Correlating lighting throughout the building to prevent excessive differences between adjacent areas so as to reduce the risk of accidents; and
f) Installing emergency lighting systems, where necessary.
4.1.2 Planning the Brightness Pattern
The brightness pattern seen within an interior may be considered as composed of three main parts — the task itself, immediate background of the task and the general surroundings of walls, ceiling, floor, equipment and furnishings.
4.1.2.1 In occupations where the visual demands are small, the levels of illumination derived from a criterion of visual performance alone may be too low to satisfy the other requirements. For such situations, therefore, illuminance recommendations are based on standards of welfare, safety and amenity judged appropriate to the occupations; they are also sufficient to give these tasks brightness which ensured that the visual performance exceeds the specified minimum. Unless there are special circumstances associated with the occupation, it is recommended that the illuminance of all working areas within a building should generally be 150 lux.
4.1.2.2 Where work takes place over the whole utilizable area of room, the illumination over that area should be reasonably uniform and it is recommended that the uniformity ratio (minimum illuminance divided by average illuminance levels) should be not less than 0.7 for the working area.
3Orientation of Building
3.1 The chief aim of orientation of buildings is to provide physically and psychologically comfortable living inside the building by creating conditions which suitably and successfully ward off the undesirable effects of severe weather to a considerable extent by judicious use of the recommendations and knowledge of climatic factors.
3.2 Basic Zones
3.2.1 For the purpose of design of buildings, the country may be divided into the major climatic zones as given in Table 2, which also gives the basis of this classification.
Table 2Classification of Climate (Clause 3.2.1)
Sl No.
Climatic Zone
Mean Monthly Maximum Temperature °C
Mean Monthly Relative Humidity Percent
(1)
(2)
(3)
(4)
i)
Hot-dry
Above 30
Below 55
ii)
Warm-humid
Above 30
Above 55
Above 25
Above 75
iii)
Temperate
25-30
Below 75
iv)
Cold
Below 25
All values
v)
Composite
see 3.2.2
The climatic classification map of India is shown in Fig. 2.
3.2.2 Each climatic zone does not have same climate for the whole year; it has a particular season for more than six months and may experience other seasons for the remaining period. A climatic zone that does not have any season for more than six months may be called as composite zone.
3.3 Climatic Factors
From the point of view of lighting and natural ventilation, the following climatic factors influence the optimum orientation of the building:
a) Solar radiation and temperature,
b) Relative humidity, and
c) Prevailing winds.
Based upon Survey of India Political map printed in 2002.
The interstate boundaries between Arunachal Pradesh, Assam and Meghalaya shown on this map are as interpreted from the North-Eastern Areas (Reorganization) Act, 1971, but have yet to be verified.
4.4Energy Conservation in Lighting
4.4.1 A substantial portion of the energy consumed on lighting may be saved by utilization of daylight and rational design of supplementary artificial lights.
4.4.2 Daytime use of artificial lights may be minimised by proper design of windows for adequate daylight indoors. Daylighting design should be according to 4.2.
4.4.3 Fenestration expressed as percentage of floor area required for satisfactory visual performance of a few tasks for different separation to height (S/H) ratio of external obstructions such as opposite buildings may be obtained from the design nomogram (see Fig. 4). The obstructions at a distance of three times their height or more (S/H >3) from a window façade are not significant and a window facing such an obstruction may be regarded as a case of unobstructed window.
4.4.3.1 The nomogram consists of horizontal lines indicating fenestration percentage of floor area and vertical lines indicating the separation to height ratio of external obstructions such as opposite buildings. Any vertical line for separation to height ratio other than already shown in the nomogram (1.0, 2.0 and 3.0) may be drawn by designer, if required. For cases where there is no obstruction, the ordinate corresponding to the value 3.0 may be used. The value of percentage
fenestration and separation to height ratio are marked on left hand ordinate and abscissa, respectively. The illumination levels are marked on the right hand ordinate. The values given within brackets are the illumination levels on the work plane at center and rear of the room. The wattage of fluorescent tubes required per m² of the floor area for different illumination levels is shown on each curve.
4.4.3.2 Following assumptions have been made in the construction of the nomogram:
a) An average interior finish with ceiling white, walls off white and floor grey has been assumed.
b) Ceiling height of 3 m, room depths up to 10 m and floor area between 30 m² and 50 m² have been assumed. For floor area beyond 50 m² and less than 30 m², the values of percent fenestration as well as wattage per m² should be multiplied by a factor of 0.85 and 1.15, respectively.
c) It is assumed that windows are of metallic sashes with louvers of width up to 600 mm or a Chhajja (balcony projection) at ceiling level of width up to 2.0 m. For wooden sashes, the window area should be increased by a factor of about 1.1.
d) Luminaires emanating more light in the downward direction than upward direction (such as reflectors with or without diffusing plastics) and mounted at a height of 1.5 m to 2.0 m above the work plane have been considered.
5Ventilation
5.1 General
Ventilation of buildings is required to supply fresh air for respiration of occupants, to dilute inside air to prevent vitiation by body odours and to remove any products of combustion or other contaminants in air and to provide such thermal environments as will assist in the maintenance of heat balance of the body in order to prevent discomfort and injury to health of the occupants.
5.2Design Considerations
5.2.1 Respiration
Supply of fresh air to provide oxygen for the human body for elimination of waste products and to maintain carbon dioxide concentration in the air within safe limits rarely calls for special attention as enough outside air for this purpose normally enters the areas of occupancy through crevices and other openings.
5.2.1.1 In normal habitable rooms devoid of smoke generating source, the content of carbon dioxide in air rarely exceeds 0.5 percent to 1 percent and is, therefore, incapable of producing any ill effect. The amount of air required to keep the concentration down to 1 percent is very small. The change in oxygen content is also too small under normal conditions to have any ill effects; the oxygen content may vary quite appreciably without noticeable effect, if the carbon dioxide concentration is unchanged.
5.2.2 Vitiation by Body Odours
Where no products of combustion or other
contaminants are to be removed from air, the amount of fresh air required for dilution of inside air to prevent vitiation of air by body odours, depends on the air space available per person and the degree of physical activity; the amount of air decreases as the air space available per person increases, and it may vary from 20 m³ to 30 m³ per person per hour. In rooms occupied by only a small number of persons such an air change will automatically be attained in cool weather by normal leakage around windows and other openings and this may easily be secured in warm weather by keeping the openings open.
No standards have been laid down under Factories Act, 1948 as regards the amount of fresh air required per worker or the number of air changes per hour. Section 16 of the Factories Act, 1948 relating to overcrowding requires that at least 14m³ to 16m³ of space shall be provided for every worker and for the purpose of that section no account shall be taken of any space in a work room which is more than 4.25m above the floor level.
NOTE — Vitiation of the atmosphere can also occur in factories by odours given off due to contaminants of the product itself, say for example, from tobacco processing in a ‘Beedi’ factory. Here the ventilation will have to be augmented to keep odours within unobjectionable levels.
5.2.2.1 Recommended values for air changes
The standards of general ventilation are recommended/ based on maintenance of required oxygen, carbon dioxide and other air quality levels and for the control of body odours when no products of combustion or other contaminants are present in the air; the values of air changes should be as follows:
4.3Artificial Lighting
4.3.1 Artificial lighting may have to be provided,
a) where the recommended illumination levels have to be obtained by artificial lighting only;
b) to supplement daylighting when the level of illumination falls below the recommended value; and
c) where visual task may demand a higher level of illumination.
4.3.2 Artificial Lighting Design for Interiors
For general lighting purposes, the recommended practice is to design for a level of illumination on the working plane on the basis of the recommended levels for visual tasks given in Table 4 by a method called 'Lumen method'. In order to make the necessary detailed calculations concerning the type and quantity of lighting equipment necessary, advance information on the surface reflectances of walls, ceilings and floors is required. Similarly, calculations concerning the brightness ratio in the interior call for details of the interior decoration and furnishing. Stepwise guidance regarding designing the interior lighting systems for a
28
building using the ‘Lumen method’ is given in 4.3.2.1 to 4.3.2.4.
4.3.2.1 Determination of the illumination level
Recommended value of illumination shall be taken from Table 4, depending upon the type of work to be carried out in the location in question and the visual tasks involved.
4.3.2.2 Selection of the light sources and luminaires
The selection of light sources and luminaires depends on the choice of lighting system, namely, general lighting, directional lighting and localized or local lighting.
4.3.2.3 Determination of the luminous flux
a) The luminous flux (F) reaching the working plane depends upon the following:
Lumen output of the lamps,
Type of luminaire,
Proportion of the room (room index) (kr),
Reflectance of internal surfaces of the room,
Depreciation in the lumen output of the lamps after burning their rated life, and
Depreciation due to dirt collection on luminaires and room surface.
b) Coefficient of utilization or utilization factor
5.6Determining Rate of Ventilation
5.6.1 Natural Ventilation
This is difficult to measure as it varies from time to
time. The amount of outside air through windows and other openings depends on the direction and velocity of wind outside (wind action) and/or convection effects arising from temperature or vapour pressure differences (or both) between inside and outside of the building (stack effect).
5.6.1.1 Wind action
For determining the rate of ventilation based on wind action the wind may be assumed to come from any direction within 45° of the direction of prevailing wind. Ventilation due to external wind is given by the following formula:
Q w = K. A. V
where
Qw = rate of air flow, in m³/h;
K = coefficient of effectiveness, which may be taken as 0.6 for wind perpendicular to openings and 0.3 for wind at an angle less than 45° to the openings;
A = free area of inlet openings, in m²; and
V = wind speed, in m / h
NOTE — For wind data at a place, the local Meteorological Department may be consulted.
5.6.1.2 Stack effect (thermal action)
Ventilation due to convection effects arising from temperature difference between inside and outside is given by:
Q T = 7. 0 A √ h (t r - t o)
where
Q T = rate of air flow, in m ³ / h;
5.7Energy Conservation in Ventilation System
5.7.1 Maximum possible use should be made of wind induced natural ventilation. This may be accomplished by following the design guidelines given in 5.7.1.1.
5.7.1.1 Adequate number of circulating fans should be installed to serve all interior working areas during summer months in the hot dry and warm humid regions to provide necessary air movement at times when ventilation due to wind action alone does not afford sufficient relief.
5.7.1.1.1 The capacity of a ceiling fan to meet the requirement of a room with the longer dimension D metre should be about 55Dm³/min.
5.7.1.1.2 The height of fan blades above the floor should be (3H + W)/4, where H is the height of the room, and W is the height of work plane.
5.7.1.1.3 The minimum distance between fan blades and the ceiling should be about 0.3 m.
5.7.2 Electronic regulators should be used instead of resistance type regulators for controlling the speed of fans.
5.7.3 When actual ventilated zone does not cover the entire room area, then optimum size of ceiling fan should be chosen based on the actual usable area of room, rather than the total floor area of the room. Thus smaller size of fan can be employed and energy saving could be achieved.
5.7.4 Power consumption by larger fans is obviously higher, but their power consumption per square metre of floor area is less and service value higher. Evidently, improper use of fans irrespective of the rooms' dimensions is likely to result in higher power consumption. From the point of view of energy consumption, the number of fans and the optimum sizes for rooms of different dimensions are given in Table 13.
Table 13Optimum Size/Number of Fans for Rooms of Different Sizes (Clause 5.7.4)
Sl No.
Room Width m
Optimum Size, mm/Number of Fans for Room Length
4 m(3)
5 m(4)
6 m(5)
7 m(6)
8 m(7)
9 m(8)
10 m(9)
11 m(10)
12 m(11)
14 m(12)
16 m(13)
i)
3
1 200/1
Annex B(Clauses 4.2.5, 4.2.5.2, 4.2.5.4 and 4.2.6.1) SKY COMPONENT TABLES B-1 Description of Tables
B-1.1 The three sky component tables are as given below:
a) Table 15 — Percentage sky components on the horizontal plane due to a vertical rectangular opening for the clear design sky.
b) Table 16 — Percentage sky components on the vertical plane perpendicular to a vertical rectangular opening for the clear design sky.
c) Table 17 — Percentage sky components on the vertical plane parallel to a vertical rectangular opening for the clear design sky.
B-1.2 All the tables are for an unglazed opening illuminated by the clear design sky.
B-1.3 The values tabulated are the components at a point P distant from the opening on a line perpendicular to the plane of the opening through one of its lower corners, and l and h are the width and height respectively of the rectangular opening (see Fig. 13).
B-1.4 Sky component for different h / d and l / d values are tabulated, that is, for windows of different size and for different distances of the point P from the window.
B-1.5 By suitable combination of the values obtained from the three tables, for a given point for a given window, the sky component in any plane passing through the point may be obtained.
B-1.6 Method of Using the Tables
B-1.6.1 Method of using the Tables to get the sky
component at given point is explained with help of the following example.
Annual Average (Arithmetic Mean)
Short Term Level (Not to Exceed More than Once a Year)
Averaging Period
(1)
(2)
µ g/m³(3)
µ g/m³(4)
h(2)
i)
Suspended particulates
60
150
24
ii)
Sulphur oxides
80
400
24
iii)
Carbon monoxide
20 000
30 000
8
iv)
Photochemical oxidant
100
500
1
v)
Hydrocarbons (not including methanes)
1 800
4 000
3
vi)
Nitrogen oxide
200
500
24
2.2.10 General Ventilation — Ventilation, either natural or mechanical or both, so as to improve the general environment of the building, as opposed to local exhaust ventilation for contamination control.
2.2.11 Globe Temperature — The temperature measured by a thermometer whose bulb is enclosed in a matt black painted thin copper globe of 150 mm diameter. It combines the influence of air temperature and thermal radiations received or emitted by the bounding surfaces.
2.2.12 Humidification — The process whereby the absolute humidity of the air in a building is maintained at a higher level than that of outside air or at a level higher than that which would prevail naturally.
2.2.13 Humidity, Absolute — The mass of water vapour per unit volume.
2.2.14 Humidity, Relative — The ratio of the partial pressure or density of the water vapour in the air to the saturated pressure or density, respectively of water vapour at the same temperature.
2.2.15 Local Exhaust Ventilation — Ventilation effected by exhaust of air through an exhaust appliance, such as a hood with or without fan located as closely as possible to the point at which contaminants are released, so as to capture effectively the contaminants and convey them through ducts to a safe point of discharge.
2.2.16 Make-Up Air — Outside air supplied into a building to replace the indoor air.
2.2.17 Mechanical Ventilation — Supply of outside air either by positive ventilation or by infiltration by reduction of pressure inside due to exhaust of air, or by a combination of positive ventilation and exhaust of air.
2.2.18 Natural Ventilation — Supply of outside air into a building through window or other openings due to wind outside and convection effects arising from temperature or vapour pressure differences (or both) between inside and outside of the building.
2.2.19 Positive Ventilation — The supply of outside air by means of a mechanical device, such as a fan.
2.2.20 Propeller Fan — A fan in which the air leaves the impeller in a direction substantially parallel to its axis designed to operate normally under free inlet and outlet conditions.
2.2.21 Spray-Head System — A system of atomizing water so as to introduce free moisture directly into a building.
2.2.22 Stack Effect — Convection effect arising from temperature or vapour pressure difference (or both) between outside and inside of the room and the difference of height between the outlet and inlet openings.
2.2.23 Tropical Summer Index (TSI) — The temperature of calm air at 50 percent relative humidity which imparts the same thermal sensation as the given environment.
2.2.24 Threshold Limit Value (TLV) — Refers to airborne concentration of contaminants currently accepted by the American Conference of Governmental Industrial Hygienists and represents conditions under which it is believed that nearly all occupants may be repeatedly exposed, day after day, without adverse effect.
2.2.25 Velocity, Capture — Air velocity at any point in front of the exhaust hood necessary to overcome opposing air currents and to capture the contaminants in air at that point by causing the air to flow into the exhaust hood.
2.2.26 Ventilation — Supply of outside air into, or the removal of inside air from an enclosed space.
2.2.27 Wet Bulb Temperature — The steady temperature finally given by a thermometer having its bulb covered with gauze or muslin moistened with distilled water and placed in an air stream of not less than 4.5 m/s.
θ
=
Lzsecθ(for15∘<
θ≤
90∘)
Lθ=Lzsec15∘(for0∘≤θ≤15∘)=3.8637Lz
2.1.7 Colour Rendering Index (CRI) — Measure of the degree to which the psychophysical colour of an
FIG. 1 ALTITUDE AND AZIMUTH OF A CELESTIAL BODY
object illuminated by the test illuminant conforms to that of the same object illuminated by the reference illuminant, suitable allowance having been made for the state of chromatic adaptation.
2.1.8 Correlated Colour Temperature (CCT) (K) — The temperature of the Planckian radiator whose perceived colour most closely resembles that of a given stimulus at the same brightness and under specified viewing conditions.
2.1.9 Daylight Area — The superficial area on the working plane illuminated to not less than a specified daylight factor, that is, the area within the relevant contour.
2.1.10 Daylight Factor — The measure of total daylight illuminance at a point on a given plane expressed as the ratio (or percentage) which the illuminance at the point on the given plane bears to the simultaneous illuminance on a horizontal plane due to clear design sky at an exterior point open to the whole sky vault, direct sunlight being excluded.
2.1.11 Daylight Penetration — The maximum distance to which a given daylight factor contour penetrates into a room.
2.1.12 Direct Solar Illuminance — The illuminance from the sun without taking into account the light from the sky.
2.1.13 External Reflected Component (ERC) — The ratio (or percentage) of that part of the daylight illuminance at a point on a given plane which is received by direct reflection from external surfaces as compared to the simultaneous exterior illuminance on a horizontal plane from the entire hemisphere of an unobstructed clear design sky.
2.1.14 Glare — A condition of vision in which there is discomfort or a reduction in the ability to see significant objects or both due to an unsuitable distribution or range of luminance or due to extreme contrasts in space and time.
2.1.15 Illuminance — At a point on a surface, the ratio of the luminous flux incident on an infinitesimal element of the surface containing the point under consideration to the area of the element.
NOTE — The unit of illuminance (the measurement of illumination) is lux which is 1 lumen per m².
2.1.16 Internal Reflected Component (IRC) — The ratio (or percentage) of that part of the daylight illuminance at a point in a given plane which is received by direct reflection or inter-reflection from the internal surfaces as compared to the simultaneous exterior illuminance on a horizontal plane due to the entire hemisphere of an unobstructed clear design sky.
2.1.17 Light Output Ratio (LOR) or Efficiency ( η ) — The ratio of the luminous flux emitted from the luminaire to that emitted from the lamp(s) (nominal luminous flux). It is expressed in percent.
2.1.18 Light Pipe — A conduit made of a highly reflective material, which is capable of channeling light from one end to the other through successive internal reflections. Such a pipe may be flexible or rigid.
2.1.19 Light Shelf — A daylighting system based on sun path geometry used to bounce the light off a ceiling, project it deeper into a space, distribute it from above, and diffuse it to produce a uniform light level below.
2.1.20 Lumen (lm) — SI unit of luminous flux. The luminous flux emitted within unit solid angle (one steradian) by a point source having a uniform intensity of one candela.
2.1.21 Luminance (At a point of a Surface in a Given Direction) (Brightness) — The quotient of the luminous intensity in the given direction of an infinitesimal element of the surface containing the point under consideration by the orthogonally projected area of the element on a plane perpendicular to the given direction. The unit is candela per square metre (cd/m²).
2.1.22 Luminous Flux ( φ ) — The quantity characteristic of radiant flux which expresses its capacity to produce visual sensation evaluated according to the values of relative luminous efficiency for the light adapted eye:
a) Effective Luminous Flux (φn) — Total luminous flux which reaches the working plane.
b) Nominal Luminous Flux ( φo ) — Total luminous flux of the light sources in the interior.
2.1.23 Maintenance Factor (d) — The ratio of the average illuminance on the working plane after a certain period of use of a lighting installation to the average illuminance obtained under the same conditions for a new installation.
2.1.24 Meridian — It is the great circle passing through the zenith and nadir for a given point of observation.
2.1.25 North and South Points — The point in the respective directions where the meridian cuts the horizon.
2.1.26 Orientation of Buildings — In the case of non-square buildings, orientation refers to the direction of the normal to the long axis. For example, if the length of the building is east-west, its orientation is north-south.
2.1.27 Peripheral Field — It is the rest of the visual field which enables the observer to be aware of the spatial framework surrounding the object seen.
NOTE — A central part of the peripheral field, subtending an angle of about 30° on either side of the point of fixation, is chiefly involved in the perception of glare.
2.1.28 Reflected Glare — The variety of ill effects on visual efficiency and comfort produced by unwanted reflections in and around the task area.
2.1.29 Reflection Factor (Reflectance) — The ratio of the luminous flux reflected by a body (with or without diffusion) to the flux it receives. Some symbols used for reflection factor are:
rc = reflection factor of ceiling.
rw = reflection factor of parts of the wall between the working surface and the luminaires.
rf = reflection factor of floor.
2.1.30 Reveal — The side of an opening for a window.
2.1.31 Room Index (kr) — An index relating to the shape of a rectangular interior, according to the formula:
kr=(L+W)HmL.W
where L and W are the length and width respectively of the interior, and Hm is the mounting height, that is, height of the fittings above the working plane.
NOTES
1 For rooms where the length exceeds 5 times the width, L shall be taken as L = 5W.
2 If the reflection factor of the upper stretch of the walls is less than half the reflection factor of the ceiling, for indirect or for the greater part of indirect lighting, the value Hm is measured between the ceiling and the working plane.
6
2.1.32 Sky Component (SC) — The ratio (or percentage) of that part of the daylight illuminance at a point on a given plane which is received directly from the sky as compared to the simultaneous exterior illuminance on a horizontal plane from the entire hemisphere of an unobstructed clear design sky.
2.1.33 Solar Load — The amount of heat received into a building due to solar radiation which is affected by orientation, materials of construction and reflection of external finishes and colour.
2.1.34 Utilization Factor (Coefficient of Utilization) ( µ ) — The ratio of the total luminous flux which reaches the working plane (effective luminous flux, φn ) to the total luminous flux of the light sources in the interior (nominal luminous flux, φo ).
2.1.35 Visual Field — The visual field in the binocular which includes an area approximately 120° vertically and 160° horizontally centering on the point to which the eyes are directed. The line joining the point of fixation and the centre of the pupil of each eye is called its primary line of sight.
2.1.36 Working Plane — A horizontal plane at a level at which work will normally be done (see 4.1.4.3 and 4.1.4.4).
4.1.2.3 When the task brightness appropriate to an occupation has been determined, the brightness of the other parts of the room should be planned to give a proper emphasis to visual comfort and interest.
A general guide for the brightness relationship within the normal field of vision should be as follows:
a) For high task brightness Maximum (above 100cd / m²):
Between the visual task and 3:1 the adjacent areas like table tops
Between the visual task and 10:1 the remote areas of the room
b) For low and medium task brightness (below 100 cd/m² ): The task should be brighter than both the background and the surroundings; the lower the task brightness, the less critical is the relationship.
4.1.2.4 In case of all buildings and facilities open to and used by the public including all forms of public housing by the government/civic bodies and private developers, the requirements for visual contrast as given in 13 and Annex B of Part 3 ‘Development Control and Rules and General Building Requirements’ of the Code shall also be complied with for ensuring visual comfort for elders and persons with disabilities.
4.1.3 Glare
Excessive contrast or abrupt and large changes in
brightness produce the effect of glare. When glare is present, the efficiency of vision is reduced and small details or subtle changes in scene cannot be perceived. It may be,
a) direct glare due to light sources within the field of vision;
b) reflected glare due to reflections from light sources or surfaces of excessive brightness; and
c) veiling glare where the peripheral field is comparatively very bright.
4.1.3.1 An example of glare sources in daylighting is the view of the bright sky through a window or skylight, especially when the surrounding wall or ceiling is comparatively dark or weakly illuminated. Glare can be minimised in this case either by shielding the open sky from direct sight by louvers, external hoods or deep reveals, curtains or other shading devices or by cross lighting the surroundings to a comparable level. A gradual transition of brightness from one portion to the other within the field of vision always avoids or minimises the discomfort from glare.
For electric lamps the minimum shielding angles for lamp luminance shall not be less than the values given in the table below:
Lamp Luminance kcd/m2
Minimum Shielding Angle Degree
1 to 20
10
20 to 50
15
50 to 500
20
≥ 500
30
The above mentioned shielding angle should not be applied to luminaires that do not appear in the field of view of a worker during usual work and/or do not give the worker any noticeable disability glare.
Table 4 also gives recommended value of quality class of direct glare limitation for different tasks. These are numbers assigned to qualitative limits of direct glare: high, medium and low quality as 1, 2 and 3, respectively. For more details reference may be made to good practice [8–1(2)].
4.1.4 Recommended Values of Illuminance
Table 4 gives recommended values of illuminance commensurate with the general standards of lighting described in this Section and related to many occupations and buildings. These are valid under most of the conditions whether the illumination is by daylighting, artificial lighting or a combination of the two. The great variety of visual tasks makes it impossible to list them all and those given should be regarded as representing types of task.
4.1.4.1 The different locations and tasks are grouped within the following four sections:
a) Industrial buildings and process;
b) Offices, schools and public buildings;
c) Surgeries and hospitals; and
d) Hotels, restaurants, shops and homes.
4.1.4.2 The illumination levels recommended in Table 4 are those to be maintained at all time on the task. As circumstances may be significantly different for different interiors used for the same application or for different conditions for the same kind of activity, a range of illuminances is recommended for each type of interior or activity instead of a single value of illuminance. Each range consists of three successive steps of the recommended scale of illuminances. They represent good practice and should be regarded as giving order of illumination commonly required rather than as having some absolute significance. For working interiors the middle value of each range represents the recommended service illuminance that would be used unless one or more of the factors mentioned below apply.
4.1.4.2.1 The higher value of the range should be used when,
a) unusually low reflectances or contrasts are present in the task;
b) errors are costly to rectify;
c) visual work is critical;
d) accuracy or higher productivity is of great importance; and
e) visual capacity of the worker makes it necessary.
4.1.4.2.2 The lower value of the range may be used when,
a) reflectances or contrast are unusually high;
b) speed and accuracy is not important; and
c) the task is executed only occasionally.
4.1.4.3 Where a visual task is required to be carried out throughout an interior, general illumination level to the recommended value on the working plane is necessary; where the precise height and location of the task are not known or cannot be easily specified, the recommended value is that on horizontal plane 850 mm above floor level.
NOTE — For an industrial task, working plane for the purpose of general illumination levels is that on a work place which is generally 750 mm above the floor level. For certain purposes, such as viewing the objects of arts, the illumination levels recommended are for the vertical plane at which the art pieces are placed.
4.1.4.4 Where the task is localized, the recommended value is that for the task only; it need not, and sometimes should not, be the general level of illumination used
12
throughout the interior. Some processes, such as industrial inspection process, call for lighting of specialized design, in which case the level of illumination is only one of the several factors to be taken into account.
4.1.4.5 In case of all buildings and facilities open to and used by the public, including all forms of public housing by the government/civic bodies and private developers, the minimum luminance level as given in 13 and Annex B of Part 3 'Development Control Rules and General Building Requirements' of the Code shall also be complied with for ensuring sufficient lighting for accessibility by elders and persons with disabilities.
4.1.5 Lighting for Movement About a Building
Most buildings are complexes of working areas and other areas, such as passages, corridors, stairways, lobbies and entrances. The lighting of all these areas shall be properly correlated to give safe movement within the building at all times.
In case of all buildings and facilities open to and used by the public, including all forms of public housing by the government/civic bodies and private developers, the illuminance in these areas shall comply with requirements given in 13 and Annex B of Part 3 'Development Control Rules and General Building Requirements' of the Code.
4.1.5.1 Corridors, passages and stairways
Accidents may result if people leave a well-lighted working area and pass immediately into corridors or on to stairways where the lighting is inadequate, as the time needed for adaptation to the lower level may be too long to permit obstacles or the treads of stairs to be seen sufficiently quickly. For the same reason, it is desirable that the illumination level of rooms which open off a working area should be fairly high even though the rooms may be used only occasionally.
It is important, when lighting stairways, to prevent disability from glare caused by direct sight of bright sources to emphasize the edges of the treads and to avoid confusing shadows. The same precautions should be taken in the lighting of catwalks and stairways on outdoor industrial plants.
4.1.5.2 Entrances
The problems of correctly grading the lighting within a building to allow adequate time for adaptation when passing from one area to another area are particularly acute at building entrances. These are given below:
a) By day, people entering a building will be adapted to the very high levels of brightness usually present outdoors and there is risk of accident if entrance areas, particularly any steps, are poorly lighted. This problem may often be overcome by arranging windows to
give adequate natural lighting at the immediate entrance, grading to lower levels further inside the entrance area. Where this cannot be done, supplementary artificial lighting should be installed to raise the level of illumination to an appropriate value.
b) At night it is desirable to light entrance halls and lobbies so that the illumination level reduces towards the exit and so that no bright fittings are in the line of sight of people leaving the building. Any entrance steps to the building should be well-lighted by correctly screened fittings.
4.1.6 Colour Rendering
The colour appearance of light and its colour rendering capability are different aspects of the light sources. A faithful reproduction of an object colour depends on the colour rendering capability of the light source. In 1965 International Commission on Illumination (CIE) developed a quantitative method of assignment of colour rendering property, and is denoted as Colour Rendering Index (CRI).
CRI is arrived at by a test by which a number of specified samples are tested under a standard or reference light source and the chromaticity coordinate are plotted on the IE triangle as given in Fig. 7 of Part 2 'Physics of Light, Section 3 Colour' of National Lighting Code 2010. The same test is repeated under the source under test and corresponding chromaticity coordinate are plotted on the same plot. The difference between the position of each sample for test and standard source is measured to scale. The general colour rendering index (Ra) is obtained by the average value for eight samples (see Fig. 8 of Part 2 'Physics of Light, Section 3 Colour' of National Lighting Code 2010). For perfect agreement of colour, the R1 value should be 100. In general:
Ra = 1 / (R 1 + R 2 + R 3 + R 4 + … .. + R 8)
The specific colour rendering index for an individual sample is given by:
Ri = 100 - 4.6 Δ Ei
where
Δ Ei = chromaticity shift on the CIE chromaticity diagram for each sample.
From the obtained value of Ra, as calculated above, the colour rendering shall be evaluated as mentioned in the following table:
Colour Rendering Evaluated
Ra (General Colour Rendering Index)
True
90 - 100
Good
70 - 90
Moderate
50 - 70
Table 4Recommended Values of Illuminance (Clauses 4.1.3.1, 4.1.4, 4.1.4.2, 4.3.2 and 4.3.2.1)
Sl No.
Type of Interior or Activity
Range of Service Illuminance (See Note) lux
Quality Class of Direct Glare Limitation (See Note)
Remarks
(1)
(2)
(3)
(4)
(5)
1
AGRICULTURE AND HORTICULTURE
1.1
Inspection of Farm Produce where Colour is Important
300-500-750
1
Local lighting may be appropriate
Other Important Tasks
200-300-500
2
Local lighting may be appropriate
1.2
Farm Workshops
1.2.1
General
50-100-150
3
1.2.2
Workbench or machine
200-300-500
2
Local or portable lighting may be appropriate
1.3
Milk Premises
50-100-150
3
1.4
Sick Animal Pets, Calf Nurseries
30-50-100
3
1.5
Other Firm and Horticultural Buildings
20-30-50
3
2
COAL MINING (SURFACE BUILDINGS)
2.1
Coal Preparation Plant
2.1.1
Walkways, floors under conveyors
30-50-100
3
2.1.2
Wagon loading, bunkers
30-50-100
3
2.1.3
Elevators, chute transfer pits, wash box area
50-100-150
3
2.1.4
Drum filters, screen, rotating shafts
100-150-200
3
2.1.5
Picking belts
150-200-300
3
Directional and colour properties of lighting may be important for easy recognition of coal and rock
2.2
Lamp Rooms
2.2.1
Repair section
200-300-500
2
2.2.2
Other areas
100-150-200
3
2.3
Weight Cabins, Fan Houses
100-150-200
3
2.4
Winding Houses
100-150-200
3
3
ELECTRICITY GENERATION, TRANSMISSION AND DISTRIBUTION
3.1
General Plant
3.1.1
Turbine houses (operating floor)
150-200-300
2
3.1.2
Boiler and turbine house basements
50-100-150
3
3.1.3
Boiler houses, platforms, areas around burners
50-100-150
3
3.1.4
Switch rooms, meter rooms, oil plant rooms, HV substations (indoor)
100-150-200
2
3.1.5
Control rooms
200-300-500
1
Localized lighting of control display and the control desks may be appropriate
3.1.6
Relay and telecommunication rooms
200-300-500
2
3.1.7
Diesel generator rooms, compressor rooms
100-150-200
3
3.1.8
Pump houses, water treatment plant houses
100-150-200
3
3.1.9
Battery rooms, chargers, rectifiers
50-100-150
3
3.1.10
Precipitator chambers, platforms, etc
50-100-150
3
3.1.11
Cable tunnels and basements, circulating water culverts and screen chambers, storage tanks (indoor), operating areas and filling points at outdoor tanks
Coarse work, for example, using go/no go gauges, inspection of large sub-assemblies
300-500-750
2
Local or localized lighting may be appropriate
7.7.2
Medium work, for example, inspection of painted surfaces
500-750-1 000
1
Local or localized lighting may be appropriate
7.7.3
Fine work, for example, using calibrated scales, inspection of precision mechanisms
750-1 000-1 500
1
Local or localized lighting may be appropriate
7.7.4
Very fine work, for example, inspection of small intricate parts
1 000-1 500-2 000
1
Local lighting and optical aids are desirable
7.7.5
Minute work, for example, inspection of very small instruments
2 000
1
Local lighting and optical aids are desirable
7.8
Points Shops and Spray Booths
7.8.1
Dipping, rough spraying
200-300-500
3
7.8.2
Preparation, ordinary painting, spraying and finishing
200-500-750
2
7.8.3
Fine painting, spraying and finishing
500-750-1 000
2
7.8.4
Inspection, retouching and matching
750-1 000-1 500
2
7.9
Plating Shops
7.9.1
Vats and baths
200-300-500
3
7.9.2
Buffing, polishing burnishing
300-500-750
2
7.9.3
Final buffing and polishing
500-750-1 000
2
7.9.4
Inspection
-
-
Special light to reveal fault in the surface of the material will be required
8
ELECTRICAL AND ELECTRONIC ENGINEERING
8.1
Electrical Equipment Manufacture
8.1.1
Manufacture of cables and insulated wires, winding, varnishing and immersion of coils, assembly of large machines, simple assembly work
Table 4—(Continued)
(1)
(2)
(3)
(4)
(5)
9.2.4
Frozen foods
9.2.4.1
Process area
200-300-500
3
9.2.4.2
Packaging and storage
200-300-500
3
9.3
Bottling, Brewing and Distilling
9.3.1
Keg washing and handling, bottle washing
150-200-300
3
9.3.2
Keg inspection
200-300-500
3
9.3.3
Bottle inspection
Special lighting will be required
9.3.4
Process areas
200-300-500
3
9.3.5
Bottle filling
500-750-1 000
3
9.4
Edible Oils and Fats Processing
9.4.1
Refining and blending
200-300-500
3
9.4.2
Production
300-500-750
2
9.5
Mills-Milling, Filtering and Packing
200-300-500
3
9.6
Bakeries
9.6.1
General
200-300-500
2
9.6.2
Hand decorating, icing
300-500-750
2
9.7
Chocolate and Confectionery Manufacture
9.7.1
General
200-300-500
3
9.7.2
Automatic processes
150-200-300
3
9.7.3
Hand decoration, inspection, wrapping and packing
300-500-750
2
If accurate colour judgements are required, lamps of colour rendering group 1A or 1B are used
9.8
Tobacco Processing
9.8.1
Material preparation, making and packing
300-500-750
2
10
TEXTILES
10.1
Fibre Preparation
10.1.1
Bale breaking, washing
200-300-500
18
Table 4—(Continued)
(1)
(2)
(3)
(4)
(5)
11.2.3
Cutting, splitting, scarfing, sewing
500-750-1 000
2
Directional lighting may be useful.
11.2.4
Grading, matching
2
Local lighting may be appropriate
12
CLOTHING AND FOOTWEAR
12.1
Clothing Manufacture
12.1.1
Preparation of cloth
200-300-500
2
12.1.2
Cutting
500-750-1 000
1
12.1.3
Matching
500-750-1 000
1
12.1.4
Sewing
750-1 000-1 500
1
12.1.5
Pressing
300-500-750
2
12.1.6
Inspection
1 000-1 500-2 000
1
Local lighting may be appropriate
12.1.7
Hand tailoring
1 000-1 500-2 000
1
Local lighting may be appropriate
12.2
Hosiery and Knitwear Manufacture
12.2.1
Flat bed knitting machines
300-500-750
2
12.2.2
Circular knitting machines
500-750-1000
2
12.2.3
Lockstitch and overlocking machine
750-1 000-1 500
1
12.2.4
Linking or running on
750-1 000-1 500
1
12.2.5
Mending, handfinishing
1 000-1 500-3 000
-
Local lighting may be appropriate
12.2.6
Inspection
1 000-1 500-2 000
2
Local lighting may be appropriate
12.3
Glove Manufacture
12.3.1
Sorting and grading
500-750-1 000
1
12.3.2
Pressing, knitting, cutting
300-500-750
2
12.3.3
Sewing
500-750-1 000
2
12.3.4
Inspection
1 000-1 500-2 000
Table 4 — (Continued)
(1)
(2)
(3)
(4)
(5)
13.3.7.3
Final inspection
500-750-1 000
1
Special lighting will be required
13.4
Upholstery Manufacture
13.4.1
Cloth inspection
1 000-1 500-2 000
1
Special lighting will be required
13.4.2
Filling, covering
300-500-750
2
13.4.3
Slipping, cutting, sewing
500-750-1 000
2
13.4.4
Mattress making
13.4.5
Assembly
300-500-750
2
13.4.6
Tape edging
750-1 000-1 500
2
Local lighting may be appropriate
14
PAPER AND PRINTING
14.1
Paper Mills
14.1.1
Pulp mills, preparation plants
200-300-500
3
14.1.2
Paper and board making
14.1.2.1
General
200-300-500
3
14.1.2.2
Automatic process
150-200-300
3
Supplementary lighting may be necessary for maintenance work
14.1.2.3
Inspection, sorting
300-500-750
1
14.1.3
Paper converting processes
14.1.3.1
General
200-300-500
3
14.1.3.2
Associated printing
300-500-750
2
14.2
Printing Works
14.2.1
Type foundries
14.2.1.1
Matrix making, dressing type, hand and machine coating
200-300-500
3
14.2.1.2
Front assembly, sorting
500-750-1 000
2
14.2.2
Composing rooms
14.2.2.1
Hand composing, imposition and distribution
500-750-1 000
1
20
Table 4 — (Continued)
(1)
(2)
(3)
(4)
(5)
15.2.3
Extruding, moulding
300-500-750
2
15.2.4
Inspection
750-1 000-1 500
-
16
DISTRIBUTION AND STORAGE
16.1
Work Stores
100-150-200
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.1
Unpacking, sorting
150-200-300
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.2
Large item storage
50-100-150
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.3
Small item rack storage
200-300-500
3
Avoid glare to drivers of vehicles approaching the loading bay
16.1.4
Issue counter, records, storeman's desk
300-500-750
2
Local or localized lighting may be appropriate
16.2
Warehouses and Bulk Stores
16.2.1
Storage of goods where indentification requires only limited preparation of detail
50-100-150
3
16.2.2
Storage of goods where identification requires perception of detail
100-150-200
3
16.2.3
Automatic high bay rack stores
16.2.3.1
Gangway
20
16.2.3.2
Control station
150-200-300
3
16.2.3.3
Packing and dispatch
200-300-500
3
16.2.3.4
Loading bays
100-150-200
3
Avoid glare to drivers of vehicles approaching the loading bay
16.3
Cold Stores
16.3.1
General
200-300-500
3
16.3.2
Breakdown, make-up and dispatch
200-300-500
3
16.3.3
Loading bays
100-150-200
3
Avoid glare to drivers of vehicles approaching the loading bay
17
Table 4—(Continued)
(1)
(2)
(3)
(4)
(5)
18.3.3
Head ironing, pressing, mending, spotting, inspection
300-500-750
3
18.3.4
Launderettes
200-300-500
3
18.4
Sewage Treatment Works
18.4.1
Walkways
30-50-100
3
18.4.2
Process areas
50-100-150
3
19
RETAILING
The service illuminance should be provided on the horizontal plane of the counter. Where wall displays are used, a similar illuminance on the walls is desirable
19.1
Small Shops with Counters
300-500-750
1
19.2
Small Self-Service Shops with Island Displays
300-500-750
1
19.3
Super Markets, Hyper-Markets
19.3.1
General
300-500-750
2
19.3.2
Checkout
300-500-750
2
19.3.3
Showroom for large objects, for example, cars, furniture
300-500-750
1
19.3.4
Shopping precincts and arcades
100-150-200
2
20
PLACES OF PUBLIC ASSEMBLY
20.1
Public Rooms, Village Halls, Worship Halls
200-300-500
1
20.2
Concert Halls, Cinemas and Theatres
20.2.1
Foyer
150-200-300
20.2.2
Booking office
200-300-500
Local or localized lighting may be appropriate
20.2.3
Auditorium
50-100-150
Dimming facilities will be necessary. Special lighting of the aisles is desirable
20.2.4
Dressing rooms
200-300-500
Special mirror lighting for make-up may be required
20.2.5
Projection room
100-150-200
20.3
Churches
20.3.1
Body of church
22
Table 4 — (Continued)
(1)
(2)
(3)
(4)
(5)
20.4.9.1
Morning/day/evening
200-300-500
20.4.9.2
Night desks
30
20.4.9.3
Night, medical trolleys
50-100-150
20.4.10
Operating theatres
20.4.10.1
General
300-500-750
20.4.10.2
Local
10 000 to 50 000
Special operating lights are used.
20.4.11
Pathology departments
20.4.11.1
General
200-300-500
20.4.11.2
Examination
300-500-750
20.4.11.3
Pharmacies
200-300-500
20.4.11.4
Reception/enquiry
200-300-500
20.4.11.5
Recovery rooms
200-300-500
20.4.12
Ward-circulation
20.4.12.1
Day
50-100-150
20.4.12.2
Morning/evening
50-100-150
20.4.12.3
Night
3-5
20.4.13
Ward-bed head
20.4.13.1
Morning/evening
30-50
20.4.13.2
Reading
100-150-200
20.4.14
Night
20.4.14.1
Adult
0.1-1
20.4.14.2
Pediatric
1
20.4.14.3
Psychiatric
1-5
20.4.14.4
Watch
5
20.4.15
X-Ray areas
20.4.15.1
General
150-200-300
20.4.15.2
Diagnostic
150-200-300
20.4.15.3
Operative
200-300-500
20.4.15.4
Process dark room
Table 4—(Continued)
(1)
(2)
(3)
(4)
(5)
20.6.3.3
Bookshelves
100-150-200
2
The service illuminance should be provided on a vertical surface at the foot of the bookshelves
20.6.3.4
Study tables, carrels
300-500-750
1
20.6.3.5
Map room
200-300-500
1
20.6.4
Display and exhibition areas
20.6.4.1
Exhibits insensitive to light
200-300-500
20.6.4.2
Exhibit sensitive to light, for example, pictures, prints, rare books in archives
50 to 150
20.6.5
Library workrooms
20.6.5.1
Book repair and binding
300-500-750
2
20.6.5.2
Catalogue and sorting
300-500-750
2
20.6.5.3
Remote book stores
100-150-200
3
20.7
Museums and Art Galleries
20.7.1
Exhibits insensitive to light
200-300-500
20.7.2
Light sensitive exhibits, for example, oil and temper paints, undyed leather, bone, ivory, wood, etc
150
This is a maximum illuminance to be provided on the principal plane of the exhibit
20.7.3
Extremely light sensitive exhibits, for example, textiles, water colours, prints and drawings, skins, botanical specimens, etc
50
This is the maximum illuminance to be provided on the principal plane of the object
20.7.4
Conservation studies and workshops
300-500-750
1
20.8
Sports Facilities
Multi-purpose sports halls
300-750
This lighting system should be sufficiently flexible to provide lighting suitable for the variety of sports and activities that take place in sports halls. Higher illuminance of 1000-2000 lux would be required for television coverage
21
EDUCATION
21.1
Assembly Halls
21.1.1
General
24
Table 4 — (Concluded)
(1)
(2)
(3)
(4)
(5)
22.2.7
Time table
150-200-300
2
Localized lighting may be appropriate
22.2.8
Ticket barriers
150-200-300
2
Localized lighting may be appropriate
22.2.9
Platforms (covered)
30-50-100
2
Care should be taken to light and mark the edge of the platform clearly
22.2.10
Platforms (open)
20
Care should be taken to light and mark the edge of the platform clearly
22.3
Coach Stations
22.3.1
Ticket offices
300-500-750
2
Localized lighting over the counter may be appropriate
22.3.2
Information offices
300-500-750
2
Localized lighting over the counter may be appropriate
22.3.3
Left luggage office
22.3.3.1
General
50-100-150
3
22.3.3.2
Counter
150-200-300
3
Localized lighting is appropriate
22.3.4
Waiting rooms
150-200-300
2
22.3.5
Concourse
150-200-300
2
22.3.6
Time tables
150-200-300
2
Local lighting is appropriate
22.3.7
Loading areas
100-150-200
3
23
GENERAL BUILDING AREAS
23.1
Entrance
23.1.1
Entrance halls, lobbies, waiting rooms
150-200-300
2
23.1.2
Enquiry desks
300-500-750
2
Localized lighting may be appropriate
23.1.3
Gatehouses
150-200-300
2
23.2
Circulation Areas
23.2.1
Lifts
50-100-150
23.2.2
Corridors, passageways, stairs
50-100-150
2
4.1.7 For detailed information regarding principles of good lighting, reference may be made to good practice [8-1(2)].
FIG. 2 CLIMATIC ZONES OF INDIA
3.4 Solar Radiation
3.4.1 The best orientation from solar point of view requires that the building as a whole should receive the maximum solar radiation in winter and the minimum in summer. For practical evaluation, it is necessary to know the duration of sunshine, and hourly solar intensity on the various external surfaces on representative days of the seasons. The total direct plus diffused diurnal solar loads per unit area on vertical surface facing different directions are given in Table 3 for two days in the year, that is, 22 June and 22 December, representative of summer and winter, for latitudes corresponding to some important cities all over India. From Table 3, the total heat intake can be calculated for all possible orientations of the building for these extreme days of summer and winter. Solar load on vertical surfaces of different orientation can be calculated as per the method given in Annex A.
3.4.1.1 Except in cold climatic zone, suitable sun-breakers have to be provided to cut off the incursion of direct sunlight to prevent heat radiation and to avoid glare.
3.5 Relative Humidity and Prevailing Winds
3.5.1 The discomfort due to high relative humidity in air when temperatures are also high can be counteracted, to a great extent, by circulation of air with electric fans or by ventilation. In the past, simultaneously with heavy construction and surrounding Verandahs to counter the effect of sun's radiation, there was also an over emphasis on prevailing winds to minimise the adverse effects of high humidity
with high temperatures. With the introduction of electric fan to effectively circulate air and owing to taking into account the rise in cost of construction of buildings, emphasis should be placed on protection from solar radiation where temperatures are very high. When, however, there is less diurnal variation between morning and mean maximum temperatures along with high humidity, as in coastal areas, the emphasis should be on prevailing winds.
3.5.1.1 For the purpose of orientation, it is necessary to study the velocity and direction of the wind at each hour and in each month instead of relying on generalizations of a month or a period or for the year as a whole. This helps to spot the right winds for a particular period of day or night.
3.5.1.2 It is generally found that variation up to 30° with respect to the prevalent wind direction does not materially affect indoor ventilation (average indoor air speed) inside the building.
3.5.2 In hot-dry climate, advantage can be taken of evaporative cooling in summer to cool the air before introducing it into the building. But in warm humid climate, it is desirable either to regulate the rate of air movement with the aid of electric fans or to take advantage of prevailing winds.
3.6 Aspects of Daylighting
Since the clear design sky concept for daylighting takes care of the worst possible situation, orientation is not a major problem for daylighting in buildings, except that
Table 3Total Solar Radiation (Direct Plus Diffused) Incident on Various Surfaces of Buildings, in W/m²/day, for Summer and for Winter Seasons (Clause 3.4.1)
Sl No.
Orientation
Latitude
(1)
(2)
9°N (3)
13°N (4)
17°N (5)
21°N (6)
25°N (7)
29°N (8)
i)
North
Summer
1 494
1 251
2 102
1 775
2 173
1 927
Winter
873
859
840
825
802
765
ii)
North-East
Summer
2 836
2 717
3 144
3 092
3 294
3 189
Winter
1 240
1 158
1 068
1 001
912
835
iii)
East
Summer
3 344
3 361
3 475
3 598
3 703
3 794
Winter
2 800
2 673
2 525
2 409
2 211
2 055
iv)
South-East
Summer
2 492
2 660
2 393
2 629
2 586
2 735
Winter
3 936
3 980
3 980
3 995
3 892
3 818
v)
South
Summer
1 009
1 185
1 035
1 117
1 112
1 350
Winter
4 674
4 847
4 958
5 059
4 942
4 981
vi)
South-West
Summer
2 492
2 660
2 393
2 629
2 586
2 735
Winter
3 936
3 980
3 980
3 995
3 892
3 818
vii)
West
Summer
3 341
3 361
3 475
3 598
3 703
3 794
Winter
2 800
2 673
2 525
2 409
2 211
2 055
viii)
North-West
Summer
2 836
2 717
3 144
3 092
3 294
3 189
Winter
1 240
1 158
1 068
1 001
912
835
ix)
Horizontal
Summer
8 107
8 139
8 379
8 553
8 817
8 863
Winter
6 409
6 040
5 615
5 231
4 748
4 281
direct sunshine and glare should be avoided. However, due allowance should be given to the mutual shading effects of opposite facades.
3.7 Planting of Trees
Planting of trees in streets and in open spaces should be done carefully to take advantage of both shades and sunshine without handicapping the flow of natural winds. Their advantage in abating glare and in providing cool and/or warm pockets in developed areas should also be taken. Some trees shed leaves in winter while retaining thick foliage in summer. Such trees will be very advantageous, particularly where southern and western exposures are concerned, by allowing maximum sun during winter and effectively blocking it in summer.
3.8 For detailed information regarding orientation of buildings and recommendations for various climatic zones of country, reference may be made to good practice [8-1(1)].
4.4.3.3 Method of use
The following steps shall be followed for the use of nomogram:
a) Step 1 — Decide the desired illumination level depending upon the task illumination requirement in the proposed room and read the value of watts per m² on the curve corresponding to the required illumination level.
b) Step 2 — Fix the vertical line corresponding to the given separation to height ratio of opposite buildings on the abscissa. From the point of intersection of this vertical line and the above curve move along horizontal, and read the value of fenestration percent on the left hand ordinate.
c) Step 3 — If the floor area is greater than 50 m² or if it is less than 30 m² , the value of watt per m² as well as fenestration percent may be easily determined for adequate daylighting and supplemental artificial lighting for design
WORK PLANE ILLUMINATION (LUX) INCLUSIVE OF SUPPLEMENTAL LIGHTS DURING POOR DAYLIGHT CONDITIONS
bok Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up
SEPARATION TO HEIGHT RATIO
FIG. 4 NOMOGRAPH FOR DAYLIGHTING AND SUPPLEMENTAL LIGHTING DESIGN OF BUILDINGS
32
purposes. However, if the fenestration provided is less than the required value, the wattage of supplementary artificial lights should be increased proportionately to make up for the deficiency of natural illumination.
4.4.4 For good distribution of day light on the working plane in a room, window height, window width and height of sill should be chosen in accordance with the following recommendations:
a) In office buildings windows of height 1.2 m or more in the centre of a bay with sill level at 1.0 to 1.2 m above floor and in residential buildings windows of height 1.0 m to 1.1 m with sill height as 0.7 m to 0.9 m above floor are recommended for good distribution of daylight indoors. Window width can accordingly be adjusted depending upon the required fenestration percentage of the floor area.
b) If the room depth is more than 10 m, windows should be provided on opposite sides for bilateral lighting.
c) It is desirable to have a white finish for ceiling and off white (light colour) to white for walls. There is about 7 percent improvement in lighting levels in changing the finish of walls from moderate to white.
4.4.5 For good distribution and integration of daylight with artificial lights the following guidelines are recommended:
a) Employ cool daylight fluorescent tubes for supplementary artificial lighting.
b) Distribute luminaries with a separation of 2 m to 3 m in each bay of 3 m to 4 m width.
c) Provide more supplementary lights such as twin tube luminaries in work areas where daylight is expected to be poor, for example in the rear region of a room having single window and in the central region of a room having windows on opposite walls. In the vicinity of windows only single tube luminaries should be provided.
4.4.6 Artificial Lighting
Energy conservation in lighting is affected by reducing wastage and using energy effective lamps and luminaires without sacrificing lighting quality. Measures to be followed comprise utilization of daylight, energy effective artificial lighting design by providing required illumination where needed, turning off artificial lights when not needed, maintaining lighter finishes of ceiling, walls and furnishings, and implementing periodic schedule for cleaning of
luminaires and group replacement of lamps at suitable intervals. Choice of light sources with higher luminous efficacy and luminaires with appropriate light distribution is the most effective means of energy saving in lighting. However, choice of light sources also depends on the other lighting quality parameters like colour rendering index and colour temperature or appearance. For example, high pressure sodium vapour lamps, which have very high luminous efficacy, are not suitable for commercial interiors because of poor colour rendering index and colour appearance, but are highly desirable in heavy industries. Also the choice of light sources depends on the mounting height in the interiors. For example, fluorescent lamps are not preferred for mounting beyond 7 m height, when high pressure gas discharge lamps are preferred because of better optical control due to their compact size.
4.4.6.1 Efficient artificial light sources and luminaires
Luminous efficacies of some of the lamps used in lighting of buildings are given in Table 8 along with average life in burning hours, colour rendering index and colour temperature.
Following recommendations may be followed in the choice of light sources for different locations:
a) For supplementary artificial lighting of work area in office building care should be taken to use fluorescent lamps, which match with colour temperature of the daylight.
b) For residential buildings fluorescent lamps and/or CFLs of proper CRI and CCT are recommended to match with the colours and interior design of the room.
c) For commercial interiors, depending on the mounting heights and interior design, fluorescent lamps, CFLs and low wattage metal halide lamps are recommended. For highlighting the displays in show windows, hotels, etc, low wattage tubular or dichroic reflector type halogen lamps can be used.
d) For industrial lighting, depending on the mounting height and colour consideration fluorescent lamps, high pressure mercury vapour lamps or high pressure sodium vapour lamps are recommended.
4.4.6.2 For the same lumen output, it is possible to save 50 to 70 percent energy if CFL lamps are replaced with induction lighting, and 40 to 60 percent if replaced with LED lamps. Similar energy effective solutions are to be chosen for every application area.
Similarly with white fluorescent tubes recommended for corridors and staircases, the electrical consumption reduces to 1/4.5 of the energy consumption with incandescent lamps.
Table 8Luminous Efficacy, Life, Lumen Maintenance and Colour Rendition of Light Sources (Clause 4.4.6.1)
Sl No.
Light Source
Wattage Range W
Efficacy lm/W
Average Life h
Lumen Maintenance
Colour Rendition
(1)
(2)
(3)
(4)
(5)
(6)
(7)
i)
Incandescent lamps
15 to 200
12 to 20
500 to 1 000
Fair to good
Very good
ii)
Tungsten halogen
300 to 1 500
20 to 27
200 to 2 000
Good to very good
Very good
iii)
Standard fluorescent lamps
20 to 80
55 to 65
5 000
Fair to good
Good
iv)
Compact fluorescent lamps (CFL)
5 to 40
60 to 70
7 500
Good
Good to very good
v)
Slim line fluorescent
18 to 58
57 to 67
5 000
Fair to good
Good
v)
High pressure mercury vapour lamps
60 to 1 000
50 to 65
5 000
Very low to fair
Federate
vi)
Blended - light lamps
160 to 250
20 to 30
5 000
Low to fair
Federate
vii)
High pressure sodium vapour lamps
50 to 1 000
90 to 125
10 000 to 15 000
Fair to good
Low to good
viii)
Metal halide lamps
35 to 2 000
80 to 95
4 000 to 10 000
Very low
Very good
ix)
Low pressure sodium
10 to 180
100 to 200
10 000 to 20 000
Good to very good
Poor
x)
LED
0.5 to 2.0
60 to 100
10 000
Very good
Good for white LED
1 The table includes lamps and wattages currently in use in buildings in India.
2 Luminous efficacy varies with the wattage of the lamp.
3 Average life values are from available Indian Standards. Where Indian Standard is not available, values given are only indicative.
4 For exact values, it is advisable to contact manufacturers.
4.4.6.3 Efficient luminaire also plays an important role for energy conservation in lighting. The choice of a luminaire should be such that it is efficient not only initially but also throughout its life. Following luminaries are recommended for different locations:
a) For offices semi-direct type of luminaries are recommended so that both the work plane illumination and surround luminance can be effectively enhanced.
b) For corridors and stair cases direct type of luminaries with wide spread of light distributions are recommended.
c) In residential buildings, bare fluorescent tubes are recommended. Wherever the incandescent lamps are employed, they should be provided with white enameled conical reflectors at an inclination of about 45° from vertical.
4.4.7 Cleaning Schedule for Window Panes and Luminaires
Adequate schedule for cleaning of window panes and luminaries will result in significant advantage of enhanced daylight and lumen output from luminaries. This will tend to reduce the duration over which artificial lights will be used and minimise the wastage of energy. Depending upon the location of the building a minimum of three to six months interval for periodic cleaning of luminaries and window panes is
recommended for maximum utilization of daylight and artificial lights.
4.4.8 Photocontrols for Artificial Lights
There is a considerable wastage of electrical energy in lighting of buildings due to carelessness in switching off lights even when sufficient daylight is available indoors. In offices and commercial buildings, occupants may switch on lights in the morning and keep them on throughout the day. When sufficient daylight is available inside, suitable photo controls can be employed to switch off the artificial lights and thus prevent the wastage of energy.
The photocontrol should have the following features:
a) An integrated photocontrol system continually measures the amount of visible light under the lighting fixture and maintains the lux levels as referred in Table 4.
b) An integrated photocontrol system should maintain six daylighting scenarios that can be adjusted by the user namely; daytime occupied, daytime unoccupied, sunset occupied, sunset unoccupied, night time occupied and night time unoccupied.
c) The photocontrol sensor should have a 60° cone of reference to measure the amount of light on the work surface.
4.4.9 Solar Photovoltaic Systems (SPV)
Solar photovoltaic system enables direct conversion of sunlight into electricity and is a viable option for lighting purpose in remote nongrid areas. The common SPV lighting systems are:
a) Solar lantern,
b) Fixed type solar home lighting system, and
c) Street lighting system.
4.4.9.1 SPV lighting system should preferably be provided with CFL for energy efficiency.
4.4.9.2 Inverters used in buildings for supplying electricity during the power cut period should be charged through SPV system.
4.4.9.3 Regular maintenance of SPV system is necessary for its satisfactory functioning.
4.4.10 Lighting shelves and light pipes may be explored for utilization and integration in the lighting design.
Sl No.(1)
Application(2)
Air Change per Hour(3)
1.
Assembly rooms
4-8
2.
Bakeries
20-30
3.
Banks/building societies
4-8
4.
Bathrooms
6-10
5.
Bedrooms
2-4
6.
Billiard rooms
6-8
7.
Boiler rooms
see Note 2
8.
Cafes and coffee bars
10-12
9.
Canteens
8-12
10.
Cellars
3-10
11.
Changing rooms
6-10
12.
Churches
1-3
13.
Cinemas and theatres
10-15
14.
Club rooms
12, Min
15.
Compressor rooms
10-12
16.
Conference rooms
8-12
17.
Corridors
5-10
Sl No.(1)
Application(2)
Air Change per Hour(3)
18.
Dairies
8-12
19.
Dance halls
12, Min
20.
Dye works
20-30
21.
Electroplating shops
10-12
22.
Engine rooms/DG Rooms/GG Rooms
see Note 2
23.
Entrance halls
3-5
24.
Factories and work shops
8-10
25.
Foundries
15-30
26.
Garages
6-8
27.
Glass houses
25-60
28.
Gymnasium
6, Min
29.
Hair dressing saloon
10-15
30.
Hospitals sterilising
15-25
31.
Hospital wards
6-8
32.
Hospital domestic
15-20
33.
Laboratories
6-15
34.
Launderettes
10-15
35.
Laundries
10-30
36.
Lavatories
6-15
37.
Lecture theatres
5-8
38.
Libraries
3-5
39.
Lift cars
20, Min
40.
Living rooms
3-6
41.
Mushroom houses
6-10
42.
Offices
6-10
43.
Paint shops (not cellulose)
10-20
44.
Photo and X-ray dark room
10-15
45.
Public house bars
12, Min
46.
Recording control rooms
15-25
47.
Recording studios
10-12
48.
Restaurants
8-12
49.
Schoolrooms
5-7
50.
Shops and supermarkets
8-15
51.
Shower baths
15-20
52.
Stores and warehouses
3-6
53.
STP rooms
30, Min
54.
Squash courts
4, Min
55.
Swimming baths
10-15
56.
Toilets
6-10
57.
Underground vehicle parking
6, Min
58.
Utility rooms
15-30
59.
Welding shops
15-30
NOTES
1 The ventilation rates may be increased by 50 percent where heavy smoking occurs or if the room is below the ground.
2 The ventilation rate shall be as per 11.2.2 of Part 8 ‘Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation’ of the Code.
5.2.3 Heat Balance of Body
Especially in hot weather, when thermal environment inside the room is worsened by heat given off by machinery, occupants and other sources, the prime need for ventilation is to provide such thermal environment as will assist in the maintenance of heat balance of the body in order to prevent discomfort and injury to health. Excess of heat either from increased metabolism due to physical activity of persons or gains from a hot environment has to be offset to maintain normal body temperature (37°C). Heat exchange of the human body with respect to the surroundings is determined by the temperature and humidity gradient between the skin and the surroundings and other factors, such as age of persons, clothing, etc, and the latter depends on air temperature (dry bulb temperature), relative humidity, radiation from the solid surroundings and rate of air movement. The volume of outside air to be circulated through the room is, therefore, governed by the physical considerations of controlling the temperature, air distribution or air movement. Air movement and air distribution may, however, be achieved by recirculation of the inside air rather than bringing in all outside air. However, fresh air supply or the circulated air will reduce heat stress by dissipating heat from body by evaporation of the sweat, particularly when the relative humidity is high and the air temperature is near body temperature.
5.2.3.1 Indices of thermal comfort
Thermal comfort is that condition of thermal environment under which a person can maintain a body heat balance at normal body temperature and without perceptible sweating. Limits of comfort vary considerably according to studies carried out in India and abroad.
The thermal indices which find applications for Indian climate are as follows:
a) Effective temperature (ET),
b) Tropical summer index (TSI), and
c) Adaptive thermal comfort.
5.2.3.1.1 Effective temperature (ET)
Effective temperature is defined as the temperature of still, saturated air which has the same general effect upon comfort as the atmosphere under investigation. Combinations of temperature, humidity and wind velocity producing the same thermal sensation in an individual are taken to have the same effective temperature.
Initially two scales were developed, one of which referred to men stripped to the waist, and called the basic scale. The other applies to men fully clad in indoor clothing and called the normal scale of effective
36
temperature. Bedfort (1946) proposed the use of globe temperature reading instead of the air temperature reading to make allowance for the radiant heat. This scale is known as the corrected effective temperature (CET) scale. No allowance, however, was made for the different rates of energy expenditure. The scale was compiled only for men either seated or engaged in light activity.
Figure 5 represents the corrected effective temperature nomogram. The CET can be obtained by connecting the appropriate points representing the dry bulb (or globe) and wet bulb temperatures and reading the CET value at the intersection of this line with the relevant air velocity curve from the family of curves for various air velocities running diagonally upwards from left to right.
The effective temperature scale may be considered to be reasonably accurate in warm climates where the heat stress is not high but it may be misleading at high levels of heat stress. There appears to be an inherent error in this scale if used as an index of physiological strain, the error increasing with the severity of the environmental conditions. For low and moderate degrees of heat stress, the effective temperature scales
appear to assess climatic heat stress with an accuracy which is acceptable for most practical purposes.
5.2.3.1.2 Tropical summer index (TSI)
The TSI is defined as the temperature of calm air, at 50 percent relative humidity which imparts the same thermal sensation as the given environment. The 50 percent level of relative humidity is chosen for this index as it is a reasonable intermediate value for the prevailing humidity conditions. Mathematically, TSI ( ° C) is expressed as:
T S I = 0. 7 4 5 t g + 0. 3 0 8 t w - 2. 0 6 √(v + 0 . 8 4 1)
where
t w = wet bulb temperature, in ° C;
t g = globe temperature, in ° C; and
V = air speed, in m / s.
The thermal comfort of a person lies between TSI values of 25° C and 30° C with optimum condition at 27.5° C. Air movement is necessary in hot and humid weather for body cooling. A certain minimum desirable wind speed is needed for achieving thermal comfort at different temperatures and relative humidities. Such
FIG. 5 CORRECTED EFFECTIVE TEMPERATURE NOMOGRAM
wind speeds are given in Table 9. These are applicable to sedentary work in offices and other places having no noticeable sources of heat gain. Where somewhat warmer conditions are prevalent, such as in godowns and machine shops and work is of lighter intensity, and higher temperatures can be tolerated without much discomfort, minimum wind speeds for just acceptable warm conditions are given in Table 10. For obtaining values of indoor wind speed above 2.0 m/s, mechanical means of ventilation may have to be adopted (see also Part 8 'Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation' of the Code).
The warmth of the environment was found tolerable between 30° C and 34° C (TSI), and too hot above this limit. On the lower side, the coolness of the environment was found tolerable between 19° C and 25° C (TSI) and below 19° C (TSI), it was found too cold.
Table 10Minimum Wind Speeds (m/s) for Just Acceptable Warm Conditions (Clause 5.2.3.1.2)
Sl No.
Dry Bulb Temperature
Relative Humidity Percent
°C
30(3)
40(4)
50(5)
60(6)
70(7)
80(8)
90(9)
i)
28
1)
1)
1)
1)
1)
1)
1)
ii)
29
1)
1)
1)
1)
1)
1)
1)
iii)
30
1)
1)
1)
1)
1)
1)
1)
iv)
31
1)
1)
1)
1)
1)
0.06
0.23
v)
32
1)
1)
1)
0.09
0.29
0.60
0.94
vi)
33
1)
0.04
0.24
0.60
1.04
1.85
2.10
vii)
34
0.15
0.46
0.94
1.60
2.26
3.05
2)
viii)
35
0.68
1.36
2.10
3.05
2)
2)
2)
ix)
36
1.72
2.70
2)
2)
2)
2)
2)
None.
²⁾ Higher than those acceptable in practice.
5.2.3.1.3 Adaptive thermal comfort
For details on adaptive thermal comfort, reference shall be made to Part 8 ‘Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation’ of this Code.
5.2.3.2 There will be a limit of heat tolerance when air temperatures are excessive and the degree of physical activity is high. This limit is determined when the bodily heat balance is upset, that is, when the bodily heat gain due to conduction, convection and the radiation from the surroundings exceeds the bodily heat loss, which is mostly by evaporation of sweat from the surface of the body. The limits of heat tolerance for Indian workers are based on the study conducted by the Chief Adviser Factories, Government of India, Ministry of Labour and are given in his report on Thermal Stress in Textile Industry (Report No. 17) issued in 1956. According to this Report, where workers in industrial buildings wearing light clothing are expected to do work of moderate severity with the energy expenditure in the range 273 to 284 W, the maximum wet bulb temperature shall not exceed 29° C and adequate air movement subject to a minimum air velocity of 30 m/min shall be provided, and in relation to the dry bulb temperature, the wet bulb temperature of air in the work room, as far as practicable, shall not exceed that given in Table 11.
Table 11Maximum Permissible Wet Bulb Temperatures for Given Dry Bulb Temperatures (Clause 5.2.3.2)
Sl No.
Dry Bulb Temperature °C
Maximum Wet-Bulb Temperature °C
(1)
(2)
(3)
i)
30
29.0
ii)
35
28.5
iii)
40
28.0
iv)
45
27.5
v)
50
27.0
NOTES
1 These are limits beyond which the industry should not allow the thermal conditions to go for more than 1h continuously. The limits are based on a series of studies conducted on Indian subjects in psychrometric chamber and on other data on heat casualties in earlier studies conducted in Kolar Gold Fields and elsewhere.
2 Figures given in this table are not intended to convey that human efficiency at 50°C will remain the same as at 30°C, provided appropriate wet bulb temperatures are maintained. Efficiency decreases with rise in the dry bulb temperature as well, as much as possible. Long exposures to temperature of 50°C dry bulb/ 27°C wet bulb may prove dangerous.
3 Refrigeration or some other method of cooling is recommended in all cases where conditions would be worse than those shown in this table.
38
The compilation of tables for the utilization factor requires a considerable amount of calculations, especially if these tables have to cover a wide range of lighting practices. For every luminaire, the exact light distribution has to be measured in the laboratory and their efficiencies have to be calculated and measured exactly. These measurements comprise,
i) the luminous flux radiated by the luminaires directly to the measuring surface;
ii) the luminous flux reflected and re-reflected by the ceiling and the walls to the measuring surface; and
iii) the inter-reflections between the ceiling and wall which result in the measuring surface receiving additional luminous flux.
All these measurements have to be made for different reflection factors of the ceiling and the walls for all necessary room indices. These tables have also to indicate the maintenance factor to be taken for the luminous flux depreciation
throughout the life of an installation due to ageing of the lamp and owing to the deposition of dirt on the lamps and luminaires and room surfaces.
The values of the reflection factor of the ceiling and of the wall are as follows:
White and very light colours :
0.7
Light colours :
0.5
Middle tints :
0.3
Dark colours :
0.1
For the walls, taking into account the influence of the windows without curtains, shelves, almirahs and doors with different colours, etc, should be estimated.
c) Calculation for determining the luminous flux [see Table 22 of SP : 41 (S&T) — 1987 'Handbook on functional requirements of buildings other than industrial buildings']
Eav=Aμiϕ
or, φ= EavAµ , for new condition, and
φ = E av · Aµ · d, for working condition
where
φ = total luminous flux of the light sources installed in the room, in lumens;
Eav = average illumination level required on the working plane, in lux;
A = area of the working plane, in m²;
µ = utilization factor in new conditions; and
d = maintenance factor.
In practice, it is easier to calculate straightaway the number of lamps or luminaires from:
Nlamp=μ.d.ϕlampEav⋅A
Nluminaires=μ.d.ϕluminairesEav.A
where
φlamp = luminous flux of each lamp, in lumens
φluminaires = luminous flux of each luminaire, in lumens
Nlamp = total number of lamps
Nluminaires = total number of luminaires.
4.3.2.4 Arrangement of the luminaires
This is done to achieve better uniformly distributed illumination. The location of the luminaires has an important effect on the utilization factor.
a) In general, luminaires are spaced ‘x’ metre apart in either direction, while the distance of the end luminaire from the wall is ‘0.5x’ metre. The distance ‘x’ is more or less equal to the mounting height ‘ Hm ’ between the luminaire and the working plane. The utilization factor tables are calculated for this arrangement of luminaires [see Table 22 of SP : 41 (S&T) – 1987 ‘Handbook on functional requirements of buildings other than industrial buildings’].
b) For small rooms where the room index (kr) is less than 1, the distance ‘x’ should always be less than Hm , since otherwise luminaires cannot be properly located. In most cases of such rooms, four or two luminaires are placed for good general lighting. If, however, in such rooms only one luminaire is installed in the middle, higher utilization factors are obtained, but the uniformity of distribution is poor. For such cases, references should be made to the additional tables for kr = 0.6 to 1.25 for luminaires located centrally.
4.3.3 Artificial Lighting to Supplement Daylighting
4.3.3.1 The need for general supplementary artificial lighting arises due to diminishing of daylighting beyond
design hours, that is, for solar altitude below 15° or when dark cloudy conditions occur.
4.3.3.2 The need may also arise for providing artificial lighting during the day in the innermost parts of the building which cannot be adequately provided with daylighting, or when the outside windows are not of adequate size or when there are unavoidable external obstructions to the incoming daylighting.
4.3.3.3 The need for supplementary lighting during the day arises, particularly when the daylighting on the working plane falls below 100 lux and the surrounding luminance drops below 19 cd/m².
4.3.3.4 The requirement of supplementary artificial lighting increases with the decrease in daylighting availability. Therefore, conditions near sunset or sunrise or equivalent conditions due to clouds or obstructions, etc, represent the worst conditions when the supplementary lighting is most needed.
4.3.3.5 The requirement of supplementary artificial lighting when daylighting availability becomes poor may be determined from Fig. 3 for an assumed ceiling height of 3.0 m, depending upon floor area, fenestration percentage and room surface reflectance. Cool daylight fluorescent tubes are recommended with semi-direct luminaires. To ensure a good distribution of illumination, the mounting height should be between 1.5 m and 2.0 m above the work plane for a separation of 2.0 m to 3.0 m between the luminaires. Also the number of lamps should preferably be more in the rear half of the room than in the vicinity of windows. The
FIG. 3 SUPPLEMENTARY ARTIFICIAL LIGHTING FOR 40 W FLUORESCENT TUBES
following steps may be followed for using Fig. 3 for determining the number of fluorescent tubes required for supplementary daylighting.
a) Determine fenestration percentage of the floor area, that is,
Floor areaWindow area×100
b) In Fig. 3, refer to the curve corresponding to the percent fenestration determined above and the set of reflectances of ceiling, walls and floor actually provided.
c) For the referred curve of Fig. 3 read, along the ordinate, the number of 40 W fluorescent tubes required, corresponding to the given floor area on the abscissa.
4.3.4 For detailed information on the design aspects and principles of artificial lighting, reference may be made to good practice [8-1(2)].
4.3.5 For specific requirements for lighting of special occupancies and areas, reference may be made to good practice [8-1(5)].
4.3.6 Electrical installation aspect for artificial lighting shall be in accordance with Part 8 ‘Building Services, Section 2 Electrical and Allied Installations’ of the Code.
A=free area of inlet openings, in m2;
h = vertical distance between inlets and outlets, in m;
tr = average temperature of indoor air at height h, in °C; and
t₀ = temperature of outdoor air, in °C.
NOTE — The equation is based on 0.65 times the effectiveness of openings. This should be reduced to 0.50, if conditions are not favourable.
5.6.1.3 When areas of inlet and outlet openings are unequal, the value of A may be calculated using the equation:
A22=Ainlet21+Aoutlet21
5.6.1.4 Combined Effect of Wind and Thermal Action
When both forces (wind and thermal) act together in the same direction, even without interference, the
resulting air flow is not equal to the two flows estimated separately.
When acting simultaneously, the rate of air flow through the building may be computed by the following equation:
Q ² = Q w ² + Q t ²
where
Q = resultant volume of air flow, in m³ /min;
Qw = volume of air flow due to wind force, in m³/min; and
Qt = volume of air flow due to thermal force, in m³/min.
Wind velocity and direction, outdoor temperature, and indoor distribution cannot be predicted with certainty, and refinement in calculation is not justified. A simple method is to calculate the sum of the flows produced by each force separately. Then using the ratio of the flow produced by thermal forces to the aforementioned sum, the actual flow due to the combined forces can be approximated from Fig. 10. When the two flows are equal, the actual flow is about 30 percent greater than the flow caused by either force acting independently (see Fig. 10).
FLOW DUE TO TEMPERATURE DIFFERENCE AS PERCENT OF TOTAL
FIG. 10 DETERMINATION OF FLOW CAUSED BY COMBINED FORCES OF WIND AND TEMPERATURE DIFFERENCE
Judgment is necessary for proper location of openings in a building specially in the roof, where heat, smoke and fumes are to be removed. Usually, windward
44
monitor openings should be closed, but if wind is so slight that temperature head can overcome it, all openings may be opened.
5.6.1.5 For method for determining the rate of ventilation based on probable indoor wind speed with typical illustrative example for residential building, reference may be made to A-4 of good practice [9-1(6)].
5.6.2 Mechanical Ventilation
The determination of rate of ventilation in case of mechanical ventilation shall be done in accordance with Part 8 ‘Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation’ of the Code.
5.6.3 Combined effect of Different Methods of Ventilation
When combination of two or more methods of general ventilation is used, the total rate of ventilation shall be reckoned as the highest of the following three, and this rule shall be followed until an exact formula is established by research:
a) 1.25 times the rate of natural ventilation,
b) Rate of positive ventilation, and
c) Rate of exhaust of air.
5.6.4 Measurement of Air Movement
The rate of air movement of turbulent type at the working zone shall be measured either with a Kata thermometer (dry silvered type) or heated thermometer or properly calibrated thermocouple anemometer. Whereas anemometer gives the air velocity directly, the Kata thermometer and heated thermometer give cooling power of air and the rate of air movement is found by reference to a suitable nomogram using the ambient temperature.
1 400/1
1 500/1
1 050/2
1 200/2
1 400/2
1 400/2
1 400/2
1 200/3
1 400/3
1 400/3
ii)
4
1 200/1
1 400/1
1 200/2
1 200/2
1 200/2
1 400/2
1 400/2
1 500/2
1 200/3
1 400/3
1 500/3
iii)
5
1 400/1
1 400/1
1 400/2
1 400/2
1 400/2
1 400/2
1 400/2
1 500/2
1 400/3
1 400/3
1 500/3
iv)
6
1 200/2
1 400/2
900/4
1 050/4
1 200/4
1 400/4
1 400/4
1 500/4
1 200/6
1 400/6
1 500/6
v)
7
1 200/2
1 400/2
1 050/4
1 050/4
1 200/4
1 400/4
1 400/4
1 500/4
1 200/6
1 400/6
1 500/6
vi)
8
1 200/2
1 400/2
1 200/4
1 200/4
1 200/4
1 400/4
1 400/4
1 500/4
1 200/6
1 400/6
1 500/6
vii)
9
1 400/2
1 400/2
1 400/4
1 400/4
1 400/4
1 400/4
1 400/4
1 500/4
1 400/6
1 400/6
1 500/6
viii)
10
1 400/2
1 400/2
1 400/4
1 400/4
1 400/4
1 400/4
1 400/4
1 500/4
1 400/6
1 400/6
1 500/6
ix)
11
1 500/2
1 500/2
1 500/4
1 500/4
1 500/4
1 500/4
1 500/4
1 500/4
1 500/6
1 500/6
1 500/6
x)
12
1 200/3
1 400/3
1 200/6
1 200/6
1 200/6
1 400/6
1 400/6
1 500/6
1 200/7
1 400/9
1 400/9
xi)
13
1 400/3
1 400/3
1 200/6
1 200/6
1 200/6
1 400/6
1 400/6
1 500/6
1 400/9
1 400/9
1 500/9
xii)
14
1 400/3
1 400/3
1 400/6
1 400/6
1 400/6
1 400/6
1 400/6
1 500/6
1 400/9
1 400/9
1 500/9
5.4Natural Ventilation
The rate of ventilation by natural means through windows or other openings depends on,
a) direction and velocity of wind outside and sizes and disposition of openings (wind action); and
b) convection effects arising from temperature of vapour pressure difference (or both)
between inside and outside the room and the difference of height between the outlet and inlet openings (stack effect).
5.4.1 Ventilation of Non-Industrial Buildings
Ventilation in non-industrial buildings due to stack effect, unless there is a significant internal load, could be neglected, except in cold regions, and wind action may be assumed to be predominant.
5.4.1.1 In hot dry regions, the main problem in summer is to provide protection from sun's heat so as to keep the indoor temperature lower than those outside under the sun. For this purpose windows and other openings are generally kept closed during day time and only minimum ventilation is provided for the control of odours or for removal of products of combustion.
5.4.1.2 In warm humid regions, the problem in the design of non-industrial buildings is to provide free passage of air to keep the indoor temperature as near to those outside in the shade as possible, and for this purpose the buildings are oriented to face the direction of prevailing winds and windows and other openings are kept open on both windward and leeward sides.
5.4.1.3 In winter months in cold regions, the windows and other openings are generally kept shut, particularly during night; and ventilation necessary for the control of odours and for the removal of products of combustion can be achieved either by stack action or by some infiltration of outside air due to wind action.
5.4.2 Ventilation of Industrial Buildings
In providing natural ventilation of all industrial buildings having significant internal heat loads due to manufacturing process, proper consideration should be given to the size and distribution of windows and other inlet openings in relation to outlet openings so as to give, with due regard to orientation, prevailing winds, size and configuration of the building and manufacturing processes carried on, maximum possible control of thermal environment.
5.4.2.1 In the case of industrial buildings wider than 30 m, the ventilation through windows may be augmented by roof ventilation.
5.4.3 Design Guidelines for Natural Ventilation
5.4.3.1 By wind action
A building need not necessarily be oriented perpendicular to the prevailing outdoor wind; it may be oriented at any convenient angle between 0° and 30° without losing any beneficial aspect of the breeze. If the prevailing wind is from East or West, building may be oriented at 45° to the incident wind so
as to diminish the solar heat without much reduction in air motion indoors.
Inlet openings in the buildings should be well distributed and should be located on the windward side at a low level, and outlet openings should be located on the leeward side. Inlet and outlet openings at high levels may only clear the top air at that level without producing air movement at the level of occupancy.
Maximum air movement at a particular plane is achieved by keeping the sill height of the opening at 85 percent of the critical height (such as head level) for the following recommended levels of occupancy:
a) For sitting on chair 0.75m,
b) For sitting on bed 0.60m, and
c) For sitting on floor 0.40m.
Inlet openings should not as far as possible be obstructed by adjoining buildings, trees, sign boards or other obstructions or by partitions inside in the path of air flow.
In rooms of normal size having identical windows on opposite walls the average indoor air speed increases rapidly by increasing the width of window up to two-third of the wall width; beyond that the increase is in much smaller proportion than the increase of the window width. The air motion in the working zone is maximum when window height is 1.1m. Further increase in window height promotes air motion at higher level of window, but does not contribute additional benefits as regards air motion in the occupancy zones in buildings.
Greatest flow per unit area of openings is obtained by using inlet and outlet openings of nearby equal areas at the same level.
FIG. 6 EFFECT OF AREA OF OPENING ON AVERAGE INDOOR WIND VELOCITY
For a total area of openings (inlet and outlet) of 20 percent to 30 percent of floor area, the average indoor wind velocity is around 30 percent of outdoor velocity. Further increase in window size increases the available velocity but not in the same proportion as shown in Fig. 6. In fact, even under most favourable conditions the maximum average indoor wind speed does not exceed 40 percent of outdoor velocity.
Where the direction of wind is quite constant and dependable, the size of the inlet should be kept within 30 to 50 percent of the total area of openings and the building should be oriented perpendicular to the incident wind. Where direction of the wind is quite variable the openings may be arranged so that as far as possible there is approximately equal area on all sides. Thus no matter what the wind direction be, there would be some openings directly exposed to wind pressure and others to air suction and effective air movement through the building would be assured.
Windows of living rooms should open directly to an open space. In places where building sites are restricted, open space may have to be created in the buildings by providing adequate courtyards.
In the case of rooms with only one wall exposed to outside, provision of two windows on that wall is preferred to that of a single window.
Windows located diagonally opposite to each other with the windward window near the upstream corner give better performance than other window arrangements for most of the building orientations.
Horizontal louvers, that is, sunshades atop windows deflect the incident wind upward and reduce air motion in the zone of occupancy. A horizontal slot between the wall and horizontal louver prevents upward deflection of air in the interior of rooms. Provision of inverted L type ( ) louver increases the room air motion provided that the vertical projection does not obstruct the incident wind (see Fig. 7).
Provision of horizontal sashes inclined at an angle of 45° in appropriate direction helps to promote the indoor air motion. Sashes projecting outward are more effective than projecting inward.
Air motion at working plane 0.4 m above the floor can be enhanced by 30 percent using a pelmet type wind deflector (see Fig. 8).
Roof overhangs help promoting air motion in the working zone inside buildings.
In case of room with windows on one wall, with single window, the room wind velocity inside the room on the windward side is 10 percent of outdoor velocity at points up to a distance of one-sixth of room width from the window and then decreases rapidly and hardly any air movement is produced in the leeward half portion of the room. The average indoor wind velocity is generally less than 10 percent of outdoor velocity. When two windows are provided and wind impinges obliquely on them, the inside velocity increases up to 15 percent of the outdoor velocity.
Cross ventilation can be obtained through one side of the building to the other, in case of narrow buildings with the width common in the multistoreyed type by the provision of large and suitably placed windows or combination of windows and wall ventilators for the inflow and outflow of air.
Verandah open on three sides is to be preferred since it causes an increase in the room air motion for most of the orientations of the building with respect to the outdoor wind.
A partition placed parallel to the incident wind has little influence on the pattern of the air flow, but when located perpendicular to the main flow, the same partition creates a wind shadow. Provision of a partition with spacing of 0.3 m underneath helps augmenting air motion near floor level in the leeward compartment of wide span buildings.
Air motion in a building unit having windows tangential to the incident wind is accelerated when another unit is located at end-on position on downstream side (see Fig. 9).
Air motion in two wings oriented parallel to the prevailing breeze is promoted by connecting them with a block on downstream side.
FIG. 8 SKETCH OF A PELMET TYPE WIND DEFLECTOR
FIG. 9 TWO UNITS LOCATED AT THE END-ON POSITION
Air motion in a building is not affected by constructing another building of equal or smaller height on the leeward side; but it is slightly reduced if the leeward building is taller than the windward block.
Air motion in a shielded building is less than that in an unobstructed building. To minimise shielding effect, the distances between two rows should be 8 H for semi-detached houses and 10 H for long rows houses. However, for smaller spacing the shielding effect is also diminished by raising the height of the shielded building.
Hedges and shrubs defect the air away from the inlet openings and cause a reduction in indoor air motion. These elements should not be planted at a distance of about 8 m from the building because the induced air motion is reduced to minimum in that case. However, air motion in the leeward part of the building can be enhanced by planting a low hedge at a distance of 2 m from the building.
Trees with large foliage mass having trunk bare of branches up to the top level of window, deflect the outdoor wind downwards and promotes air motion in the leeward portion of buildings,
Ventilation conditions indoors can be ameliorated by constructing buildings on earth
mound having a slant surface with a slope of 10° on upstream side.
In case of industrial buildings the window height should be about 1.6 m and width about two-third of wall width. These should be located at a height of 1.1 m above the floor. In addition to this, openings around 0.9 m high should be provided over two-third length of the glazed area in the roof lights.
Height of industrial buildings, although determined by the requirements of industrial processes involved, generally kept large enough to protect the workers against hot stagnant air below the ceiling as also to dilute the concentration of contaminant inside. However, if high level openings in roof or walls are provided, building height can be reduced to 4 m without in any way impairing the ventilation performance.
The maximum width up to which buildings of height usually found in factories, being effectively ventilated by natural means by wind action, is 30 m, beyond which sufficient reliance cannot be placed on prevailing winds. Approximately half the ventilating area of openings should be between floor level and a height of 2.25 m from the floor.
NOTE — For data on outdoor wind speeds at a place, reference may be made to ‘The Climatic Data Handbook’ prepared by Central Building Research Institute, Roorkee, 1999’.
5.4.3.2 By stack effect
Natural ventilation by stack effect occurs when air inside a building is at a different temperature than air outside. Thus in heated buildings or in buildings wherein hot processes are carried on and in ordinary buildings during summer nights and during pre-monsoon periods, the inside temperature is higher than that of outside, cool outside air will tend to enter through openings at low level and warm air will tend to leave through openings at high level. It would, therefore, be advantageous to provide ventilators as close to ceilings as possible. Ventilators can also be provided in roofs as, for example, cowl, vent pipe, covered roof and ridge vent.
5.5 Mechanical Ventilation
The requirements of mechanical ventilation shall be in accordance with Part 8 ‘Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation’ of the Code.
Annex A(Clause 3.4.1) Method of Calculating Solar Load on Vertical Surfaces of Different Orientation
A-1 Details of Calculation
A-1.1 The solar energy above the earth's atmosphere is constant and the amount incident on unit area normal to sun's rays is called solar constant (1.360 8 kWm⁻² or 2 cal/cm²/min). This energy, in reaching the earth's surface, is depleted in, the atmosphere due to scattering by air molecules, water vapour, dust particles, and absorption by water vapour and ozone. The depletion varies with varying atmospheric conditions. Another important cause of depletion is the length of path traversed by sun's rays through the atmosphere. This path is the shortest when sun is at the zenith and, as the altitude of the sun decreases, the length of path in the atmosphere increases. Figure 11 gives the computed incident solar energy/hour on unit surface area normal to the rays under standard atmospheric conditions (see Note below) for different altitudes of the sun.
NOTE — The standard atmospheric conditions assumed for this computation are: cloud-free, 300 dust particles per cm ³ , 15 mm of precipitable water, 2.5 mm of ozone, at sea level.
A-1.2 In order to calculate the solar energy on any surface other than normal to the rays, the altitude of the sun at that time should be known. The corresponding value of direct solar radiation ( IN ) should then be found with the help of Fig. 12. The solar radiation incident on any surface ( IS ) is given by:
IS=IN(sinβsinϕ+cosβcosαcosϕ)
where
β = solar altitude,
φ = angle tilt of the surface from the vertical (see Fig. 12), and
α = wall solar azimuth angle.
A-2 EXAMPLE TO FIND OUT ORIENTATION ON THE BASIS OF SOLAR LOAD
A-2.1 Example
A-2.1.1 As an example, a simple building with flat roof, 10 m × 20 m , and 4 m high is dealt with below. For the sake of generalization, no shading device or verandah is taken.
A-2.1.2 As the roof is horizontal, it will receive the same solar heat in any orientation.
A-2.1.3 The area of the vertical surfaces are 4 m × 10 m = A (say) and 4 m × 20 m = 2A . Since, the external wall surface are not in shade except when the sun is
FIG. 11 DIRECT SOLAR INTENSITIES NORMAL TO SUN AT SEA LEVEL FOR STANDARD CONDITION (COMPUTED)
FIG. 12 DEFINITION OF SOLAR ANGLES
not shining on them, the total solar load in a day on a surface can be obtained by multiplying the total load per unit area per day (see Table 3) by the area of the surface. For four principal orientations of the building, the total solar load on the building is worked out in Table 14.
A-2.1.4 From Table 14, it can be seen that for the above type of building, orientation 3 (longer surface facing North and South) is appropriate as it affords maximum solar heat gain in winter and in summer. This is true for all places of India from the point of solar heat gain. By further increasing the length to breadth ratio, the
bok Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63,84.35) valid up
Table 14 Solar Heat Gained Due to Orientation of Buildings(Clause A-2.1.3)
8° N THIRUVANANTHAPURAM
13° N CHENNAI
May 16
Dec 22
May 16
Dec 22
1.
North
2 177 × A = 2 177A
—
1 625 × A = 1 625A
—
East
2 618 × 2A = 5 236A
2 177 × 2A = 4 354A
2 697 × 2A = 5 394A
2 019 × 2A = 4 038A
South
—
4 164 × A = 4 164A
—
4 385 × A = 4 385A
West
2 618 × 2A = 5 236A
2 177 × 2A = 4 354A
2 697 × 2A = 5 394A
2 019 × 2A = 4 038A
B-1.6.2 Example
It is desired to calculate the sky component due to a vertical window ABCD with width 1.8 m and height 1.5 m at a point P on a horizontal plane 3.0 m from the window wall located as shown in the Fig. 14. Foot of the perpendicular N is 0.6 m below the sill and 0.9 m to the left of AD.
Since ABCD = NB ′ CD ′ - NA ′ DD ′ - NB ′ BA ′ + NA ′ AA ′
Sky Component,F=F1−F2−F
B-2 General Instructions
B-2.1 For irregular obstructions like row of trees parallel to the plane of the window, equivalent straight boundaries horizontal and vertical, may be drawn.
B-2.2 For extremely irregular obstruction or obstructions not in a plane parallel to the window, diagrammatic methods, such as Waldrams diagrams may have to be employed.
B-2.3 For bay windows, dormer windows or corner windows the effective dimensions of window opening computed should be taken when using the tables to find the sky components.
Plate/strip inspection
300-500-700
2
4.3.6
Inspection of tin plate, stainless steel, etc
-
-
Special lighting to reveal faults in the specular surface of the material will be required
4.4
Foundries
4.4.1
Automatic plant
4.4.1.1
Without manual operation
30-50-100
3
4.4.1.2
With occasional manual operation
100-150-200
3
4.4.1.3
With continuous manual operation
150-200-300
3
4.4.1.4
Control room
200-300-500
1
Localized lighting of the control display and the control desks may be appropriate
The lighting should be designed to create an appropriate atmosphere
20.5.4
Cloak rooms, baggage rooms
50-100-150
3
20.5.5
Bed rooms
30-50-100
Supplementary local lighting at the bed head, writing table should be provided
20.5.6
Bathroom
50-100-150
Supplementary local lighting near the mirror is desirable
20.5.7
Food preparation and stores, cellars, lifts and corridors
See 'General Building Areas'
20.6
Libraries
20.6.1
Lending library
20.6.1.1
General
200-300-500
1
20.6.1.2
Counters
300-500-750
1
Localized lighting may be appropriate.
20.6.1.3
Bookshelves
100-150-200
2
The service illuminance should be provided on the vertical face at the bottom of the bookstack
20.6.1.4
Reading rooms
200-300-500
1
20.6.1.5
Reading tables
200-300-500
1
Localized lighting may be appropriate
20.6.2
Catalogues
20.6.2.1
Card
100-150-200
2
20.6.2.2
Microfiche/Visual display units
100-150-200
2
20.6.3
Reference libraries
20.6.3.1
General
200-300-500
1
20.6.3.2
Counters
300-500-750
1
Localized lighting may be appropriate.
200-300-500
3
21.1.2
Platform and stage
Special lighting to provide emphasis and to facilitate the use of the platform/ stage is desirable
21.2
Teaching Spaces
General
200-300-500
1
21.3
Lecture Theatres
21.3.1
General
200-300-500
1
21.3.2
Demonstration benches
300-500-750
1
Localized lighting may be appropriate
21.4
Seminar Rooms
300-500-750
1
21.5
Art Rooms
300-500-750
1
21.6
Needlework Rooms
300-500-750
1
21.7
Laboratories
300-500-750
1
21.8
Libraries
200-300-500
1
21.9
Music Rooms
200-300-500
1
21.10
Sports Halls
200-300-500
1
21.11
Workshops
200-300-500
1
22
TRANSPORT
22.1
Airports
22.1.1
Ticket counters, checking desks, and information desks
300-500-750
2
Localized lighting may be appropriate
22.1.2
Departure lounges, other waiting areas
150-200-300
2
22.1.3
Baggage reclaim
150-200-300
2
22.1.4
Baggage handling
50-100-150
2
22.1.5
Customs and immigration halls
300-500-750
2
22.1.6
Concourse
150-200-300
2
22.2
Railway Stations
22.2.1
Ticket office
300-500-750
2
Localized lighting may be appropriate
22.2.2
Information office
300-500-750
2
Localized lighting over the counter may be appropriate
22.2.3
Parcels office, left
22.2.4
Luggage office
22.2.4.1
General
50-100-150
2
22.2.4.2
Counter
150-200-300
2
22.2.5
Waiting rooms
150-200-300
2
22.2.6
Concourse
150-200-300
2
23.2.3
Escalators, revelators
100-150-200
23.3
Medical and First Aid Centres
23.3.1
Consulting rooms, treatment rooms
300-500-750
1
23.3.2
Rest rooms
100-150-200
1
23.3.3
Medical stores
100-150-200
2
23.4
Staff Rooms
23.4.1
Changing, locker and cleaners rooms, cloakrooms, lavatories
50-100-150
23.4.2
Rest rooms
100-150-200
1
23.5
Staff Restaurants
23.5.1
Canteens, cafeterias, dining rooms, mess rooms
150-200-300
2
23.5.2
Servery, vegetable preparation, washing-up area
200-300-500
2
23.5.3
Food preparation and cooking
300-500-750
2
23.5.4
Food stores, cellars
100-150-200
2
23.6
Communications
23.6.1
Switchboard rooms
200-300-500
2
23.6.2
Telephone apparatus rooms
100-150-200
2
23.6.3
Telex room, post room
300-500-750
2
23.6.4
Reprographic room
200-300-500
2
23.7
Building Services
23.7.1
Boiler houses
23.7.1.1
General
50-100-150
3
23.7.1.2
Boiler front
100-150-200
3
23.7.1.3
Boiler control room
200-300-500
2
Localized lighting of the control display and the control desk may be appropriate
23.7.1.4
Control rooms
200-300-500
2
Localized lighting of the control display and the control desk may be appropriate
23.7.1.5
Mechanical plant room
100-150-200
2
23.7.1.6
Electrical power supply and distribution rooms
100-150-200
2
23.7.1.7
Store rooms
50-100-150
3
23.8
Car Parks
23.8.1
Covered car parks
23.8.1.1
Floors
5-20
23.8.1.2
Ramps and corners
30
23.8.1.3
Entrances and exits
50-100-150
23.8.1.4
Control booths
150-200-300
23.8.1.5
Outdoor car parks
5-20
NOTE — For details on use of the ranges of illumination given in three steps in this table, reference shall be made to 4.1.4.2, 4.1.4.2.1 and 4.1.4.2.2. For details on quality class of direct glare limitation, reference shall be made to 4.1.3.1.
Total
12 649A
12 872A
12 413A
12 461A
2.
NE
2 650 × A = 2 650A
410 × A = 410A
2 492 × A = 2 492A
315 × A = 315A
SE
1 167 × 2A = 2 334A
3 391 × 2A = 6 782A
1 341 × 2A = 2 682A
3 423 × 2A = 6 846A
SW
1 167 × 2A = 2 334A
3 391 × A = 3 391A
1 341 × A = 1 341A
3 423 × A = 3 423A
NW
2 650 × 2A = 5 300A
410 × 2A = 820A
2 492 × A = 4 984A
315 × 2A = 630A
Total
12 618A
11 403A
11 499A
11 214A
3.
North
2 177 × 2A = 4 354A
—
1 625 × 2A = 3 250A
—
East
2 618 × A = 2 618A
2 177 × A = 2 177A
2 697 × A = 2 697A
2 019 × A = 2 019A
South
—
4 164 × 2A = 8 328A
—
4 385 × 2A = 8 770A
West
2 618 × A = 2 618A
2 177 × A = 2 177A
2 697 × A = 2 697A
2 019 × A = 2 019A
Total
9 590A
12 602A
8 644A
12 808A
4.
NE
2 650 × 2A = 5 300A
—
2 492 × A = 4 984A
315 × 2A = 630A
SE
1 167 × A = 1 167A
2 177 × A = 2 177A
1 341 × A = 1 341A
3 423 × A = 3 423A
SW
1 167 × 2A = 2 334A
4 164 × 2A = 8 328A
1 341 × 2A = 2 682A
3 423 × 2A = 6 846A
NW
2 650 × A = 2 650A
2 177 × A = 2 177A
2 492 × A = 2 492A
315 × A = 315A
Total
11 451A
12 682A
11 499A
11 214A
19° N MUMBAI
23° N KOLKATA
May 16
Dec 22
May 16
Dec 22
1.
North
962 × A = 962A
—
741 × A = 741A
—
East
2 795 × 2A = 5 590A
1 830 × 2A = 3 660A
2 871 × 2A = 5 742A
1 703 × 2A = 3 406A
South
—
4 574 × A = 4 574A
205 × A = 205A
4 637 × A = 4 637A
West
2 795 × 2A = 5 590A
1 830 × 2A = 3 660A
2 871 × 2A = 5 742A
1 703 × 2A = 3 406A
Total
12 142A
11 894A
12 430A
11 449A
2.
NE
2 255 × A = 2 255A
237 × A = 237A
2 192 × A = 2 192A
173 × A = 173A
SE
1 640 × 2A = 3 280A
3 438 × 2A = 6 876A
1 845 × 2A = 3 690A
3 454 × 2A = 6 908A
SW
1 640 × A = 1 640A
3 438 × A = 3 438A
1 845 × A = 1 845A
3 454 × A = 3 454A
NW
2 255 × 2A = 4 510A
237 × 2A = 474A
2 192 × 2A = 4 384A
173 × 2A = 346A
Total
11 685A
11 025A
12 111A
10 881A
3.
North
962 × 2A = 1 924A
—
741 × 2A = 1 482A
—
East
2 795 × A = 2 795A
1 830 × A = 1 830A
2 871 × A = 2 871A
1 703 × A = 1 703A
South
—
4 574 × 2A = 9 148A
205 × 2A = 410A
4 637 × 2A = 9 274A
West
2 795 × A = 2 795A
1 830 × A = 1 830A
2 871 × A = 2 871A
1 703 × A = 1 703A
Total
7 514A
12 808A
7 634A
12 680A
4.
NE
2 255 × 2A = 4 510A
237 × 2A = 474A
2 192 × 2A = 4 384A
173 × 2A = 346A
SE
1 640 × A = 1 640A
3 438 × A = 3 438A
1 845 × A = 1 845A
3 454 × A = 3 454A
SW
1 640 × 2A = 3 280A
3 438 × 2A = 6 876A
1 845 × 2A = 3 690A
3 454 × 2A = 6 908A
NW
2 255 × A = 2 255A
237 × A = 237A
2 192 × A = 2 192A
173 × A = 173A
Total
11 685A
11 025A
12 111A
10 881A
Table 14(Concluded)
29° N DELHI
May 16
Dec 22
1.
North
536 × A = 536A
—
East
2950 × 2A = 5900A
1467 × 2A = 2934A
South
741 × A = 741A
4543 × A = 4543A
West
2950 × 2A = 5900A
1467 × 2A = 2934A
Total
13077A
10411A
2.
NE
2098 × A = 2098A
110 × A = 110A
SE
2192 × 2A = 4384A
3265 × 2A = 6530A
SW
2192 × A = 2192A
3265 × A = 3265A
NW
2098 × 2A = 4196A
110 × 2A = 220A
Total
12870A
10125A
3.
North
536 × 2A = 1072A
—
East
2950 × A = 2950A
1467 × A = 1467A
South
741 × 2A = 1482A
4543 × 2A = 9086A
West
2950 × A = 2950A
1467 × A = 1467A
Total
8454A
12020A
4.
NE
2098 × 2A = 4196A
110 × 2A = 220A
SE
2192 × A = 2192A
3265 × A = 3265A
SW
2192 × 2A = 4384A
3265 × 2A = 6530A
NW
2098 × A = 4196A
110 × A = 110A
Total
12870A
10125A
advantage of this orientation will be more pronounced. It may also be noted that in higher altitudes, the relative merit of this orientation is more.
A-2.1.5 It is also seen that the total solar heat on the building is the same for orientation 2 and 4. But if the site considerations require a choice between these two, orientation 2 should be preferred at places north of latitude 23° N and orientation 4 at southern places. This is so because the total solar load per unit area in summer on the north western wall decreases with the increase
TYPE I
TYPE II
TYPE IV
in latitude and that on the south western wall increases. It would, therefore, be advantageous to face only smaller surface of the building to greater solar load in the summer afternoons, when the air temperature also is higher.
A-2.1.6 At hill stations, winter season cause more discomfort and so sole criterion for optimum orientation should be based on receiving maximum solar energy on building in winter.