1.1 This Part 11 covers the parameters required to be considered for planning, design, construction, operation and maintenance of buildings and those relating to land development, from sustainability point of view.
1.2 This Part of the Code is a supplement to all other Parts/Sections of the Code and shall be read along with the same.
1.3 For all buildings and facilities open to and used by the public, including all forms of public housing by the government/civic bodies and private developers, barrier free access and movement within and around buildings, for persons with disabilities and of different age groups, shall be ensured in accordance with Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
Part 11Approach to Sustainability
BUREAU OF INDIAN STANDARDS
FOREWORD
... 3
1 SCOPE
... 7
2 TERMINOLOGY
... 7
3 APPROACH TO SUSTAINABILITY
... 10
4 APPLICABILITY OF THIS PART
... 13
5 IMPLEMENTATION OF THIS PART
... 13
6 SITING, FORM AND DESIGN
... 13
7 EXTERNAL DEVELOPMENT AND LANDSCAPE
... 15
8 ENVELOPE OPTIMIZATION
... 23
9 MATERIALS
... 38
10 WATER AND WASTE MANAGEMENT
... 53
11 BUILDING SERVICES OPTIMIZATION
... 61
12 CONSTRUCTIONAL PRACTICES
... 75
13 COMMISSIONING, OPERATION, MAINTENANCE AND BUILDING PERFORMANCE TRACKING
... 82
ANNEX A DESIGN STRATEGIES AS PER CLIMATE ZONES FOR VARIOUS SEASONS
... 85
ANNEX B PRESCRIPTIVE METHOD FOR ENVELOPE OPTIMIZATION
... 87
ANNEX C TRADE-OFF METHOD FOR ENVELOPE OPTIMIZATION
... 88
ANNEX D WHOLE BUILDING ANALYSIS METHOD FOR ENVELOPE OPTIMIZATION
... 90
LIST OF STANDARDS
... 94
This Code (Part 11) covers the parameters required to be considered for planning, design, construction, operation and maintenance of buildings and those relating to land development, from the point of view of sustainability.
From the dawn of civilization, our ancestors were concerned with preservation and sustenance of environment. The ancient Vedas have several references in them on environmental protection, ecological balance, weather cycle, rainfall phenomenon, hydrological cycle and related subjects. Seers, even at those times, recognized that changes caused due to indiscreet human activities could result in imbalances in seasons, rainfall patterns, crops and atmosphere and degrade the quality of water, air, and earth resources. Basham, in ‘The Wonder that was India’, describes how palaces in Mauryan dynasty in second century B.C., were exquisitely built from carved wood of local deodars. In later years the monasteries, temples and dharmashalas were built with locally available stones and these have withstood the ravages of time. Edwin Arnold, in ‘The Light of Asia’, describes Vishramvan, the palace built with local marble and alabaster for prince Siddharth. The epic Mahabharata describes palace built by Vishwakarma. Kashi Vishwanath Temple in Varanasi was built more than a thousand years ago. Many other ancient monuments in various parts of India are classic examples of sustainable buildings.
The Taj Mahal, built more than four hundred years ago, can accommodate hundreds of people with no suffocation, as the stone jalis in the facia induce air movement and enable natural ventilation. The fort in Mandu has elaborate rainwater harvesting techniques. Havelis in northern India were invariably built around a central courtyard, which brought daylight to all nooks and corners, but the heat was kept out. Many forts and havelis have elaborate provision for evaporative cooling, using khas-screens and rainwater stored at higher plateaus. Sustainability and sustainable buildings have been the way of life in India.
It was not just palaces, monasteries and temples that were built on the platform of sustainable practices. The awareness was innate and intuitive, guided by a clear understanding of nature and driven by total alignment with environment, with the resolve not to harm nature but to respect and revere it, and to live in harmony with it. A reflection of this is visible in the locally evolved climate-responsive architecture that blended with social and cultural mores, leaving behind lasting concepts of building forms and human settlements. These buildings provided comfort to the occupants. They were passive in approach with no external intervention, which in modern times have become quite desirable. Diverse climatic conditions in our country resulted in evolution of different fabrics of built form, with the commonality being the focus on harmony with nature. It becomes obvious to see why all the scriptures, literature, life styles and cultural ethos made reference to the Panchabhoothas, which represent five elements of nature, thus blending the architecture and habitats with nature. Thus, sustainability, and sustainable buildings have been the way of life in India.
Less than a hundred years ago, industrial revolution came to India and changed many of these traditional sustainable practices in Indian buildings. The insatiable thirst for progress and comfort at any cost, altered the equation with nature forever. Concrete, steel, glass and later plastics became the dominant construction materials, beyond stone and wood of yesteryears. Power supply, artificial lighting, water supply and disposal, and thermal environmental control within built environment, were desired and obtained.
The new civilizations grew along the river banks, always regarding rivers as sacred. With the industrial revolution, untreated water, effluents from chemical industries and organic waste were discharged into rivers and water bodies, destroying our precious sources of water for domestic use. In addition, the unsustainable development and usage of buildings have led to huge construction and demolition waste, and municipal solid waste during their operation, which today have become a major problem.
Modern buildings in India consume about 25 to 30 percent of total energy, and up to 30 percent of fresh potable water, and generate approximately 40 percent of total waste. India is now entering the phase of rapid urbanization. Various studies indicate that by 2050, the built up area of India may become four times the current mass, which may pose a major challenge in preserving our fragile environment. Although the present energy consumption per
capita in India is a fraction of that of most developed nations, but with its projected growth, unless enough measures are taken, it may lead to acceleration of environment degradation, contributing to increased carbon footprint leading to global warming and climate change, resource scarcity and inequitable development.
Sustainable buildings have demonstrated reduction in energy and water consumption to less than half of the present consumption in conventional buildings and complete elimination of the construction and operational waste through recycling. The Indian way of life is Aparigraha (minimum possession), conservation (minimum consumption) and recycling (minimum waste). These three attributes are the guiding principles for sustainable buildings as well. With these attributes and its rich heritage, India can make a substantial contribution in this field and eventually lead the world on the path of sustainability.
Developed nations' approach to sustainability generally concentrates on energy efficiency through high technology innovations, and use of products, materials and designs with lower embodied energy. Their green ratings are based on intent, which implies expert inputs and simulation which often can be counter intuitive such as the envisaged load and effective use of energy efficient appliance. Indian construction industry will do better through use of products, materials and designs with lower embodied energy and our traditional wisdom and practices, building in harmony with nature through regional common knowledge, consuming as little as necessary, applying low cost technology innovations, using recycled materials, and recognizing performance (not intent) through easily measurable parameters, wherever feasible. If required, the above approach may be supplemented with an appropriate blend of the emerging and sustainable technology innovations. It is particularly emphasized that the hazard of construction and demolition waste should be properly attended to in view of increased construction and redevelopment activities in the country anticipated in future. This would require that such waste is preferably used at site and the balance, if any, may be sent to recycling plant which is closest to the site.
The Sectional Committee, reviewed the contents of the 2005 version of the Code and observed that due consideration had been given to these important dimensions in building planning, design and construction and during operation through provisions of effective utilization of natural light and ventilation; increased use of renewable energy, material selection including recyclability and reusability aspects; use of low gestation plantations and agriculture and industrial wastes; design approach; proper management practices; efficient electrical and other building services and plumbing services; energy conservation; rainwater harvesting, etc. All these have been duly interwoven throughout the Code addressing both the embodied energy and the operational energy involved, as also showing sensitivity towards the concerns such as ozone depletion, global warming, etc. The Committee, however, felt that in keeping with the present needs as well as likely future scenario, it might be appropriate to completely review all such aspects and give them a special and separate identity in the form of Part of the Code covering approach to sustainability relating to buildings and built environment. Aiming towards such objectives, the Sectional Committee first formulated this Part and incorporated in the 2005 version of the Code through Amendment No. 1 to the Code.
This revision has been taken up to further review this Part and update it particularly in view of the modifications being incorporated in other Parts/Sections in this revision of the Code, to bring coherence among the provisions of this Part and other revised Parts/Sections. The significant modifications incorporated in this revision are:
a) Inclusion of definitions of a number of additional terms such as surface coefficient, surface resistance, thermal transmission and total thermal resistance.
b) Greater emphasis on ensuring barrier free design for universal accessibility, as part of approach to sustainability.
c) Review of provisions on materials and technologies for sustainability and their updating, wherever required.
d) Inclusion of guidelines for selection of window types.
e) Modification of the clause on refrigerants for air conditioning to include refrigerants, considering sustainability aspects.
f) Inclusion of provision for preparation of overall water balance chart, as part of water and waste management.
This Part of the Code provides a comprehensive set of requirements, intended to reduce the negative impact of buildings on the natural environment. It can be readily used by the owners, developers/builders, architects, engineers, building services engineers and other building professionals as well as by manufacturers of building materials apart from the Authorities concerning land and building development, government and private construction agencies and academic and research institutions. The intent of this Part of the Code is to highlight sustainability measures including those referred to in different Parts/Sections of the Code as may be required as well as to define
4
comprehensive sustainability standards for the building construction and related built environment.
The approach to sustainability is founded on principles consistent with this Code, to adequately protect public health, safety and welfare and to provide requirements that do not unnecessarily increase construction cost nor restrict the use of new / innovative materials, products or methods of construction. The benefits of incorporating measures listed in this Part are not only environment friendly, but also result in much better health and productivity of occupants, at minimal additional initial cost over the cost of conventional buildings, while substantially reducing the life cycle cost. This minimal additional cost is offset during a few years usage of the buildings, and vast advantage in cost is accrued during the life cycle of the building.
The measures of sustainable buildings described in this Part, set performance thresholds and incorporate features that allow Authority to customize requirements according to local geographical conditions, environmental priorities and agenda. These are not specific to any rating system and are not intended to provide a single metric indication of overall building performance. The flexibility of these provisions allows the practitioners to easily exercise their judgment in holistically and objectively applying the underlying principles of sustainability to a development or building facility, considering its functionality and required comfort level.
The provisions of this Part of the Code are without prejudice to the concerned statutory provisions including those given in various Acts and Rules and Regulations framed thereunder.
The information contained in this Part of the Code has been brought in coherence with the provisions contained in other parts of the Code, as also with the concerned Indian Standards on various areas. In the formulation of this Part, efforts have been made to take into cognizance the various latest applicable practices followed in the country and abroad, relevant to sustainability in buildings. This has been done by taking into consideration the publications of the American Society for Heating, Refrigeration, Air conditioning Engineers; American Society for Testing and Materials; Bureau of Energy Efficiency, India; Indian Green Building Council; Indian Society for Heating, Refrigeration, Air conditioning Engineers; International Organisation for Standardisation; and The Energy and Resources Institute, India.
All standards cross-referred to in the main text of this Part, are subject to the revision. The parties to agreement based on this Part are encouraged to investigate the possibility of applying the most recent editions of the standards.
For the purpose of deciding whether a particular requirement of this Part is complied with, the final value, observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS 2 : 1960 ‘Rules for rounding off numerical values (revised)’. The number of significant places retained in the rounded off value should be the same as that of the specified value in this Part of the Code.
Book Supply Bureau Under the License from BJS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.84.35) valid up NATIONAL BUILDING CODE OF INDIA
2Terminology
2.0 For the purpose of this Part of the Code, the definitions given below shall apply.
2.1 Adaptive Thermal Comfort — The comfort that relates indoor design temperatures or acceptable temperature ranges to outdoor meteorological and climatological parameters.
NOTE — The adaptive thermal comfort model refers to the concept of specifying indoor comfort temperature set points based on the physiological, behavioural and psychological measures that the occupants take, voluntarily or involuntarily, to adapt themselves to the thermal environment and achieve comfort.
2.2 Authority Having Jurisdiction — The Authority which has been created by a statute and which, for the purpose of the Code/Part, may authorize a committee or an official or an agency to act on its behalf; herein after called the ‘Authority’.
2.3 Biodiversity — The variability among living organisms from all sources including terrestrial, marine and other aquatic ecosystems and the ecological complexes of which they are a part; this includes diversity within species, between species, and of ecosystems.
2.4 Building Environment — The surrounding in which a building operates, including air, water, land, natural resources, flora, fauna, human beings and their inter-relations.
2.5 Building Performance — The ability of a building to fulfil required functions under intended use conditions or behaviour when in use.
2.6 Built Environment — The collection of man-made or induced physical objects located in a particular area or region.
NOTE — When treated as a whole, the built environment typically is taken to include buildings, external works (landscape areas), infrastructure and other construction works within the area under consideration.
2.7 Disaster — It is a catastrophe, mishap, calamity or grave occurrence in any area, arising from natural or man-made causes, or by accident or negligence which results in substantial loss of life, or human suffering or damage to, and destruction of, property or damage to or degradation of environment, and is of such a nature of magnitude as to be beyond the coping capacity of the community of the affected area.
2.8 Ecological Footprint — The impact of a person or community, expressed as the amount of land required to sustain their use of natural resources.
2.9 Ecosystem — The community of biological organisms and their physical environment, functioning together as an interdependent unit within a defined area.
NOTE — For the purpose of this definition, humans, animals, plants, and microorganisms are individually all considered biological organisms.
2.10 Embodied Energy — The sum total of energy that is used to extract, process, package, transport, and install the material in the building.
NOTE — Embodied energy data is often collected using input and output analysis.
2.11 Emissivity(E) — The ratio of rate of heat emitted by a surface as compared to that of an absolutely black surface under similar conditions. It varies with the temperature of the emitting surface.
2.12 Environmental Impact — Any change to the environment, whether adverse or beneficial, wholly or partially, resulting from environmental aspects of a built environment.
2.13 Green Roof System — An assembly that supports an area of planting/landscaping, built up on a waterproofed substrate at any level that is separated from the natural ground by a human made structure.
2.14 Heat Island Effect — A phenomenon in which air and surface temperature of an area are higher than nearby areas due to the replacement of natural land cover with pavement, building, and other infrastructure.
2.15 Horizontal Sun Angle (HSA) — The horizontal angle between the normal of the window and the sun azimuth angle at a given time (see Fig. 1).
FIG. 1 HORIZONTAL AND VERTICAL SOLAR ANGLE FORMULATION
2.16 Indoor Air Quality (IAQ) — The nature of indoor air that affects the health and well-being of building occupants.
2.17 Indoor Environment Quality (IEQ) — The condition or state of the indoor environment.
2.18 Life Cycle Assessment (LCA) — A method of evaluating a product by reviewing the ecological impact over the life of the product.
NOTE — At each stage, the product and its components are evaluated based upon the materials and energy consumed, and the pollution and waste produced. Life stages include extraction of raw materials, processing and fabrication, transportation, installation, use and maintenance, and reuse/recycling/disposal.
2.19 Light Shelf — An architectural element that allows daylight penetration in a building. It is usually a horizontal light-reflecting overhang on a window or opening and is placed above eye-level and has a high-reflectance upper surface. This surface reflects daylight onto the ceiling and deeper into a space.
2.20 Non-renewable Resource — A resource that exists in a fixed quantity that cannot be replenished on a human time scale.
NOTE — Non-renewable resources have the potential for renewal only by the geological, physical and chemical processes taking place over hundreds of millions of years. Non-renewable resources exist in various places in the earth's crust. Examples include iron ore, coal, and oil.
2.21 Renewable Resource — A resource that is available naturally, harnessed, and can be replenished.
NOTE — Sustainable use of renewable resource implies that the rate of replenishment, or cleansing takes place at a rate equal to or greater than the current rate of depletion of that resource. Examples include trees in forest, grasses in grassland, and fertile soil.
2.22 Reuse — Using a material, product or component of the waste stream in its original form more than once.
2.23 Recycling — A process to convert discarded
materials that would otherwise become waste, into valuable resources.
2.24 Skylight Roof Ratio (SRR) — The ratio of the total skylight area of the roof, measured to the outside of the frame, to the gross exterior roof.
2.25 Solar Heat Gain Coefficient (SHGC) — The fraction of incident solar radiation admitted through a fenestration, both directly transmitted, and absorbed and subsequently released inward through conduction, convection and radiation (see Fig. 2).
FIG. 2 MECHANISM OF SOLAR HEAT GAIN
2.26 Solar Reflectance Index (SRI) — A measure of material's ability to reject solar radiation, as shown by a small temperature rise.
NOTE — SRI of standard black surface (having reflectance of 0.05 and emittance of 0.9) and a standard white surface (of reflectance 0.8 and emittance 0.9) are taken as 0 and 100, respectively.
2.27 Surface Coefficient (f) — The thermal transmission by convection, conduction and radiation from unit area of the surface, for unit temperature difference between the surface and the surrounding medium. It is expressed in W/m²K.
NOTE — The value of f depends on many factors, such as, air or fluid movement in contact with the surface, roughness and emissivity of the surface and upon the temperature and nature of surroundings.
2.28 Surface Resistance (1/f) — The reciprocal of surface coefficient. It is expressed in m²K/W .
2.29 Sustainability — The state in which components of ecosystem and their functions are maintained for the present and future generations.
NOTES
1 Sustainability is the goal of sustainable development and can result from the application of the concept of sustainable development.
2 In building construction, it relates to how the attributes of the activities, materials/products or services used in construction work, or the use of construction works, contribute to the
8
maintenance of ecosystem components and functions for future generations.
3 While the challenge of sustainability is global, the strategies for sustainability in building construction are local and may differ in context and content from region to region.
4 ‘Components of ecosystem’ includes plants and animals, as well as humans and their physical environment. For humans, this includes a balancing of key elements of human needs namely the economic, environmental, social and cultural conditions for societies’ existence.
2.30 Sustainable Buildings — A building that meets the specified building performance requirements while minimizing disturbance to and improving the functioning of local, regional, and global ecosystem both during and after its construction and specified service life.
NOTE — A sustainable building optimizes efficiencies in resource management and operational performance; and, minimises risks to human health safety and the environment.
2.31 Sustainable Development — The development that meets the need of the present without compromising the ability of future generations to meet their own.
2.32 Thermal Absorptivity — A factor indicating the relative amount of radiation absorbed by a surface as compared to an absorbing black body under the same conditions. Its value is dependent upon the temperature of the source and of the receiving surface.
2.33 Thermal Capacity — The amount of heat necessary to raise the temperature of a given mass by 1° C. Numerically, the thermal capacity per unit area of surface is the sum of the products of the mass per unit area of each individual material in the roof, wall or floor surface multiplied by its individual specific heat.
2.34 Thermal Conductance (R) — The thermal transmission of a single layer structure per unit area divided by the temperature difference between the hot and cold faces. It is expressed in W/m² K.
NOTE — Thermal conductance is a measure of the thermal transmission per unit area through the total thickness of the structure under consideration. Thermal conductivity on the other hand refers to unit thickness of material. Further, this term applies only to a single layer of material and not to a composite insulation or to a structure made up of several layers of materials or medium.
2.35 Thermal Conductivity (k) — The quantity of heat in the steady state conditions flowing in unit time through a unit area of a slab of uniform material thickness of infinite extent and of unit thickness, when unit difference of temperature is established between its faces. Its unit is W/mK.
NOTE — Thermal conductivity is a characteristic property of a material and its value may vary with a number of factors, including density, porosity, moisture content, fibre diameter, pore size, type of gas in the material, mean temperature and outside temperature range. The conductivity value varies from
0.03 W/mK for insulators to 400 W/mK for metals. Materials with lower conductivity are preferred, as they are better insulators and reduce the external heat gains from the envelope or loss of internal heat to outside cold environment.
2.36 Thermal Comfort — That condition of mind which expresses satisfaction with the thermal environment and is assessed by subjective evaluation.
2.37 Thermal Reflectivity — The ratio of the reflected heat to that of the total heat incident on a surface at a certain mean temperature range.
2.38 Thermal Resistance (R) — The reciprocal of thermal conductance. For a structure having plane parallel faces, thermal resistance is equal to thickness (L) of the structure divided by thermal conductivity (k).
R=kL
NOTE — The usefulness of the quantity is that when heat passes in succession through two or more components of the building units, the resistance may be added together to get the total resistance of the structure.
2.39 Thermal Resistivity (1 / k) — The reciprocal of thermal conductivity. It is expressed in mK / W.
2.40 Thermal Transmission or Rate of Heat Flow (q) — The quantity of heat flowing in unit time under the conditions prevailing at that time. Its unit is W.
2.41 Thermal Transmittance (U) — Thermal transmission through unit area of the given building unit divided by the temperature difference between the air or other fluid on either side of the building unit in steady state conditions. It is also called as U-value. Its unit is W/m²K.
NOTE — Thermal transmittance differs from thermal conductance in so far as temperatures are measured on the two surfaces of a material or structure or building unit in the latter case and in the surrounding air or other fluid in the former case. Thermal conductance is a characteristic of the structure or building unit whereas thermal transmittance depends on conductance and surface coefficients of the structure or building unit under the conditions of use.
2.42 Total Thermal Resistance ( RT ) — It is the sum of the surface resistances and the thermal resistance of the building unit itself. It is expressed in m²K/W .
2.43 Tropical Summer Index (TSI) — The temperature of calm air at 50 percent relative humidity which imparts the same thermal sensation as the given environment. TSI (in °C) is expressed as:
T S I = 0. 7 4 5 t g + 0. 3 0 8 t w - 2. 0 6 √(v + 0 . 8 4 1)
where
t g = globe temperature, ° C;
tw = wet bulb temperature, °C; and
v = wind speed, m / s
2.44 Vertical Solar Angle (VSA) — The angle that a plane containing the bottom two points of the window and the centre of the sun makes with the ground when measured normal to the shaded surface (see Fig. 1).
2.45 Visual Light Transmittance (VLT) — The ratio of total transmitted light to total incident light.
2.46 Volatile Organic Compound (VOC) — The carbon compounds (excluding carbon monoxide, carbon dioxide, carbonic acid, metallic carbides or carbonates, and ammonium carbonate) which participate in atmospheric photochemical reactions. The compounds vapourize at normal room temperatures.
2.47 Waste — Substances or objects which the holder intends or is required to dispose of.
3Approach to Sustainability
3.1 Need for Sustainable Development
Building construction, occupancy and additions/alterations including preventive and remedial maintenance are always energy and material intensive. Large amount of primary form of natural materials, water, air, energy, etc, are consumed. The energy and material resources required for a building can be categorised as embodied energy, recurring operation energy, refurbishment energy, and end of life disposal. These elements and their use are inter-dependent. There is need for integrated approach of considering them all together in general design development and construction practice. However, conventional approach towards utilizing them is independent of each other and results in very low efficiency in material and resource use.
With increasing urbanization and rapid rise in people's economic level and consumption pattern in many parts of the country, there is an increasing trend to consume more natural resources per capita. This is evident from the aspirational lifestyles and resulting changing tastes and expenditure patterns of individuals and societies. This is equally witnessed from modern construction trends and changing sky lines of cities that bear no resemblance to local climate and resource availability. This is constantly putting tremendous pressure on fragile ecosystem by over-exploitation of natural resources adversely affecting biodiversity of our planet. Realizing this fact, there are efforts for a changing approach towards nature from ‘humanization of nature’ to ‘naturization of human’ and more recently towards sustainable development. The concept is to ensure that every living being on earth have equal opportunity to utilize the natural resources for survival and mutual sustenance.
To achieve this, it is important to accept the major challenge in controlling and judiciously using natural resources to shrink ecological footprint. The way to achieve this is by holistically planning our growth needs, one of which is construction and combining them with need based economy, but at the same time without compromising on functionality and essential comforts.
The basic components of building facility, their inter-relation, tradeoffs and effect on surrounding micro-climatic conditions have to be estimated, to achieve the harmony between buildings and ecological surroundings. Ideally a building should symbiotically fit within prevalent natural cycles. It is necessary to assess the association of various factors involved, rationalizing the impact of construction on neighbourhood and/or building micro-climatic conditions to discern sustainability in the built environment.
3.4Technology Options
The consequential building envelope to create harmonious development and productive living environment with neighbourhood and building environments poses one of the biggest challenges in selection of building materials, technologies and practices. It may be a combination of natural and manmade materials with least embodied energy and also leading to use of rapidly renewable resources. The trade-off between choice of the materials and technologies and their effect on environment has to be balanced with the aim of a closed-loop system. As a holistic approach, all efforts should be made towards,
a) encouraging and harnessing building materials out of agricultural, industrial and bio-wastes, which have an enormous scope for regeneration.
b) encouraging indigenous environment-friendly and acceptable cost-effective technologies and practices in identifying and pursuing sustainable developments amenable to local, cultural and resource diversity.
c) identifying and encouraging appropriate technologies for more research and development applications.
d) making building construction more indigenous, more adaptable to local climatic zone and executable to achieve the basic provisions for sustainable development to ensure sustained availability of building resources through regeneration and/or reuse/recycle.
e) encouraging use of traditional materials, technologies, vernacular design and construction practices, which have stood the test of time and which may be blended with the modern technology applications.
3.5Energy Efficient Design and Processes
All efforts need to be made towards optimum and efficient use of energy sources for life sustenance. The increasing thrust on using non-fossil fuel energy for all needs have to be given priority consideration. The tapping of renewable sources of energy for lighting, heating, cooling and ventilation needs, deserve special attention. For example, an improved day light factor will reduce the day lighting needs by means of
supplementary lighting with added health benefits such as reduced eye strain (associated with constant elimination conditions). India with over 95 percent of the clear design sky available, the design has to fully utilize the associated benefits. While deciding on the energy choices, life cycle cost analysis including tangible and intangible benefits should be made and not look at the onetime initial capital expenditure alone. The end of life options should also be perceived.
3.6 Reduced Embodied and Operational Energy
All designs, materials and technologies, construction practices should be selected and employed, aimed at reducing the overall embodied and operational energy involved in construction and operation of the built facility. The construction should promote sustainability through adoption of local resources (natural and man-made) and skills.
3.7 Integrated Water Management
Considering an ever increasing demand for water for a growing population, efforts are needed to substantially reduce per capita water consumption in buildings. Integrated and sustainable water management focusing on least anthropogenic water discharge from human activities should be pursued. The use of water conserving fixtures, landscaping, rainwater harvesting, aquifer recharging and waste water recycling need to be given due priority consideration.
3.8 Operation and Maintenance of Services
This should involve use of efficient building and plumbing services components and fixtures tailor-made to meet sustainability objectives and creating sufficient awareness among the users of building facility and its services, during the occupancy stage.
3.9 Monitoring Compliances
The measures adopted during design, construction and occupancy stages should be monitored against norms as per this Code at periodic time interval to ensure sustainability.
5Implementation of This Part
Provisions for building planning, design including material selection and structural design, construction, operation and maintenance have been covered in National Building Code of India: Part 0 to Part 10. These also allow various options to be exercised, for example while various building materials have been listed therein along with their quality requirements for compliance, the choice may rest with the owner/building professionals, say for walling or masonry units, the options could be: use of common burnt clay bricks, perforated clay bricks, hollow clay bricks, fly ash lime bricks, fly ash clay bricks, calcium silicate bricks, solid/hollow concrete blocks, light weight concrete blocks, autoclaved aerated concrete blocks, preformed foam concrete blocks or any other alternative specified. This Part of the Code discusses such options from sustainability point of view for guiding in their appropriate selection. Similar explanation applies to other materials as also other aspects in planning, design, construction, operation and maintenance. However, once a choice of material, design methodology, construction technique/methodology, operation and maintenance related options, etc, is made, the provisions given in this Part of the Code for the same shall be complied with. This Part also prescribes provisions to be necessarily complied with so as to help achieve the objective of sustainability.
This Part should, therefore, be implemented in light of the above while following the approach given in 3. The Authority may require submission and verification of relevant documents while applying for building permit, to demonstrate compliance to the requirements of various provisions under this Part.
6Siting, Form and Design
6.1 General
Before initiating the formal design process, it is critical to evaluate all the passive design options to take advantage of local site and climatic conditions,
acceptable thermal comfort conditions and other occupant requirements. Passive techniques are very cost effective, climate responsive and energy efficient and help a building integrate better with its immediate environment and most importantly do not create any negative impact on the environment unlike active systems that may cause various negative impacts including ozone depletion, global warming and environmental disruptions. The objective, therefore, is to encourage passive design strategies for every building as a means to reducing overall energy demand before pursuing active and mechanical means in an effort to not only save energy but also to minimise the overall negative impact on the environment.
The requirements for the development of buildings and building sites that encourages sustainable building practices including siting, form and architectural approach towards sustainable development, are given in 6.2. The purpose includes providing guidelines that establish objectives for siting and form of residential, mercantile, industrial or other building occupancy developments early in the design stage so as to address sustainability through design. These objectives include, but are not limited to, energy conservation, water conservation and reduced greenhouse gas emissions.
6.2 Site Design and Development
6.2.1 Site Assessment Prior to Design
The responsible design professional shall prepare an assessment of the onsite natural resources and pre-site conditions. The person shall,
a) establish, if there are any protected areas such as floodplains; forest department areas; water bodies such as sea, lakes, rivers, wetlands, tributaries and/or streams; coastal regulation protected areas; defence areas; public parks and recreation areas (unless otherwise used for the purpose of the park); natural contours/terrain requiring protection and agricultural land (unless serving an agriculturally related purpose such as storage, processing, transport, etc) and demonstrate that no critical natural resource is impacted by the project and/or dredging operations;
b) establish the degree to which the existing soil at site and hydrology has been disturbed prior to development and demonstrate various site erosion protection measures taken including measures to preserve natural stormwater drainage system, top soil and existing vegetation, minimise soil disturbance as specified in Part 10 ‘Landscape Development, Signs and Outdoor Display Structures
7External Development and Landscape
7.1 Landscape Planning and Design
The landscape planning and design shall be in accordance with Part 10 ‘Landscape Development, Signs and Outdoor Display Structures, Section 1 Landscape Planning, Design and Development’ of the Code. In addition, the provisions given in 7.1.1 to 7.1.3 shall be followed.
7.1.1 Landscape Design
Proper landscaping helps in maintaining natural capacity of site for stormwater management, filtration, groundwater recharge and maintenance of soil structure thereby contributing to soil organic matter, and preventing erosion. It helps in moderating microclimate through evaporation, transpiration and the uptake and storage of carbon in trees and other vegetation.
7.1.1.1 Microclimatic conditions
Microclimatic conditions play an important role in landscape design and in working out irrigation requirements, as it accounts for the environmental conditions specific to the landscape, including temperature, wind and humidity. For example, a water body can increase the humidity and a wind funnel can increase the evapotranspiration rate and hence the irrigation requirement. The microclimatic conditions may be taken into account in landscape irrigation calculations by applying a microclimate factor.
The average microclimate factor is 1.0 and this refers to conditions where the landscape evapotranspiration rate is unaffected by buildings, pavements, reflective surfaces and slopes. Higher microclimate factor conditions occur where evaporative potential is increased due to landscapes surrounded by heat absorbing and reflective surfaces or due to exposure to particularly windy conditions. Examples of high microclimate factor areas include parking lots, west sides of buildings, west and south sides of slopes, medians, and areas experiencing wind funnel effects. Areas with low microclimate factor include shaded areas and areas protected from wind. North sides of buildings, courtyards, areas under wide building overhangs and north sides of slopes.
Need for reducing the noise at site shall be assessed. If so required, appropriate measures may be taken for noise abatement, such as quieter pavement or road surfacing, dense foliage, earth berms, barriers or screens, and scheduling maintenance activities when site users are not present. Walls, fences and vegetation may also be used to break, guide, deflect or filter the wind and thereby alter its effects. Noise may be reduced with use broad-leaved trees more than with the conifers and this further improves when foliage extends close to the ground. The best location for a noise barrier is either very close to the source or very close to the receiver while the worst position for attenuation is halfway between them. Provisions of Part 8 ‘Building Services, Section 4 Acoustics, Sound Insulation and Noise Control’ of the Code shall be followed.
7.2Rainwater Harvesting — Surface Runoff
7.2.1 Rainwater Harvesting
Rainwater harvesting refers to collection and storage of rainwater and also other activities aimed at harvesting surface and groundwater, prevention of losses through evaporation and seepage and all other hydrological studies and engineering interventions, aimed at conservation and efficient utilization of the limited water endowment of physiographic unit such as watershed. In general, rainwater harvesting is the activity of direct collection of rainwater. The rainwater collected can be stored for direct use or can be recharged into the groundwater. While enough measures should be taken voluntary, the Authority should encourage and appropriately provide for ensuring rainwater harvesting in outdoor built environment.
The system of collection of rainwater and its conservation for future needs has traditionally been practiced in the country, such as through Baoris, step wells, lakes, tanks, roof top collection systems, etc, to meet the domestic and irrigation demands. This also helps to arrest groundwater decline and augment groundwater table, beneficiate water quality in aquifers, conserve surface water runoff during monsoon, reduce soil erosion and inculcate a culture of water conservation.
Two broad approaches to rainwater harvesting are:
a) Storing rainwater for direct use — Under this approach, for domestic and irrigation purposes, the rainwater is directly collected either in the natural or man-made structures such as Nadi, Tanka, Kund, sand filter bed, pond, rooftop rainwater collection structure, etc.
Roof rainwater collection system augments the water demands by collecting rainwater from the roof and diverting it to specially designed storage or recharge tanks, as per the requirement. On sloping roofs, evaporation losses are small, so collection efficiency may be of the order of 85 percent. Rainwater may be collected from any kind of roof. Tiled or metal roofs are easier to use for the purpose and a smooth surface for the roof will help in water flow and collection.
To reduce contamination of rooftop rainwater, the necessary actions and precautions as given below shall be followed:
Avoid overhanging of trees above the roof to prevent leaves and bird droppings falling on the roof.
Do not allow the first rainfall to enter the tank by diverting it away from tank; although human or animal coliforms are not involved, bird droppings or lizard faeces, and other air borne dirt are also to be washed away from the roof.
7.3Water Elements and Irrigation Practices
7.3.1 Design and Post Occupancy Maintenance of Water Features
The site maintenance plan (see 7.1.2.3) shall include appropriate maintenance activities for the water features taking care of the following considerations:
a) Use of chemicals likely to harm aquatic life, such as chlorine and bromine shall be avoided.
b) Maintenance activities to ensure that the water features do not create habitat for mosquitoes, shall be included.
c) Water features shall be designed such that they match or mimic water in the natural
18
environment; and water features that are incompatible with the local ecological context (for example, a lake in a desert) shall be avoided.
d) Volumes of rainwater or water from other non-potable sources available on site for use in water features shall be estimated, and water features shall be so designed that these are integrated with the site so as to utilize this water on site, and not require additional water from potable water sources.
e) Non-potable water from sources such as gray water, reclaimed water or storm-water basins shall be collected and used for non-potable applications.
f) Design and maintain water features as natural ecosystems with water source(s), plants and aquatic organisms appropriate for local conditions.
g) Water quality may be enhanced in created water features with biologically-based water treatment including with the use of certain enzymes, mineral, and oxygen-based additives, especially during initial establishment.
h) Natural swimming pools or other water features intended for human contact may require additional treatment methods such as ozonation or thermal treatment.
7.3.2 Water Conservation and Irrigation Practices
Selecting efficient irrigation systems, planting vegetation appropriate for site conditions and climate, and using captured rainwater or gray-water can reduce water waste and conserve sources of potable water. Typically, half of irrigation water may get wasted as a result of evaporation, wind, improper system design, and over-watering requiring the following considerations which may be followed:
a) Low water demand vegetation (xeriscape) and high-efficiency equipment (for example, drip irrigation) and/or climate based controllers for irrigation systems should be used.
7.4External Access Design
7.4.1 Reduced Environmental Impacts from Parking Facilities
Open parking areas, if largely made of concrete and asphalt, absorb heat and contribute substantially to the heat island effect. This shall be mitigated by following the considerations given below:
a) Rendering these areas white or light in colour instead of black, so that they may reflect a lot of sunlight back to space rather than absorbing it.
b) Providing shade and/or using light-coloured/high-albedo materials and/or open grid pavement for the site's non-roof impervious surfaces, including parking lots, walkways, plazas, etc.
c) Limiting the net paved area of the site under parking, roads, paths, or any other use so as not to exceed 25 percent of the site area or net imperviousness of the site not to exceed the imperviousness factor as prescribed in 4.5.11.2.1 of Part 9 ‘Plumbing Services, Section 2 Drainage and Sanitation’ of the Code, whichever is more stringent.
Additionally, the following shall be complied with:
More than 50 percent of the total paved area shall have pervious paving/open grid pavement/grass pavers, or
A minimum 50 percent of the total paved area (including parking) shall have shading by vegetated roof/pergola with planters, or
A minimum 50 percent of the total impervious paving area (including parking) shall be topped with finish having solar reflectance of 0.5 or higher.
The external access, including pedestrian walkways/pathways shall be designed and developed in accordance with Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
7.4.2 Long term Public and Private Transportation Plan
The long term public and private transportation plan shall take care of the following considerations:
a) Incorporating urban transportation as an important parameter at the urban planning stage rather than being a consequential requirement;
b) Encouraging integrated land use and transport planning in cities so that travel distances are minimised and access to livelihoods, education, and other social needs, especially for the marginal segments of the urban population is improved;
c) Improving access of business to markets and the various factors of production;
8Envelope Optimization
8.1 Building Envelope
The building envelope acts as the interface between indoor and external climatic conditions. It potentially
regulates the building climatic response. The building envelope should be designed to conserve energy substantially. Well designed building envelope maximizes daylight, natural ventilation (access to fresh air) and views to the exterior, and enables to modulate solar heat gain and control/reduce noise. The building envelope may also be designed to integrate systems for renewable energy and rainwater harvesting. In general, the design strategies drawn from long experience in the country in its various climatic zones may be taken into account (see Annex A for guidance).
Building envelope components and their configuration largely determine the amount of heat gain or loss and wind that enters inside the building and extent of natural ventilation in the building. The primary components of building envelope which affect the performance of a building are,
a) walls,
b) roof (including skylights and clerestories),
c) fenestration (openings with or without glazing),
d) floor, and
e) surface finishes.
FIG. 3 FACADE LIGHTING USING SHIELDED FIXTURES
8.1.1 Walls
Walls are a major part of the building envelope, which are exposed to external environment conditions such as solar radiation, outside air temperature, wind and precipitation. The construction of wall and thereby its heat storing capacity and heat conduction property has a major impact on indoor thermal comfort in naturally ventilated buildings and on cooling loads in air conditioned buildings. The wall material, thickness, finishes should be selected according to climate zone and building's comfort requirement. Wall properties that determine heat transfer are thermal conductivity, thermal resistivity, thermal absorptivity, emissivity, thermal reflectivity and thermal capacity (see 2).
8.1.1.1 Enhancement of thermal performance of walls
Thermal performance of walls can be improved by following ways:
a) Thermal insulation (applying insulation on wall surface) — Thermal insulation plays an important role in reducing the thermal conductance or U-value of walls. The effect of insulation is to reduce heat gain and heat loss. Insulation should always be placed on the hotter side of the surface. In hot climate zone, insulation should be placed on the external side of wall composition. Insulation also controls the interior mean radiant temperature (MRT) by isolating the interior surfaces from the impacts of exterior
7.5External Lighting Design
7.5.1 Landscape Lighting Design — Allowable Lighting Power Density (LPD)
Light pollution can disrupt circadian rhythms and melatonin production, which has been linked to serious health concerns. Reasonable use of outdoor lighting restores dark night skies and preserves the ambiance of the night. Whether outdoor light is directly adjacent to a species habitat or located at some distance is an important consideration, as through sky glow, the combined effects of artificial lighting on vast numbers of nocturnal species have the potential to disrupt the functioning of entire ecosystems by disturbing balances in competition and predation. The landscape lighting should be designed such that light fixtures emit minimum light as per the specified total fixed lumens and only light the areas as required for safety and comfort. In addition, the lighting shall be efficient complying with the requirements of maximum LPD given in Table 1.
7.5.2 External Signage Design
External signage may be designed to address the following main issues related to overall sustainability:
a) The signage shall be classified as external lit and internal lit and further classified based on functional requirements such as emergency, way finding, etc. The requirements of each type of signage are different and should be evaluated based on the same. The recommended lighting power density is 130 W/m² , maximum for internally illuminated signage, and 25 W/m² , maximum for externally illuminated signage.
b) Illuminated signage forms a substantial part of upward directed lighting. Efforts should be made to shield the lighting.
c) Paints, adhesives, etc, used in the signage should be of low VOC.
d) Fabrication of the signage should be using materials locally available and having a recycled content.
7.5.3 External Lighting
The facades may be lit with fixtures that are shielded,
22
Table 1Maximum Lighting Power Densities for Building Exteriors (Clauses 7.5.1 and 7.5.3)
Sl No.
Area to be Lit
LPDsMax(3)
(1)
3.10 Corporate Governance
The concerned top management should ensure association of all stakeholders including the training and awareness in pursuing and achieving needs for sustainable development at all stages of building lifecycle (from design to end of life). The environmental impact assessment should be carried out and remedial measures based on the findings should be taken during the life cycle of the buildings.
Section 1 Landscape Planning, Design and Development' of the Code;
c) identify and ensure diversion, avoidance of existing water, power, communication, sewerage lines, saving/replanting of old trees, removal of existing invasive vegetation on site and that no invasive vegetation is planted post completion; and
d) identify and ascertain the natural resources available onsite and surrounding areas and ensure optimum utilization of the same in construction and post occupancy.
A site assessment report for the building/development project shall be prepared.
6.2.2 Building Form, Orientation and Shading
The development shall plan on locating, orienting and shading the building so that,
a) there is adequate provision for external shading of the facades during the peak summer season;
b) there is adequate provision for vertical shading to prevent direct solar radiation and glare due to low altitude sun angles, specifically on the eastern and western facades;
c) the building is oriented optimally based on sun-path and engineering analysis; and
d) there is adequate protection for the building envelope against thermal losses, drafts and degradation by natural elements such as wind, dust, sand, snow, rainwater, hail, etc.
The above strategies shall be implemented based on the climatic conditions of the location. Specifically, the designs should be based on the heating degree days and cooling degree days of the actual location of the building. In the absence of this data, a more generalist approach based on the five climatic zones of the country may be used.
The responsible design professional shall carry out building orientation and shading studies and establish the optimal building orientation for the project and ensure appropriate shading design such that the facades are shaded for more than 50 percent of the summer solstice. A solar path analysis shall be done as an aid in arriving at optimum form and orientation for the building. Appropriate shading design can be arrived at either through simulation approach or by using the prescriptive shading norms as indicated in the SP 41:1987 'Handbook on the Functional Requirements of Buildings (other than industrial buildings)'. A design report showing both the optimum orientation and shading design strategies along with justification for the selection of the same shall be prepared.
6.2.3 Thermal Massing
The responsible design professional shall carry out building thermal massing studies to evaluate the impact on thermal mass on the consequent thermal transmittance and energy performance of the building based on the sun-path analysis and local/equivalent weather data. A report showing both the optimal thermal massing and the choice and justification of the proposed wall material of the building together with the design approach for decision making shall be prepared, together with other documents while applying for the building permit.
6.2.4 Reduced Building Footprint in Multi-Storeyed Building Designs
The requirements for open spaces (within a plot) as specified in 8 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code shall be complied with. In any case, at least 30 percent of the open spaces shall be maintained as softscapes (permeable surface on ground). For areas where the calculated softscape area requirement is less than 10 percent of the total plot area, a minimum of 10 percent softscape area shall be provided.
6.2.5 Optimum Building Volume
For air conditioned buildings, efforts shall be made in design to reduce building volume by reducing floor to floor and floor to ceiling height without compromising the utility and functional efficiency of the building. For natural ventilated buildings or mixed mode ventilated building, the optimum building volume and floor to floor heights to be ascertained and a report on the design and justification of the same shall be prepared.
6.2.6 Building Form Development Plan
A report shall be prepared on the evolution of the form of the building based on science of architecture, climatology and building physics. The plan shall be in line with the decision making process of the project team and a narrative shall be prepared briefly mentioning the justification behind the selected building form and orientation of the building and shading devices to ensure that the final design meets with the intent of this Part.
6.2.7 Natural Ventilation, Cooling and Wind Effects
A report illustrating the evaluation of the various natural ventilation and cooling studies to maximize natural ventilation or mixed mode ventilation based on adaptive thermal comfort criteria for the project, shall be prepared. In addition, for high rise buildings, wind analysis shall be carried out to evaluate the impact of wind movement and natural air flow changes because of the new building proposed to be erected. Strategies
may include application of cross-ventilation and thermal comfort, factoring prevalent wind patterns, seasonality, stack effect and other principles. A narrative on how these aspects have been factored in the design shall be prepared.
6.2.8 Optimal Daylighting
A day lighting analysis study based on the proposed form of the building for the project shall be carried out and a report thereof prepared. It shall be demonstrated that at least 25 percent of the regularly occupied areas of the building achieve sufficient day lighting with a minimum day lighting factor of 2 percent or as described in SP 41:1987 ‘Handbook on the Functional Requirements of Buildings (Other than Industrial Building)’. For details of day lighting harvesting methods and calculations (see 8.1.3.2).
6.2.9 Defining Building Service Life in Terms of Minimum Component Service Life
A building service life plan shall be prepared along with the design and construction documents. The plan shall clearly indicate the design service life and the minimum design service life shall be not less than 60 years for the structure itself and not less than 10 years for various service components, equipment and systems within the building. All plan shall include dismantling, de-mounting and re-use plan.
6.2.10 Life Cycle Assessment (Optional)
The materials and assemblies may be selected based on their carbon footprint (GHG emission potentials) and/or a life cycle assessment of the embodied energy of the product. For more details on LCA analysis of building materials (see 9.1.4).
7.1.1.3 Building shadow considerations on landscape
Vegetation provides climate moderating benefits as well as benefits to human health. Most vegetation requires sunlight in varying degrees for their growth and maintenance. The buildings by their design, shade certain parts of the external areas for some part of the day or other. External landscapes shall be designed taking the shading pattern of the buildings into consideration. For instance the northern side external areas of the building tend to be shaded for large parts
of the day, while the southern side has access to sunlight for most times of the day, the choice of vegetation should be based on the availability of sunlight along different solar exposures and the requirement of various species of vegetation. Vegetation also has the potential to reduce the energy consumption of a building by providing shading and a cool microclimate. Vegetation and/or vegetated structures shall be kept in strategic locations around buildings to reduce energy consumption and costs associated with indoor climate control.
7.1.2 Hard Landscape Design
7.1.2.1 Pervious paving design
Pervious paving helps in holding rainwater, reducing the rate of storm water flow, infiltrating storm water into the ground for reuse and also helps in filtering the rainwater. Besides helping in storm water management, pervious paving helps in reducing the heat island effect. For sustainable site planning, perviousness in the paved areas of the site may be maximized.
However, the rainwater harvesting potential of pervious paving is subject to local geo-morphological formations and the use of the same should be assessed based on local conditions. For example, in coastal areas, where the water table may be high and the water absorptive capacity is low, pervious paving may not be as effective.
7.1.2.2 Heat island effect and parking design
The heat island effect raises the localized temperature, impacting local climate/microclimate. Plants and animals that are sensitive to large fluctuations in day time and night time temperatures may not thrive in areas affected by heat island. Heat islands also exacerbate air pollution as smog is produced faster at higher temperatures and as rising temperatures lead to increased cooling requirements, requiring energy and causing associated emissions.
Open parking areas consisting of concrete and asphalt absorb heat and contribute substantially to the heat island effect. Shading and/or use of light-coloured/high-albedo materials and/or open grid pavement for the site's non-roof impervious surfaces, including parking lots, walkways, plazas, etc, shall be made to help in reducing the heat island effect.
The solar energy should instead be utilized for generation of renewable energy, thus serving the dual purpose of dampening the heat island effect and reduction in use of fossil fuel for energy generation (see 11.16).
7.1.2.3 Post-occupancy maintenance
A site maintenance plan shall be developed that outlines the long term strategies and identifies short-term actions
to achieve sustainable maintenance goals. The plan should address issues such as plant maintenance, integrated pest management, soil management, fertilizer use, rainwater harvesting, reducing freshwater consumption, site safety, and irrigation allotment and schedule.
7.1.3 Soft Landscape Design
7.1.3.1 Preserving top soil
Healthy soils allow rainwater to penetrate, preventing excess runoff, sedimentation, erosion, and flooding. Soils also help clean and store water, and recharge groundwater. By storing water and slowing the delivery of water to plants, healthy soils play a significant role in vegetation health. In areas of previously disturbed soils, soil function shall be restored to rebuild ability of soils to support healthy plants, biological communities, and water storage and infiltration. In existing soils, depending upon the requirement, the need of soil compaction, organic matter levels, and the balance of soil organisms shall be addressed. It shall be ensured that adequate soil volume is made available for proper plant growth. In order to protect soil horizons and maintain soil structure, existing hydrology, organic matter, and nutrients stored in soils, the disturbance to healthy soil shall be limited. Typically, the first 200 mm soil depth is most conducive for plant growth, and is considered as top soil. Where healthy top soil is being disturbed due to construction activities like excavation, the top soil should be stripped and stacked on one side till further use. Use of excessive chemicals such as fertilizers may result in lasting damage to the soil ecology and shall, therefore, be avoided. See Part 10 'Landscape Development, Signs and Outdoor Display Structures, Section 1 Landscape Planning, Design and Development' of the Code, for further details regarding protection of landscape during construction.
7.1.3.2 Ecological design/conserving biodiversity
A diverse range of species, especially native plants can provide habitat for native fauna, including important pollinator species (for example, insects, birds and bats) that are necessary for plant reproduction, including cultivation of crops. Also, biodiversity in landscapes helps in retaining soil nutrients and is more resistant to attacks by pests. The following considerations shall be used:
a) Protection and use of existing vegetation — Such sites shall be selected that do not include habitat for threatened or endangered species. Site may be designed to minimise disruption to existing habitats. Trees designated as important by concerned local, state or central authorities shall be preserved. Mature trees are significant community resources because
of their cultural, aesthetic, or historic relevance and shall be preserved. Transplantation for mature trees within the site or to another site shall be explored, where vegetation clearing is necessary for construction.
b) Use of vegetation that promotes a regional identity and a sense of place — Native plants which are endemic to the location and appropriate non-native plants adapted to site conditions, climate, and design which support biodiversity, reduced pesticide use and water conservation, shall be used. Only non-invasive plants that are nursery grown, legally harvested or salvaged for reuse from on or off-site shall be used.
c) Conservation of native endangered species — Native vegetation that is endangered in the locality may be planted to conserve/enhance the gene pool of native vegetation and promote biodiversity.
7.1.3.3 Landscape design for controlling solar gain
Vegetation placed in strategic locations around buildings provides an opportunity to reduce energy consumption and costs associated with indoor climate control for cooling. Trees, shaded trellises, green roofs, green facades and green walls may be used individually or in conjunction with other measures to increase shading both on the ground and on the building surface. Deciduous trees allow access to the sun in winter and provide shade in summer. Vegetation provides significant opportunities in conserving building energy consumption, especially if the west, south-west, south-east and east facades of the building are shaded. For buildings with natural ventilation, the vegetation species shall be carefully chosen such that they provide shade, but do not significantly block cool breezes or any convective air currents.
7.1.3.4 Vertical landscaping and roof gardens
Roof garden and/or green walls or vertical landscaping may be provided as it helps in conserving energy by providing shading, reduces heat island effect, helps (specially in dense areas) in maintaining a certain biomass critical for human health and also helps in reducing storm water flow rates through bio-retention. Required caution shall be observed in respect of water proofing requirement for the above.
Growth of cities puts a significant pressure on natural resources resulting in drastic reduction of green open spaces, depletion of trees, heat island effects, and floods and other natural disasters, further aggravated by the effects of climate change. Proper attention may be given
to the potentials of urban forestry and agriculture for contributing towards urban greening, heat reduction, storage of excess storm water and maintaining flood plains free from construction. Large scale developments that exceed 10 hectare should be encouraged to fulfil minimum 5 percent bio-capacity required to sustain themselves.
Filter the water on entering the tank by suitable filter and also cleaning the filter and tank regularly.
Seal tanks to keep out sunlight (to prevent algae growth), mosquitoes, lizards, birds, etc.
Disinfect tanks once in a year with bleaching powder.
b) Recharging groundwater aquifers — This approach involves use of various kinds of recharge structures, which not only arrest the water but also promote water percolation through soil strata to recharge the depleting aquifers. Structures like percolation tank, anicut, gabion, etc, facilitate the recharge of underground aquifers. However, meteorological and hydrological investigations along with geo-technical investigations shall be carried out before selecting the best suited method for groundwater recharge. Direct injection of rainwater through deep bore wells should be avoided for quality control reasons.
For rainwater harvesting a reference to 4.5.12 of Part 9 'Plumbing Services, Section 2 Drainage and Sanitation' of the Code may be made. For further details, reference may also made to good practice [11(1)].
b) If turf grasses are to be used, they should be selected, to be regionally appropriate and to minimise post-establishment requirements for irrigation. The turf area should not exceed 30 percent of the total landscaped area.
c) Reuse gray-water, captured rainwater and/or condensate water for irrigation to decrease potable water use for irrigation as well as to create a net benefit to the local watershed by making the landscape part of the natural water-treatment process.
d) If gray-water or wastewater is to be recycled for landscape irrigation, tests should be conducted to determine suitability for reuse.
e) Irrigation systems should be so designed that trees, shrubs and ground cover are irrigated in separate hydrazones such that watering can be discontinued zone by zone as plants become established.
f) A sub-surface drainage system shall be planned in areas covered with turf to collect excess water for reuse.
d) Bringing about a more equitable allocation of road space with people, rather than vehicles, as its main focus;
e) Encouraging greater use of public transport and non-motorized modes;
f) Enabling the establishment of quality focussed multi-modal public transport systems that are well integrated, providing seamless travel across modes;
g) Establishing enforcement mechanisms to ensure efficiency and enhanced safety for the transport system users;
h) Establishing institutional mechanisms for enhanced coordination in the planning and management of transport systems;
j) Introducing intelligent transport systems for traffic management;
k) Addressing concerns of road safety and trauma response;
m) Reducing pollution levels through appropriate travelling practices, better enforcement, stricter norms, technological improvements, use of electrically operated vehicles etc; and
n) Building capacity (institutional and manpower) to plan for sustainable urban transport and establishing knowledge management system.
7.4.3 Bicycle Lanes and Pedestrian Access — Safety and Comfort
Construction of cycle tracks and pedestrian paths in cities enhances safety and thereby enhances use of non-motorized modes. The safety concern of cyclists and pedestrians should be addressed by encouraging the construction of segregated rights of way for bicycles and pedestrians. Apart from improving safety, the segregation of vehicles moving at different speeds helps
improve traffic flow, increase the average speed of traffic and reduce emissions resulting from sub-optimal speeds. Such segregated paths are useful not only along arterials, to enable full trips using non motorist transport but also as a means of improving access to major public transport stations. Such access paths, coupled with safe bicycle parking places, may be provided for promoting an increased use of public transport. Creative facilities like shade giving landscaping, provision of drinking water and resting stations along bicycle corridors should also be encouraged to help mitigate, the effect due to adverse weather conditions. The use of the central verge along many roads, along with innovatively designed road crossings, may be considered for developing as cycle tracks. At busy intersections and high traffic corridors, pedestrian crossing shall be constructed.
Following are some of the features which should be considered while designing pedestrian and cycle/cycle-rickshaw friendly environment:
a) Design and construction ensuring safety and comfort of all the users.
b) Use of following climatic design features for streets and public spaces to make them comfortable for pedestrians, cyclists and public transport users, based on local climate:
Planting of deciduous trees all along the pedestrian/cycling path to provide adequate shade in summer and allow solar access in winter.
Considerations to overhangs, arcades and closely built buildings providing shading and comfort in summer to the public realm.
Orientation of streets to allow the desirable directional wind flow through streets and public spaces in summer and block undesirable winds in winter, to ensure comfort in the public use areas.
c) Signalization of junctions and mid-block crossings on roads to allow safe crossings at grade.
d) Multimodal interchange and provision of good para-transport options and walkability at the neighbourhood level as the most important factor in reducing use of private modes and also reducing transportation demand; and the following to be provided so that people can walk or cycle easily for short trips as well as for accessing mass transport stations:
Fast and convenient interchange between modes (distances between modal changes to be as per multimodal integration and connectivity requirements).
Closest convenient interchange access at
stations for pedestrians, non-motorized modes and public/paratransport modes, preferably within 50 m of station exits.
e) Proper street grid density as a critical requirement in urban design to ensure small blocks and an interconnected street network to provide a walkable, public transport friendly neighbourhood as per the following:
Street grid density of 7-10 km centre-to-centre/km² for residential-mixed use neighbourhoods and 13-20 km centre-to-centre/km² for commercial-mixed use neighbourhoods to provide adequate connectivity and frequent directional changes for pedestrians.
Direct and shortest route/access to station through provision of cut-throughs for pedestrians and non-motorized transport through blocks above 200 m in length with a view to making smaller block sizes.
Signalization of junctions and mid-block crossings on roads to allow safe crossings at grade at a maximum frequency of 200 m.
f) Provisions of dedicated lanes and signal prioritization for pedestrians, non-motorized transport and public transport on major corridors so as to provide priority and congestion-free movement for these modes.
g) Adequate street lighting for pedestrians and bicycles to ensure their safety; minimum illuminance being 30 lux for non-shopping areas and 20 lux for shopping areas, bus stops and signalized crossings.
h) Commercial/hawking zones at regular intervals in accordance with the local byelaws/ masterplan (within 5 min walk from every home in the city) to encourage walkability and increased street activity and to provide safety.
j) Amenities for public transport users:
Amenities at-grade crosswalks (and overpasses on highways) at intervals of 80-200 m, aligning with location of transit stops, type of street/land use activities and neighbouring building entries and destinations.
Dustbins, letter-boxes, signages and other public amenities at street corners for high usability.
Accessible public toilets at every 500 m to 800 m distance, preferably located close to bus stops for easy access by pedestrians and public transport users.
k) Barrier free environment to make public streets and crosswalks fully navigable by all persons including the persons with disability and the elderly.
m) Vertical mixing of uses such that all non-work trips are reduced to be under 500 m walking distance such that vehicular trips may be eliminated for daily errands; for example through mixed convenient/community shopping uses with residential uses to reduce dependency on private vehicle and shifting all short trips from private vehicle to walking, cycle-rickshaw or public transport.
7.4.4 Off Street Parking
The off street parking shall be planned taking care of the following objectives as per Part 3 ‘Development Control Rules and General Building Requirements’ of the Code:
a) To relieve congestion on streets by providing convenient off-street parking and loading facilities in proportion to the demand created by the use;
b) To provide for the safe and orderly movement of traffic through proper design and location of adequate parking, loading, and manoeuvring areas;
c) To protect neighbourhoods and surrounding land uses from vehicular parking, loading and traffic congestion, noise and dust, through proper aesthetic design and location of entries, parking areas, and landscaping;
d) To promote businesses, industries and commercial activities by providing safe, convenient, attractive parking facilities and environments; and
e) To encourage the use of efficient forms of transportation.
7.4.5 Discouraging Subsidized Parking in Public Realm
Subsidized parking in public roads and spaces, especially in urban areas with high traffic density or having likely projected high traffic density should be discouraged to reduce private vehicle usage and inducing a modal shift towards public transport. Parking management may be used as a demand management tool rather than a supply based tool, with the following considerations:
a) Discouragement to the use of car as a feeder or a general mode of transport, with park and ride facilities being only at stations of mass rapid transport system (MRTS).
b) Providing parking only for servicing rather
than for access, and only emergency vehicle access to be provided which can be done through provision of mountable kerbs, etc, on pedestrian dominated streets.
c) No free or subsidized parking in public space and actual parking cost to be defined by market forces.
d) Enforcement of parking caps in areas with mass rapid transport access.
e) Park once-and-walk facilities in busy markets and residential/mixed use areas.
f) Strict enforcement of parking through self-regulating design.
7.4.6 Providing Neighbourhood Connectivity, Walkability and Safety
At the site design and block design level, several measures should be taken for reducing transportation demand and promoting walkability, and ensuring that the neighbourhood is a safe walkable place. These measures should include the following:
a) Vertical mixing of housing and community based uses to ensure vibrancy and safety.
b) Based on local climate, minimum 2 h daylight access to neighbouring buildings to be ensured through provision of required street width-to-height ratios, in accordance with Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
c) Block sizes and paseos — For blocks where any one side is greater than 200 m in length, a public access cut-through for pedestrians and non-motorized transport (NMT) shall be provided. This ensures connectivity and walkability in the neighbourhood enabling short local trips to be made on foot.
d) The setbacks and boundary wall for commercial properties should be designed so as to also promote safety and encourage pedestrian communication.
7.4.7 Ecology of Streets
As streets constitute about 20 to 25 percent of the impervious cover of the city, they have a large detrimental effect on the heat island effect and ecological character of a city. The following design components should be integrated in street design:
a) Planting of trees as an essential component for all streets to provide shade to pedestrians and reduce solar gain.
b) Use of high albedo (diffused reflectivity) materials for paving and increasing greenery around to reduce heat island effect.
c) Decreasing impervious surfaces through permeable paving, tree planting zones, etc, to increase groundwater infiltration and prevent seasonal flooding.
d) Integrate natural storm water filtration and absorption into street design through bio-filtration beds, bio-swales and detention ponds.
conditions. Insulation along with infiltration control is important for reducing heating and cooling loads in simple occupancy (skin) load dominated buildings such as residences. In buildings, that are internal load dominated such as offices with high equipment load, the insulation thickness and properties should be determined based on thermal performance analysis including the role of insulation in reducing cooling energy consumption, particularly in hot and dry, composite and warm humid climates. Thermal insulation may be made from a variety of materials and in several forms. Broadly they may be divided into following five categories:
Rigid or semi rigid blocks and boards (such as, mineral wool, expanded polystyrene boards);
Boards with impact or weather resistant surfaces suitable as exterior grade material;
Loose fill (such as, cellulose, fibre glass);
Foam and dry spray (such as, polyurethane or polyisocyanurate); and
Blankets, felts or sheets (such as, fibre glass, mineral wool, closed cell flexible elastomeric foam).
When specifying insulation, its key properties such as thickness, density, thermal resistivity/thermal conductivity value at specified
NATIONAL BUILDING CODE OF INDIA 2016
temperature, long term thermal retention, fire resistance, moisture resistance (structure open/closed cell), water vapour diffusion resistance, etc, should be specified. Insulation should be applied as per manufacturers' recommendations and in a manner so that it achieves rated insulation in terms of thermal resistance or R-value. Damaging or compressing the insulation reduces the effective R-value and compromises thermal performance of the construction assembly.
b) Thermal mass (increasing wall thickness) — Thermal mass in walls enables time delay in impact of external environment on internal conditions. Thermally massive walls have high thermal capacity, and thermal storage capacity increases with increasing compactness, density and specific heat capacity of the materials. Walls (and other building elements such as roof and floor) can be used for thermal storage. The effectiveness of storing heat or coolness can be increased by creating a flow of fluid through the storage media.
Thermal mass is particularly effective in hot-dry climate with larger diurnal range. The building mass stores heat during daytime when outside temperature is high, and releases it to the inside space during night when outdoor temperature is cooler. Thermal mass is also used in storing heat during daytime in cold climates, to release it into the space during night, to warm it up when outdoor conditions are colder. Materials such as concrete, brick and water have high thermal storage capacity and can be used for such application. Storage mass exposed to direct sunlight should be dark in colour to allow larger absorption. It is generally more efficient to have thicker rather than thinner storage mass. The optimum thickness varies between 100 mm and 200 mm.
NOTE — There are ongoing developments based on research, regarding use of improvised materials with special properties such as phase changing characteristics which may be considered in future along with their implications from sustainability point of view.
c) Air cavities (Providing air cavities in walls) — Air cavities in wall reduces heat gain factor. Performance is improved if the cavity is ventilated. Heat is transmitted through air cavity by convection and radiation. Cavity represents resistance that is not proportional to the thickness of the cavity. For thicknesses greater than 20 mm, the resistance to heat flow is nearly constant. Air cavity, however, may not be treated as replacement for higher
insulation, where needed as per the design requirements.
d) Surface finishes (Applying light coloured paints on walls) — Surface colour and finish plays an important role in heat gain and loss from a structure. If external surface of a building is painted with light colour, it will reflect solar radiation. But if the emissivity of the surface colour in the long wave region is also high, the heat flux into the building is considerably reduced. For example, whitewash has a lower reflectivity than aluminium, but will stay cooler when exposed to high solar radiation, due to its high emissivity at low temperatures. The effect of colour on external surfaces is more evident in lighter structure, which offers low resistance to heat flow, and because of low thermal capacity. Ongoing research has made possible paints that are dark but reflect most off infrared (IR) radiation, thereby preventing excessive heat gain.
8.1.2 Roofs
The roofs of buildings receive most of heat throughout the day. Predominantly used construction practices in the country especially in urban areas, mainly involve reinforced cement concrete (RCC) as the roofing element, which has high thermal conductivity. If the roof is exposed to solar heat, the temperature inside will also rise as the day progresses. When buildings are air conditioned, the purpose of the system is to maintain inside the building, a lower temperature than the ambient. If the roof slab is exposed to solar heat, it will allow continuous heat inside the building which in turn will add to the air conditioning load. If the roof is protected from heat incidence by suitably insulating the roof from the heat, the conditions inside can be controlled to a large extent so that the living environment inside the building remains below the ambient temperature throughout the day. The function of roof insulation is to insulate the building against heat inflow from outside during the day. The options for roof insulation are given in 8.1.2.1 to 8.1.2.2. The overall thermal transmittance from the exposed roof should be kept as minimum as possible and under normal conditions, the desirable value should not exceed 0.58W / (m²°C). The ceiling surface of floors which are not to be air conditioned may be suitably insulated to give an overall thermal transmittance not exceeding 1.16W / (m²°C). Some traditionally adopted methods of roof construction like stone Patti and jack-arched roof may be used after evaluating their thermal performance. Mechanism to shade the roof with vegetation will help a great deal in lowering solar exposures.
8.1.2.1 Over-deck and under-deck insulation
In this system a thermal barrier or insulation is provided over RCC roof, so that the amount of heat of the sun reaching the RCC slab of the roof is substantially reduced to prevent the slab from getting excessively heated up. In contrast, if the thermal barrier is provided under RCC roof, as in under-deck insulation, some heat passes through it and heats up the ambience of the room. This decreases the comfort level of the room and if the building is air conditioned, increases the air conditioning load. Over-deck insulation is, therefore, considered advantageous over under-deck insulation in hot climates. Over-deck insulation also protects waterproofing system from damage due to thermal stress caused by continuous variation in diurnal and seasonal temperatures. It also acts as a protection against mechanical damage to water proofing systems. Over-deck insulation material should have adequate compression resistance, low water absorption, resistance to high ambient temperature and low thermal conductivity. Over-deck insulation applications may be carried out by either of the following methodologies:
a) Use of preformed insulation materials — Preformed insulation materials used are classified as given below which may be laid, over the roof surface as per the manufacturers' recommendations:
Expanded polystyrene sheet.
Extruded polystyrene sheet.
Polyurethane/polyisocyanurate sheet.
Perlite board.
b) In-situ application using spray applied polyurethane — This is applied directly over the roof by spraying. This insulation has advantage of non-interference with internal constructional/operational activities of a building, jointless adhesion to the roof surface due to seamless and monolithic nature of spray, and speedy application. In-situ spray application involves a mixture of atmospheric air leading to open cell formation and may affect insulation performance over time. Therefore, it is preferable in complex locations where use of rigid boards is difficult or not possible. This insulation needs to be treated with proper water proofing treatment ensuring no water ingress into the insulation, as in case of the waterproofing treatment getting damaged, the water ingress into the insulation may lead to deterioration and adversely affecting the insulation properties.
c) Conventional roof insulation practices — There are a number of traditional roof insulation practices followed in the country
which have been effectively employed. These may include mud phuska and brick bat coba.
Other traditional practices of roof insulation — Inverted earthen pots may also be used for roof insulation. In this system burnt clay pots are placed in inverted positions and covered with filler material. The air trapped inside the pots act as insulator and renders insulating property to roof. Suitable water proofing treatment needs to be additionally applied [see also 9.2.4.1.1 (m)].
Cellular concrete may also be used depending on the thermal insulation requirement.
The thermo-physical properties of different roof constructions are given in Table 2 and Table 3 for flat roof and sloped roof, respectively.
NOTE — Thermal conductivity values are indicative and many other/traditional practices may be employed for achieving desired thermal properties.
Thermal properties of some commonly used insulating materials and building materials are given in Table 4.
For thermal performance of flat and sloped roofs with use of various other considerations of materials and for thermal properties of building and insulating materials, refer to good practice [11(2)] and SP41 ‘Handbook on Functional Requirements of Buildings’.
e) Other over-deck systems that minimise heat gains — There are other systems employing use of highly reflective and emissivity coatings that stay cooler in the summer thereby reducing energy costs, improving occupant comfort, cutting maintenance costs, increasing the life of the roof, and contributing to the reduction of heat island effect. Roofs with slopes less than 20Ú slope have a minimum initial solar reflectance of 0.70 and minimum emittance of 0.75. Cool roofs should be designed to have a minimum solar reflectance of 0.70 and a minimum thermal emittance of 0.75 or alternatively should achieve a minimum solar reflective index (SRI) of 82. Various types of cool roof systems are:
Roof coatings — These may be field applied or factory applied. Field applied roof coatings are applied directly onto the roof surface and may require an appropriate primer. Factory applied coatings are applied in factory and include coatings applied to metal sheets. Specialized white elastomeric coatings may be used for sloped roofs and cool colour polymer coatings may be used for
Table 2Typical Thermal Performance of Flat Roof Constructions (Clause 8.1.2.1)
Sl No.(1)
Specification of Roof(2)
U-Values W/(m2.K)(3)
i)
100 mm RCC
3.59
ii)
100 mm RCC + 100 mm lime concrete
2.78
iii)
100 mm RCC + 50 mm foam concrete + waterproofing
1.08
iv)
50 mm RCC + 25 mm expanded polystyrene
1.08
v)
50 mm expanded polystyrene + 50 mm RCC + waterproofing
0.62
vi)
25 mm expanded polystyrene + 50 mm RCC
1.09
vii)
100 mm RCC + 50 mm cinder concrete + 50 mm brick tile
2.07
viii)
100 mm RCC + 75 mm cinder concrete + 50 mm brick tile
1.76
ix)
115 mm RCC + 50 mm mud phuska + 50 mm brick tile
2.31
x)
115 mm RCC + 75 mm mud phuska+ 50 mm brick tile
2.01
xi)
150 mm clay unit
3.15
xii)
137.5 mm clay unit
2.99
xiii)
150 mm clay unit + 100 mm lime concrete
2.21
xiv)
137.5 mm clay unit + 100 mm lime concrete
2.14
xv)
100 mm cellular unit + 85 mm lime concrete
2.27
xvi)
125 mm cord unit + 85 mm lime concrete
2.13
xvii)
154 mm lime concrete using stone aggregate + 76 mm stone slab
3.07
xviii)
88.9 mm concrete using brick aggregate + 25.4 mm kota stone slab on each side
3.65
xix)
50.8 mm lime concrete using ballast aggregate + 114 mm reinforced brick and bitumen wash on top
2.45
xx)
50.8 mm lime concrete using brick ballast aggregate + 50.8 mm RCC slab + bitumen wash on top surface
4.02
xxi)
100 mm RCC + Inverted clay pots with mud phuska
2.344
xxii)
100 mm RCC + Extruded polystyrene 25 mm-36 kg/m3
0.749
xxiii)
100 mm RCC + Extruded polystyrene 30 mm-36 kg/m3
0.658
xxiv)
100 mm RCC + Extruded polystyrene 40 mm-36 kg/m3
Table 4 Thermal Properties of Building and Insulating Materials at Mean Temperature of 50°C (Clause 8.1.2.1)
Table 3Typical Thermal Performance of Sloped Roof Constructions (Clause 8.1.2.1)
Sl No.(1)
Specification of Sloped Roof(2)
U-Values W/(m2.K)(3)
i)
0.625 cm AC sheet
5.47
ii)
0.625 cm AC sheet + 2.5 cm air space + insulating board
2.44
iii)
0.625 cm AC sheet + air space + 5 cm fibre glass + 0.625 hard board
1.40
iv)
0.625 cm AC sheet + air space + 5 cm sandwich of fibreboard/ expanded polystyrene
0.65
v)
0.625 cm AC sheet + air space + 2.5 cm sandwich of fibreboard/ expanded polystyrene
1.22
vi)
0.3 cm GI sheet
6.16
vii)
2.5 cm tile + 2.5 cm bamboo reinforcement
3.56
viii)
5 cm tile + 2.5 cm bamboo reinforcement
3.20
ix)
2.5 cm thatch roof + 2.5 cm bamboo reinforcement
2.38
x)
5 cm thatch roof + 2.5 cm bamboo reinforcement
1.69
xi)
Mangalore tiles on wooden rafters
4.07
roof tiles, and these can be sprayed on existing roofs.
Broken china mosaic terracing — Properly sized broken pieces of glossy glazed tiles may be used as a cost effective cool roofing option.
Cool colours — Cool colour roofing materials are created by integrating pigments that reflect infrared energy, even though their colour may still absorb some of the visible spectrum. In this way, roofing products can be dark coloured and still be cool.
Traditional methods — Lime wash also renders similar property but has limited life and has to be reapplied.
Issues of excessive glare do arise with white roof coatings.
Sl No.
Type of Material
Density
Thermal Conductivity
Specific Heat Capacity
Sl No.
Type of Material
kg/m³
W/mK
kJ/kgK
(1)
(2)
(3)
(4)
(5)
i) Building materials:
i) Building materials:
i) Building materials:
i) Building materials:
i) Building materials:
1)
Burnt brick
1 820
0.811
0.88
2)
Mud brick
1 731
0.750
0.88
3)
Dense concrete
2 410
1.74
0.88
4)
RCC
2 288
1.58
0.88
5)
Limestone
2 420
1.80
0.84
6)
Stale
2 750
1.72
0.84
7)
Reinforced brick
1 920
1.10
0.84
8)
Brick tile
1 892
0.798
0.88
9)
Lime concrete
1 646
0.730
0.88
10)
Mud phuska
1 622
0.519
0.88
11)
Cement mortar
1 648
0.719
0.92
12)
Cement plaster
1 762
0.721
0.84
13)
Cinder concrete
1 406
0.686
0.84
14)
Foam slag concrete
1 320
0.285
0.88
15)
Gypsum plaster
1 120
0.512
0.96
16)
Cellular concrete
704
0.188
1.05
17)
AC sheet
1 520
0.245
0.84
18)
GI sheet
7 520
61.06
0.50
19)
Timber
480
0.072
1.68
20)
Timber
720
0.144
1.68
21)
Plywood
640
0.174
1.76
8.1.2.2 Green roof system
Green roofs have the potential to improve the thermal performance of a roofing system through shading, insulation, evapotranspiration and thermal mass, thus reducing energy demand of building for space conditioning. The green roof moderates the heat flow through the roofing system and helps in reducing the temperature fluctuations due to changing outside environment. If widely used, green roofs can reduce the problem of heat island effect which in turn reduces the energy consumption in urban areas. Green roof systems comprise a lightweight growing medium, plants and a root repellent layer in addition to the regular components of a roof. The additional components and thickness of the growing medium provides thermal insulation, while the green cover lowers ambient temperatures through evapotranspiration. Issues related to dead weight and water proofing should be considered while designing roof. There are three types of green roofs, as follows:
a) Intensive green roof— It is like a conventional garden or park with almost no limit on the type of available plants including trees and shrubs.
b) Extensive green roof — It is designed for little maintenance or human intervention once it is established.
c) Modular block green roof— It is designed in modular units which interlock and each module contains drainage systems and plants.
Use of photovoltaic panels for renewable energy (see 8.3.2) can also be advantageously used for their effect on shading of roof top.
8.1.3 Fenestration
8.1.3.1 Of all the elements of building envelope, windows and glazed areas are most vulnerable to heat gains. Windows are required to bring inside natural daylight and wind, however, with light it also bring in heat. Proper location, sizing and detailing of windows
and shading form is therefore a very important aspect in a solar passive building design. Primary factors/components of a window which have significant impact on energy and cost of the building are window size and placement, glazing, frame, shading (external and internal), and screens or Jalis.
8.1.3.1.1 Window size and placement
The following may be taken into consideration:
a) Height of window head — The higher the window head or lintel, the deeper the penetration of daylight.
b) Sill height (height from floor to the bottom of the window) — The optimum sill for good illumination as well for good ventilation should be between the workspace and head level of a person. For carrying out any task, the suitable work plane levels shall be in accordance with 4.1.3.3 of Part 8 ‘Building Service, Section 1 Lighting and Natural Ventilation’ of the Code. Strip windows provide more uniform daylight. Punched windows should be paired with work areas to avoid creating contrasts of light and dark areas. Windows close to task areas should be with optimum visual transmission without glare with good insulation performance as they may be source of thermal discomfort. Small horizontal openings close to the floors and the ceiling are extremely effective in reducing the window area to reduce heat ingress and provide adequate daylight levels in the space. In case of larger windows, glazing selection and shading effectiveness are quite important to control glare and heat gain.
Use of separate apertures for view and daylight — For good day lighting and glare control, window should have clear glass with a partition for maximum daylight penetration and tinted glass below the clear glass for glare control. The structure in between the two provides a visual break and an opportunity to attach light shelf or shading device.
d) Window wall ratio (WWR) — Window to wall ratio is the net glazing area (window area minus mullions and frame or approximately 80 percent of opening) divided by gross exterior wall area. Gross wall area is the overall area of a wall including openings such as windows and doors, with measurement taken horizontally from outside surface to outside surface and measured vertically from top of the floor to the top of the roof (see Fig. 4).
NOTE — The above represents only one approach in the entire range of window to wall ratio. The issue is primarily of window to wall ratio, and not window to glazing ratio.
Screens make effective windows which reduce heat ingress and yet allow the air movement.
8.1.3.1.2 Glazing
The most commonly used glazing material in openings is glass, though recently polycarbonate sheets are being used for skylights. The primary properties of glazing that impact energy use in buildings are,
a) visible transmittance (affecting daylight),
b) visible reflectance (affecting heat and light reflection),
c) thermal transmittance or U-value (affecting conduction heat gains),
d) solar heat gain (affecting direct solar gain),
e) spectrum selectivity (affecting daylight and heat gain),
f) glazing material, and
g) glazing colour (affecting the thermal and visual properties of glazing systems).
Use of insulated glazing units (IGU) may be considered in appropriate cases. IGU are hermetically sealed, multiple pane assemblies consisting of two or more glazing layers held and bonded at their perimeter by a space bar typically containing a desiccant material. The glazing used in IGUs may be clear, tinted or coated or reflective. The spacer serves to separate the panes of glass and to provide a surface for primary and secondary sealant adhesion. As heat transfer at the edge of the IGU is greater than its centre, the choice of material for spacer is critical to the performance of IGU. The hermetically sealed space between glass panes may be filled with dry air or other alternatives such as argon and krypton.
While selecting a glazing, attention should be given to the following:
Selecting between dual pane and single pane glazing.
Selecting a spectrally selective glazing (to keep off infra red and permit visible light).
Balancing the conflict between glare and light.
Trading off window size and glazing selection.
Dark or tinted glass may not necessarily provide good solar control.
Not depending on glazing alone to reduce heat gain and discomfort.
Selection of frame for glazing (see 8.1.3.1.3).
Varying the selection and configuration of a glazed facade.
8.1.3.1.3 Frame
The type and quality of window frame affects air infiltration and heat gain/heat loss characteristics of windows. Window frames are usually made of aluminium, steel, wood, PVC, RCC, fibreglass or composites of these materials. Wood, fibreglass, RCC and vinyl frames are better insulators than metal. Some frames are designed with internal thermal breaks that reduce heat flow through the frame. These thermally broken frames can resist heat flow considerably better as compared to those without thermal breaks. The sealing between the openings and the window frames, and between the opening sashes of windows and fixed portions, are important as major heat loss happens from this area due to poor design of sealant material, and should be ensured. Adequate provision shall also be made to ensure that the frames are not susceptible to water ingress in case of driving rain.
For further details, reference may be made to 9.2.3.2.
8.1.3.1.4 Shading devices
Direct sunlight can cause glare. Controls are therefore necessary to allow diffused natural light. Windows shading devices may be employed which help in keeping out the heat, block uncomfortable direct sun, and soften harsh daylight contrasts. Shading devices are also critical for visual and thermal comfort and for minimizing mechanical cooling loads. The three main ways of controlling direct sunlight are:
a) External shading and screens/Jalis,
b) Internal shading,
c) Use of solar control glass (spectrally selective), and
d) Horizontal/vertical or angled louvers.
8.1.3.2 Design for windows in air conditioned and non air conditioned spaces/mixed mode ventilated spaces
8.1.3.2.1 Windows in air conditioned buildings
Window (including both glazing and frame) affects the
energy performance of an air conditioned space by impacting the HVAC energy consumption of the building and also the energy consumption for indoor lighting. Following are major types of energy flow which occur through a window impacting the HVAC energy consumption (see also Fig. 5):
a) Non-solar heat losses and gains in the form of conduction, convection, and radiation — The non-solar heat flow through a window occurs due to the temperature difference between the indoor and outdoor. Window loses heat to the outside during the winter season and gains heat from the outside during the summer season, adding to the heating/cooling load in a building.
b) Solar heat gains in the form of radiation — The direct solar radiation entering into a conditioned space adds to the cooling load in summers and reduces heating load in winters in a building.
c) Infiltration — Infiltration is the unregulated exchange of air between indoors and outdoors through joints and cracks around window frame, sash and glazing. The air tightness of a window depends on both the characteristics of the window such as sash type and overall quality of window construction and the quality of the installation. These air exchanges can significantly influence indoor thermal comfort and consequent heating and cooling loads.
FIG. 5 TYPICAL FLOW OF SOLAR HEAT AND AIR INFILTRATION THROUGH A GLAZED WINDOW SECTION
Following are various parameters, related to the thermal performance of a window which should be considered to achieve energy efficiency in air conditioned building:
U-value of fenestration — The U-value of a single pane window is mainly due to the thin films of still air on the interior and moving air on the external glazing surfaces. The glazing itself doesn't offer much resistance to heat flow. Double glazing units, help reduce the U-value by creating still air (insulated) spaces. In addition to the normal double glazed windows, other options aimed at decreasing U-values, such as low-emittance (low-E) coatings and gas fills, may also be available. A low-E coating is a microscopically thin, virtually invisible, metal or metallic oxide coating deposited on a glazing surface. The coating may be applied to one or more of the glazing surfaces facing an air space in a multiple-pane window. The coating limits radiative heat flow between panes by reflecting heat. In case of air filled panes, the air-gap between window panes can be filled with gases which have better thermal resistance property than air such as argon and krypton.
For details regarding window frames and their thermal performance, reference may be made to 8.1.3.1.3.
Solar heat gain coefficient (SHGC) of fenestration — Additional glazing layers provides more barriers to solar radiation, thus reducing the SHGC of a window. Tinted glazing, such as bronze and green, provide lower solar heat gain coefficients compared to the clear glass. Spectrally selective glazing, including some low-E coated glazing with low solar heat gain, block out part of the heat from the sun such as from infra-red radiations, while maintaining higher visible transmittances.
Shading and adjusted SHGC — Exterior or interior shading devices such as awnings, louvered screens, sunscreens, venetian blinds, roller shades, and drapes can complement and enhance the performance of windows with low SHGC. Many shading devices have an advantage that they can be adjusted to vary solar heat transmission with the time of day and season. Adjustable shades can also be integrated to permit some extra heat gain in the winter, if required.
Exterior shading devices are more effective than interior devices in reducing solar heat gain because they block radiation before it passes through a window. Light-coloured shades are preferable to dark ones because they reflect more and absorb less, radiation.
Projection factor (PF) — The projection factor for horizontal overhang and vertical fins may be taken as follows:
a) For horizontal overhang — Projection factor for overhang is calculated by measuring the depth of the overhang (A) and dividing that by the distance from the bottom of the window to the lowest point of the overhang (B) (see Fig. 6).
b) SHGC for a window having an external shading device can be calculated by multiplying the SHGC value of the window with the M factor given in Table 5 for different projection factors for different orientations. The factor M is the relative reduction in the annual solar cooling load attributed to the overhangs and/or vertical fins for the given projection factor.
Table 5M Factor for Different Projection Factors for Different Orientations [Clauses 8.1.3.2.1(4)(b) and B-3]
Location
Orien-tation
Overhang M Factor for the Projection Factor
Vertical Fin M Factor for Projection Factor
Overhang + Vertical Fin M Factor for Projection Factors
0.25 to 0.49
0.50 to 0.74
0.75 to 0.99
More than 1.00
0.25 to 0.49
0.50 to 0.74
0.75 to 0.99
More than 1.00
0.25 to 0.49
0.50 to 0.74
0.75 to 0.99
More than 1.00
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
15° North Latitude or greater
N
0.88
0.80
0.76
0.73
0.74
0.67
0.58
0.52
0.64
0.51
0.39
0.31
E/W
0.79
0.65
0.56
0.50
0.80
0.72
0.65
0.60
0.60
0.39
0.24
0.16
S
0.79
0.64
0.52
0.43
0.79
0.69
0.60
0.56
0.60
0.33
0.10
0.02
Less than 15° North Latitude
N
0.83
0.74
0.69
0.66
0.73
0.65
0.57
0.50
0.59
0.44
0.32
0.23
E/W
0.80
0.67
0.59
0.53
0.80
0.72
0.63
0.58
0.61
0.41
0.26
0.16
S
0.78
0.62
0.55
0.50
0.74
0.65
0.57
0.50
0.53
0.30
0.12
0.04
32
c) For vertical fins — Projection factor for vertical fin is calculated by measuring depth of the vertical fin and dividing it by the distance from the window jamb to the farthest point of the external shading projection (see Fig. 7).
Impact on lighting energy consumption — During day time when natural light outside, is available in abundance, window can be utilized as a tool to harness natural light from Sun and sky to light the space. Buildings, in which artificial lighting is integrated with the day lighting, can reduce their energy consumption significantly. Good day lighting in a building depends upon the following factors:
a) Window wall ratio (WWR) — See 8.1.3.1.1(d).
b) Visible light transmittance (VLT) of glazing.
c) Day-lighting and window design — Day lighting is utilization of light from the sun and sky to augment or replace electric light. Appropriate fenestration and lighting controls can be used to modulate daylight admittance and to reduce electric lighting, while meeting the occupants' visual comfort.
d) Day-lit perimeter zone for vertical fenestration — The day-lit zone associated to a window can be defined as an area having a depth which is twice the window height (measured from ground) and having the width which is equal to the window width plus 1.0 m on each of
FIG. 6 PROJECTION FACTOR FOR HORIZONTAL OVERHANG FOR A TYPICAL WINDOW SECTION
FIG. 7 PROJECTION FACTOR FOR VERTICAL FINS
the vertical sides of window as indicated in the Fig. 8.
The fenestration area, located above 1.0 m but below 2.2 m is considered as vision window area. The vision window area is usually provided with the glass with lower VLT in order to reduce glare.
The fenestration area located above 2.2 m is considered as daylight window area. Larger the daylight window
All dimensions in metre.
Dimension of day-lit perimeter: Depth (m) = 2 x Y; Width (m) = X + 1 + 1.
FIG. 8 DAY-LIT PERIMETER ZONE ASSOCIATED TO A WINDOW
c)
Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up
area more will be the daylight penetration into a space. The daylight window area is usually provided with glass with higher VLT so as to receive daylight to the greater depths of the space. The daylight window area can be designed in form of light shelves, as shown in Fig. 9, which enhance the penetration of daylight. The extent of natural light penetration into the room depends on the colour (reflectance) of the interior wall surfaces, the furnishing colour and partly the colour of the flooring.
The following should be determined and shall conform to the requirements of this Code:
i) U-value for a fenestration product (including the sash and frame).
ii) The SHGC for a fenestration product (including the sash and frame).
iii) Air leakage through fenestration, shall not exceed 2.0 litre /s.m².
iv) Window wall ratio on a facade, correlated to the visible light transmittance of the glazing which shall not exceed 60 percent.
NOTE — It may be noted that screens make effective windows which reduce heat ingress and yet permit natural ventilation.
8.1.3.2.2 Window design guideline for non-conditioned/mixed mode buildings
The following may be considered in selection of type of windows:
a) Horizontal pivot windows — These produce very effective ventilation because large open areas are created at a separation equivalent to the window height. Air will tend to enter at the lower level and exit via the top of the window. These are easily adjustable to provide control of the ventilation rate. These are often used in taller buildings, as both sides of glass can be cleaned from the inside of the building with ease. The main disadvantage of this type of window is that, when opened, the top of
SECTION OF A ROOM THROUGH A WINDOW GLAZING
FIG. 9 ARRANGEMENT SHOWING VISION WINDOW AREA AND DAY LIGHT WINDOW AREA
the sash interferes with the curtains.
Vertical pivot windows — These are less efficient than horizontal pivot windows because the open area is uniformly distributed throughout the height of the window rather than concentrated at the extremes; but these can work well in combinations. There is an advantage that these can be both opened and closed by pushing and are easy to clean from the inside. When fully open these offer a safe vertical barrier. The inward opening section may interfere with curtains when fully open.
Casement windows — These offer the same advantages as vertical pivot windows but are susceptible to gusts. The most commonly used are double sided hinged outward opening windows which have great versatility with respect to air flow control. Most casement windows are designed to open outwards, which poses a problem for installation of window air conditioners.
d) Top/bottom hung windows — These are less effective as ventilators than pivot windows as all the opening area is concentrated at one end, the top or bottom of the window.
e) Sliding windows — These have similar characteristics as horizontal or vertical pivot windows. Sliding windows are easy to open; these slide to the side instead of having to be pushed inside/outside. A good seal is important in reducing draughts and energy loss when closed. Cleaning the inside of slider windows is easy, but cleaning the outside may be difficult.
f) Tilting top vents — These provide smaller opening areas than the other systems as these occupy only a relatively small proportion of the window height. However, these can provide good draught-free ventilation, especially in cross-ventilation mode. The inward opening function of tilt and turn windows limit the available space.
The window may also be provided with fixed/sash/sliding/roller insect screens to allow fresh air without the inlet of mosquitoes and other insects through openable windows.
As compared to air-conditioned spaces, the window design in non-conditioned/mixed mode buildings takes a different approach. The glazing system for windows in non-conditioned/mixed mode spaces is usually single pane/panel glazed units as the windows will be opened to allow ventilation. Thus there is less relevance to install double glazing units with low SHGC and U-values.
However, in the non-conditioned/mixed mode buildings the shading device plays a crucial role in the thermal performance of a window. Windows on facades, for different orientations, should be provided by the shading devices which can cut the direct incident solar radiation for the critical solar angles.
In the non-conditioned buildings/mixed mode buildings, penetration of direct solar radiation needs to be regulated. The critical Horizontal Solar Angle (HSA) and Vertical Solar Angle (VSA) (see Fig.1) for fenestrations located on the cardinal directions should be regulated by designing appropriate shading devices. The horizontal solar angle at critical hours can be regulated by the vertical fins provided as external shading devices. The vertical solar angle at critical hours can be regulated by the horizontal fins provided as external shading devices.
The maximum permissible WWR on a facade should not exceed 60 percent. Window opening requirements for naturally ventilated low rise residential and office buildings include the following:
a) In order to allow outside air to enter the space, window openings should be oriented appropriately to optimize heat and solar heat gain.
b) In order to facilitate cross ventilation, location of window openings should be located opposite to each other on walls parallel to each other.
c) In order to achieve the required air change per hour in a given space, cross ventilation and stack ventilation mode of natural ventilation should be adopted.
The external shading devices can be designed in various ways to stop the solar radiation entering through the window. Figure 10 shows the commonly used shading devices.
Example to design shading device for a window
Design of shading device for a window of height 1.5 m and width 3.0 m to cut the HSA of 45° and VSA of 60° should be as follows:
a) Design of shading device to cut the VSA — The vertical solar angle of 60° can be cut by providing a single horizontal overhang of length 867 mm or it can be cut by providing two horizontal projections 60 mm thick each of length 415 mm placed at a distance of 720 mm as shown in Fig.11.
The length and spacing can be calculated either by the drafting softwares by graphical method or by manually calculating using the following formula:
Depth of shading device
=Spacing between the shadingdevice×tan(90∘−
For a given VSA, either of the values for depth or spacing between shading overhangs can be selected to get the value of the other.
b) Design of shading device to cut the HAS — The horizontal solar angle of 45° can be cut by providing a single vertical fin of length 3 000 mm or it can be cut by providing four vertical fins 60 mm thick each of length 705 mm placed at a distance of 705 mm as shown in Figure 12.
The length and spacing can be calculated either by the drafting softwares by graphical method or by manually calculating using the formula:
Depth of vertical fins = Spacing between the vertical fins × tan (90° – HSA)
For a given HSA either of the values for depth or spacing between vertical fins can be selected to get the value of the other.
It is desirable to break single overhang with larger depth into multiple overhangs of smaller length. It enhances the amount of (diffused) daylight penetration in the space. Figure 13 shows the comparison between amount of daylight penetration for two shading devices, one with single deep overhang and the other with multiple smaller overhangs. Another alternative is use of screens which make effective window/opening protection by reducing heat ingress and yet permitting air movement.
FIG. 10 COMMONLY USED SHADING DEVICES
All dimensions in millimetres. FIG. 12 DESIGN OF SHADING DEVICE TO CUT HSA
All dimensions in millimetres.
FIG. 11 DESIGN OF SHADING DEVICE TO CUT VSA
Window design for natural ventilation — Windows are required to provide natural cooling through ventilation. Optimized window design helps to achieve thermal comfort with no additional energy and/or financial investment. Optimized window design helps to reduce dependence on air conditioning where natural ventilation is possible and helps in reducing discomfort in naturally ventilated spaces. Following are the general guidelines for achieving effective natural ventilation:
Natural ventilated buildings should take advantage of the predominant wind originating from east and west directions to maximize cross ventilation. Stack ventilation can be enhanced by providing openings on the opposite side of the wall, where the inlet opening should be located at the bottom most part of the wall and outlet openings should be on the topmost part of the opposite wall in order to increase the height difference between the two (see Fig. 14).
Naturally ventilated buildings should have a narrow room width; and it is difficult to naturally ventilate buildings with room depth more than 15m.
For total area of openings (inlet and outlet) of 20 to 30 percent of floor area, the average indoor wind velocity that may be achieved is around 30 percent of outdoor wind velocity. Even on increasing the size of window further, the maximum indoor wind velocity does not exceed 40 percent of outside wind velocity.
To enhance physiological comfort through natural ventilation, the bottom side of the
opening may be kept at 85 percent of the height of the room taken from ceiling or as per Table 6 for the corresponding occupant activity.
Section in Elevation
FIG. 13 COMPARISON OF DAYLIGHT PENETRATION WITH USE OF TWO SHADING DEVICES NAMELY DEEP OVERHANGS AND LOUVERS
FIG. 14 ARRANGEMENT OF OPENINGS IN WALLS FOR ENHANCED VENTILATION
Table 6 Critical Height Requirement for Physiological Cooling[Clause 8.1.3.2.2(d)]
Sl No.
Pattern of Activities
Recommended Height of the Bottom Side of Opening
m
(1)
(2)
(3)
i)
Sitting on chair
0.75
ii)
Sitting on bed
0.60
iii)
Sitting on floor
0.40
Clerestory or vented skylight provides an opening for vitiated air to escape through natural buoyant ventilation. The light well of the skylight may also act as a solar chimney to augment natural buoyant flows.
Openings in lower part of the structure, such as basement windows, should be provided to complete the ventilation system.
(2)
i)
Uncovered parking areas:a) Parking lots and drives
1.6 W/m²
ii)
Building grounds:a) Walkways less than 3 m wideb) 1) Walkways 3 m wide or greater2) Plaza areas3) Special feature areasc) Stairways
3.28 W/linear metre 2.15 W/m² 10.76 W/m²
iii)
Building entrances and exits:a) Main entriesb) Other doors
98.52 W/linear metre of door width 65.68 W/linear metre of door width
iv)
Canopies and overhangs:a) Canopies (free standing and attached and overhangs)
13.45 W/m²
v)
Outdoor sales:a) Open areas (including vehicle sales lots)b) Street frontage for vehicle sales lots in addition to open areas allowance
5.38 W/m² 65.68 W/linear metre
vi)
Building facades
2.15 W/m² for each illuminated wall or surfaceor 16.42 W/linear metre for each illuminated wall or surface length
vii)
Automated teller machines (ATMs) and night depositories
270 W per location plus 90 W per additional ATM per location
viii)
Entrances and gatehouse inspection stations at guarded facilities
13.45 W/m² of uncovered areas covered areas are included under the canopies and overhangs
ix)
Loading areas for law enforcement, fire, ambulance and other emergency service vehicles
5.38 W/m² of uncovered areas covered areas are included in the canopies and overhangs
x)
Drive-up windows at fast food restaurants
400 W per drive-through
xi)
Parking near 24 h retail entrance
800 W per main entry
xii)
Landscaped areas, including individual house courtyards, terraces
2.15 W/m²
with less than 10 percent lumens above 90° from the nadir (see Fig. 3) and the lighting power density of the facade lighting may be as given in Table 1.
7.5.4 Light Trespass Allowance
The light trespass allowance may vary for different site surroundings, and a light should also vary for different settings depending upon the requirements. The site settings may be kept as,
a) Dark — For rural setting.
b) Low lighting setting — For residential areas/sub-urban areas and townships.
c) Medium lighting setting — For medium rise buildings, high rise buildings, commercial/office areas and high density for non-commercial area.
d) High lighting setting — For malls, entertainment areas and city centre areas.
3.11Disaster Preparedness
3.11.1 General
Disaster preparedness as part of approach to sustainability is in addition to the normal considerations of structural safety, health safety, fire safety and public safety taken into account in the building planning, design, construction, use and occupancy, and end of life. The disasters may be natural disasters such as earthquake, floods, cyclone, tsunami, landslides and avalanches; and man-made disasters such as nuclear, chemical, and biological disasters, explosions, act of sabotage and terrorism. Consequence of such disasters could be life threatening and debilitating in the long run.
Also man-made or natural disasters can trigger combined form of progressive disasters. The severity index is another important factor which will be governed by geomorphology, wind flows and cyclonic vulnerability, and climatic zone wherein the construction is proposed. See Part 6 ‘Structural Design’ of the Code for structural design of buildings for various loads, forces and effects using various building material options and structure systems.
3.11.2 Approach
The approach to disaster mitigation and management should be holistic and integrated with emphasis on prevention, mitigation and preparedness rather than being relief centric. The approach should emphasize on preparedness through planning, protection, training and partnership measures with associated stakeholders.
These efforts are aimed to protect and conserve existing development and also to minimise losses to lives, livelihood and property with clear cut focus on protection of environment. The approach shall be towards integrating disaster management as a part of design development, construction practices and management, operation and maintenance and end of life strategies. The required awareness should be achieved through multi stakeholder based planning, awareness, displays, mock drills and adequate training to both aged and young.
The disaster mitigation should also comprise identification of risks during construction, risks during occupancy stages/operations and preparing disaster preparedness plan by decommissioning. The occupancy type, density of occupancy and any specific/strategic aspects should be considered while working out disaster preparedness plan to achieve minimum damages and/or losses to lives, livelihood, properties and environment for the sustainable buildings for least damages or losses.
3.11.3 Disaster Risk Assessment and Mitigation
The formulation of disaster preparedness plan for any location should comprise the following steps:
a) Step 1 — Identify the geomorphology; river, coastal and cyclonic proximity; and climatic zone related disasters risks.
b) Step 2 — Identify population, business related disasters and vulnerabilities.
c) Step 3 — Carry out risk assessment through hazard analysis and vulnerability analysis including possible combining effects of multiple hazards. Also include the effect on micro-climate and environment biodiversity. Coastal zones which are falling in high cyclonic flood zone, tsunami, and seismic zones of high intensity and landslide sensitive areas should receive special attention.
d) Step 4 — Identify the socio-economic, socio-political hazards and vulnerabilities attributed to man-made disasters.
e) Step 5 — Prepare a disaster risk mitigation plan supported with sufficient budgetary provisions.
f) Step 6 — The disaster resistant building construction and infrastructure development features shall form part of the submittal to the Authority for statutory approvals.
g) Step 7 — Establish/nominate a responsible senior person/safety officer as controller for regulating, planning and monitoring disaster preparedness plan for whole project. Carry out all constructions, installations and operations in line with the disaster resistant features for each of the vulnerabilities.
h) Step 8 — Prepare and have mock drills at regular intervals for creating awareness and response preparation amongst stakeholder involved.
j) Step 9 — Prepare operation manual for post-construction operation and up keep of disaster resistant features and equipment.
The basic action plan should focus on capacity building amongst stakeholders involved, communication, coordination, role of information technology, role of every individual working at site and role of emergency response cell of building in conjunction with the mitigation plans of local/state level authorities. The possible after-effects on human and natural habitats and mitigation plan should form integral part of disaster preparedness plan for least damage to human life, built environment and related ecosystems.
8.3Renewable Energy Integration in Envelope
8.3.1 Integration of Solar Thermal Technologies
Solar collectors that harness the solar energy directly into usable heat can be aesthetically integrated with the building envelope or they may be mounted on the roof of building.
8.3.2 Integration of Photovoltaic Technologies
Building integrated photovoltaic (BIPV) system is the integration of photovoltaic (PV) and the building envelope. The PV modules can be designed and installed to serve the double purpose of both power generation and that of the building skin replacing conventional building envelope materials. By avoiding the cost of conventional materials, the incremental cost of photovoltaic is reduced and its life cycle cost is lower.
A complete BIPV system includes the following:
a) PV modules (which may be thin-film poly or mono crystalline, amorphous with transparent, semi-transparent, or opaque backing);
b) Charge controller, to regulate the power into and out of the battery storage bank (in standalone systems);
c) Power storage system, generally comprising utility grid in utility-interactive systems or, a number of batteries in stand-alone systems;
d) Power conversion equipment including an inverter to convert the d.c. output of PV modules to a.c. compatible with the utility grid;
e) Backup power supplies such as diesel generators (optional), typically employed in stand-alone systems; and
f) Appropriate support and mounting hardware, wiring, and safety disconnects.
While photovoltaic panels as in (a) are considered as PV array, other components given in (b) to (f) are usually referred to as the balance of system (BoS). Not only solar photovoltaic technologies but other ways of producing renewable energy may also be integrated in to design, depending upon suitability to geomorphological conditions, geo-thermal pumps, wind, etc.
3.2Elements of Sustainability
The generalized design process towards sustainability should creatively address the following considerations:
a) Set the design parameters to be implemented to be equal to or higher than benchmarking standards given in this Code.
b) Make the basic performance requirements and set standards, applicable/ selectively adaptable to the climatic zone and geological conditions in which the construction is proposed.
c) Have deep understanding of requirements of performance and human comfort in a building and its surroundings, considering building type and use, quality of building and plumbing services as desired, needs of persons with disabilities and of different age groups, and other parameters.
d) Question the need, identify their optimum levels in long term scenario, and take the design provisions to that level only.
e) Ensure what is sustainable today, remains that way in decades to come, and ensure the required performance levels of systems designed. If required extensive damages done could also be rectified/reversed in course of time.
f) Ensure that sustainability is not only in parts, but also a holistic effort and local action should contribute to sustainability.
g) Make efforts to maximize the use of traditional wisdom in design, wherever applicable, as it represents the knowledge about the long-term behaviour of materials and technology and their strengths as well as weaknesses.
h) While having an open approach, assess new materials and technologies for their long-term impact in the context of the country and its development priorities, before accepting them for use.
j) Take decision making processes to measurable levels wherever feasible, in order to make informed choices. Also by willing to accept limitations of decisions made.
k) Take the savings' benchmark targets closer to the minimum consumption standards; undertake value engineering exercises for deciding among the options.
This process emphasizes the requirement of bottom up approach which invariably considers microclimatic and cultural conditions around.
NOTE — The ‘bottom up approach’ concentrates more on how little is consumed; pursue deep understanding of sustainability; uses low technology innovations, materials and practices; recognizes performance to be more important than intent; and necessitates the use of common knowledge and common sense in design decisions. On the contrast, the ‘top down approach’ concentrates more on how much energy is saved; accepts the understanding of sustainability, may not be developed indigenously, more readily; uses high technology innovations, materials and practices; is driven by green brand and accompanying recognitions based on intent; and necessitates expert inputs and simulations.
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 43 mm polyurethane of 36 kg/m3+ brick tiling
0.409
xlvi)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 71 mm expanded polyurethane of 24 kg/m3+brick tiling
0.409
xlvii)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 58 mm extruded polyurethane of 29 kg/m3+brick tiling
0.409
xlviii)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 140 mm exfoliated vermiculite of 264 kg/m3+brick tiling
0.409
xlix)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 43 mm polyisocynuarate of 32 kg/m3+brick tiling
0.409
l)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 73 mm polyurethane of 36 kg/m3+brick tiling
0.261
li)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 122 mm expanded polystyrene of 24 kg/m3+brick tiling
0.261
lii)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 98 mm extruded polystyrene of 29 kg/m3+brick tiling
0.261
liii)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 240 mm exfoliated vermiculite of 264 kg/m3+brick tiling
0.261
liv)
15 mm cement plaster + 150 mm RCC + 100 mm brick bat coba + 73 mm polyisocynurate of 32 kg/m3+brick tiling
0.261
22)
Glass
2 350
0.814
0.88
23)
Alluvial clay (40 percent sands)
1 958
1.211
0.84
24)
Sand
2 240
1.74
0.84
25)
Black cotton clay (Madras)
1 899
0.735
0.88
26)
Black cotton clay (Indore)
1 683
0.606
0.88
27)
Tar felt ( 2.3 kg/m² )
0.479
0.88
28)
AAC block of 200 mm
749.6
0.089
1.0
29)
Fly ash clay brick
1 240
0.44
30)
Sand lime brick
1 820
0.90
31)
Vermiculite tiles
1 254
0.432
32)
Perlite concrete
1 000
0.261
33)
Expanded polystyrene concrete
932
0.231
Table 4 — (Concluded)
Table 4 — (Concluded)
Table 4 — (Concluded)
Table 4 — (Concluded)
Table 4 — (Concluded)
(1)
(2)
(3)
(4)
(5)
ii) Insulating materials:
ii) Insulating materials:
ii) Insulating materials:
ii) Insulating materials:
ii) Insulating materials:
1)
Expanded polystyrene
16.0
0.038
1.34
2)
Expanded polystyrene
24.0
0.035
1.34
3)
Expanded polystyrene
34.0
0.035
1.34
4)
Foam glass
127.0
0.056
0.75
5)
Foam glass
160.0
0.055
0.75
6)
Foam concrete
320.0
0.070
0.92
7)
Foam concrete
400.0
0.084
0.92
8)
Foam concrete
704.0
0.149
0.92
9)
Cork slab
164.0
0.043
0.96
10)
Cork slab
192.0
0.044
0.96
11)
Cork slab
304.0
0.055
0.96
12)
Rock wool (unbonded)
92.0
0.047
0.84
13)
Rock wool (unbonded)
150.0
0.043
0.84
14)
Mineral wool (unbonded)
73.5
0.030
0.92
15)
Glass wool (unbonded)
69.0
0.043
0.92
16)
Glass wool (unbonded)
189.0
0.040
0.92
17)
Resin bonded mineral wool
48.0
0.042
1.00
18)
Resin bonded mineral wool
64.0
0.038
1.00
19)
Resin bonded mineral wool
99.0
0.036
1.00
20)
Resin bonded mineral wool
16.0
0.040
1.00
21)
Resin bonded mineral wool
24.0
0.036
1.00
22)
Exfoliated vermiculite (loose)
264.0
0.069
0.88
23)
Asbestos mill board
1 397.0
0.249
0.84
24)
Hard board
979.0
0.279
1.42
25)
Straw board
310.0
0.057
1.30
26)
Soft board
320.0
0.066
1.30
27)
Soft board
249.0
0.047
1.30
28)
Wall board
262.0
0.047
1.26
29)
Chip board
432.0
0.067
1.26
30)
Chip board (perforated)
352.0
0.066
1.26
31)
Particle board
750.0
0.098
1.30
32)
Coconut pith insulation board
520.0
0.060
1.09
33)
Jute fibre
329.0
0.067
1.09
34)
Wood wool board (bonded with cement)
398.0
0.081
1.13
35)
Wood wool board (bonded with cement)
674.0
0.108
1.13
36)
Coir board
97.0
0.038
1.00
37)
Saw dust
188.0
0.051
1.00
38)
Rice husk
120.0
0.051
1.00
39)
Jute felt
291.0
0.042
0.88
40)
Asbestos fibre (loose)
640.0
0.060
0.84
41)
Closed cell flexible elastomeric foam - NBR
40-55
0.043
1.20
VSA
)
The design process itself can play a significant role in creating built environment respecting all principles of sustainable development. This has to take into account various climatic zones (like hot-dry, warm-humid, composite, temperate and cold climates) as well as sun path movements, location (prone to tsunami, hurricane, etc), annual wind directions and geological conditions in the design of building, its orientations, wall and roof materials combinations, space layout, fenestrations and landscape. A solar passive architecture that places minimum energy demand in maintaining thermal comfort should be explored foremost.
The sustainable design process should be based on the principles of universal design as per Part 3 'Development Control Rules and General Building Requirements' of the Code, so as to address accessibility needs of persons with disabilities and persons of different age groups.
Functional requirements of buildings have to also measure up to the required comfort levels demanded for all types of user requirements.
3.3 Life Cycle Sustenance
The process flow from concept, design, construction, commissioning, operation and maintenance, and also decommissioning and disposal at the end of useful life of structure, should be planned and important steps
chalked out for sustainable development. This should also take care of possible reuse/recycle of materials/components/structure or parts thereof. Ideally close the loop (cradle to grave) with regards to resources originally used.