1.1 This Code (Part 9/Section 2) covers the design, layout, construction and maintenance of drains for foul water, surface water, subsoil water and sewage together with all ancillary works, such as connections, manholes and inspection chambers used within the building and from building to the connection to a public sewer, private sewer, individual sewage-disposal system, cess-pool, soakaway or to other approved point of disposal/treatment work.
NOTE — A sanitary drainage system consists of a building sewer, a building drain, a soil and/or waste stack, horizontal branches or fixture drain, and vents. The sanitary drainage of a large building may have a number of primary and secondary branches, and several soil and/or waste stacks, each of them in turn may have a number of horizontal branches.
Part 9 Section 2Drainage and Sanitation
Various tables on the requirements for fitments for drainage and sanitation for various occupancies have been updated, and a new table for shopping malls and retail buildings has been included.
Enabling provisions for use of corrugated pipes, low noise pipes and under slung pipes have been included.
Information about bio-toilets has been added.
Typical mounting arrangements for various plumbing fixtures, including drainage systems and ventilation have been illustrated.
A new table for calculation of single stack sizing has been included.
Various additional requirements relating to layout of drainage and sanitation system have been added.
Venting system for high rise buildings, along with a comprehensive table on size and developed length of stack vents and vent stacks, has been included.
General provisions on design of drainage pipes have been elaborated.
Provisions relating to gradients of drainage pipes have been elaborated.
The table on fixture unit for different types of fixtures has been updated.
The tables on maximum number of fixture units that can be connected to branches and stacks, and to building drains and sewers, have been updated.
New provisions on design requirement for high rise buildings drainage system have been included.
The minimum diameter for floor drains outlets before connecting to floor trap has been included.
Provisions related to manhole covers and recommended locations have been included.
Provision for estimation of storm water runoff and coefficient of runoff for various surfaces have been included.
The table on sizing of rainwater pipes for roof drainage has been updated.
The illustration on artificial ground water recharge structure has been detailed.
Guidelines relating to siphonic drainage system for large roofs have been included.
Provisions on rainwater harvesting for plotted/group housing developments and deep well/bore well recharging, have been included.
Clarifications and recommendations on use of septic tanks have been made.
New provisions related to pumping and treatment of sewage have been included.
A provision on treatment of waste water and usage of recycled water has been included through cross-reference to Section 1 ‘Water supply’ of this Part of the Code.
Provisions have been reviewed and updated from the point of view of accessibility by elderly and persons with disabilities, also, in this context, duly giving cross-reference to 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
Certain terminologies have been included and some have been updated.
Cross-referred standards have been updated.
This Section is largely based on the following Indian Standards:
IS 1742 : 1983 Code of practice for building drainage (second revision)
IS 4111 (Part 1): 1986 Code of practice for ancillary structures in sewage system: Part 1 Manholes (first revision)
IS 5329 : 1983 Code of practice for sanitary pipe work above ground for buildings (first revision)
IS 6295 : 1986 Code of practice for water supply and drainage in high altitudes and or sub-zero temperature regions (first revision)
A reference to SP 35:1987 ‘Handbook on Water Supply and Drainage’ may be useful, from where also, assistance has been derived.
All standards, whether given herein above or cross-referred to in the main text of this Section, are subject to revision. The parties to agreement based on this section are encouraged to investigate the possibility of applying the most recent editions of the standards.
In the formulation of this Section, reference has also been made to the following:
International Plumbing Code 2015, International Code Council, and
Uniform Plumbing Code 2015, International Association of Plumbing and Mechanical Officials
2Terminology
For the purpose of this Section, the following definitions shall apply in addition to the definitions given in accepted standards [9-2(1)].
2.1 Air Admittance Valve — One way valves designed to allow air to enter drainage system when negative pressure develops in the system. The purpose is to provide a method of allowing air to enter the drainage system for prevention of siphonage of traps.
2.2 Air Break — Physical separation which may be a low inlet into the indirect waste receptor from the fixture or device indirectly connected.
2.3 Air Gap, Drainage — Unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe, plumbing fixture or appurtenance conveying waste to flood level of the receptor.
2.4 Back Up — A condition where the waste water may flow back into another fixture or compartment but not back into the potable water system.
2.5 Back Water Valve — Device installed in a drainage system to prevent reverse flow.
2.6 Bath Room Group — Group of fixtures consisting of water closet, lavatories bath tub or shower and other fittings with a floor drain located together.
2.7 Battery of Fixtures — Any group of two or more similar adjacent fixtures which discharge into a common horizontal waste or soil pipe.
2.8 Bed Pan Washer — A washer which is to be used for disposing human waste and sterilizing the Bed Pan for reuse. Bed pan washer requires water connection and electrical heating arrangement. This is to be considered as soil appliance.
2.9 Benching — Sloping surfaces constructed on either side of channels at the base of a manhole or inspection chamber for the purpose of confining the flow of sewage, avoiding the accumulation of deposits and providing a safe working platform.
2.91Systems of Drainage
a) Combined system — A system in which foul water (sewage) (black and grey water) and surface water are conveyed by the same sewers and drains.
b) Separate system — A system in which foul water (sewage) (black and grey water) and surface water are conveyed by the separate sewers and drains.
c) Partially separate system — A modification
of the separate system in which part of the surface water is conveyed by the foul (sanitary) sewers and drains.
2.92 Trade Effluent — Any liquid either with or without particles of matter in suspension which is wholly or in part produced in the course of any trade or industry, at trade premise. It includes farm wastes but does not include domestic sewage.
2.93 Trap — A fittings or device so designed and constructed as to provide, when properly vented, a
NATIONAL BUILDING CODE OF INDIA 2016
liquid seal which will prevent the back passage of air without materially affecting the flow of sewage or waste water through it.
2.94 Vertical Pipe — Any pipe or fitting which is installed in a vertical position or which makes an angle or not more than 45° with the vertical.
2.95 Vent Stack/Vent Pipe — A vertical vent-pipe installed primarily for the purpose of proving circulation of air to and from any part of the drainage system. It also protects trap seals from excessive pressure fluctuation.
2.96 Vent System — A pipe or pipes installed to provide a flow of air to or from a drainage system or to provide a circulation of air with in such system to protect traps seals from siphonage and back-pressure.
2.97 Waste Appliance — A sanitary appliance for the collection and discharge of water after use for ablutionary, culinary and other domestic purpose.
2.98 Waste Pipe — In plumbing, any pipe that receives the discharge of any fixtures, except water closets or similar fixtures and conveys the same to the house drain or soil or waste stack. When such pipe does not connect directly with a house drain or soil stack, it is called an indirect waste pipe.
2.99 Waste Water (Sullage) — The discharge from wash basins, sinks and similar appliances, which does not contain human or animal excreta.
2.100 Water Closet — A water flushed plumbing fixture designed to receive human excrement directly from the user of the fixture. The term is used sometimes to designate the room or compartment in which the fixture is placed.
2.101 Water Seal — The water in a trap, which acts as a barrier to the passage of air through the trap.
3GENERAL
3.1Basic Principles
The basic principles of water supply, drainage and sanitation are given below, and the design of drainage and sanitation should in general be guided by the applicable principles.
3.1.1 Potable Water
All premises intended for human habitation, occupancy, or use shall be provided with supply of potable water. This water supply shall not be connected with unsafe water resources, nor shall it be subject to the hazards of backflow.
3.1.2 Water Provision
Plumbing fixtures, devices and appurtenances shall be
provided with water in sufficient volume and at pressures adequate to enable them to function properly and without undue noise under normal conditions of use.
There should be at least a residual head of 0.018N / mm² at the consumer's tap. There may be certain fixtures or appliances in the installation that may require a higher pressure, such as 0.05N / mm² or even higher (such as 0.1N / mm² in case of flush valves), in which case the system shall be designed using pumps, tanks or both to achieve the required minimum pressure.
NOTE — The residual head shall be taken at the highest/farthest outlets in the building.
3.1.3 Water Efficiency
Plumbing system shall be designed, installed and adjusted to use the optimum quantity of water consistent with proper performance and cleaning.
3.1.4 Safety Devices
Plumbing system shall be designed and installed with safety devices to safeguard against dangers from contamination, explosion, overheating, etc.
3.1.5 Minimum Amenities
Each dwelling unit on premises (abutting on a sewer or with a private sewage disposal system) shall have at least one water closet, one kitchen wash place or a sink, and one bathing place or shower to meet the basic requirements of sanitation and personal hygiene.
In case of a group housing, the requirements relating to toilet or sanitary room and kitchen as given in 13 and B-9 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code shall also be complied with.
3.1.6 Drainage System
The drainage system shall be designed, installed and maintained to guard against fouling, deposit of solids and clogging and with adequate cleanouts so arranged that the pipes may be readily cleaned.
3.1.7 Materials and Workmanship
The plumbing system shall have durable material, free from defective workmanship and so designed and installed as to give satisfactory service for its reasonable expected life. The accessories of the plumbing system should be of such specifications as to meet the functional requirements of the installation, so as to also avoid any inconsistency leading to leakage and resultant seepage.
3.1.8 Fixture Traps and Vent Pipes
Each fixture directly connected to the drainage system shall be equipped with a liquid seal trap. Trap seals shall be maintained to prevent sewer gas, other
potentially dangerous or noxious fumes, or vermin from entering the building. Further, the drainage system shall be designed to provide an adequate circulation of air in all pipes with no danger of siphonage, aspiration, or forcing of trap seals under conditions of ordinary use by providing vent pipes throughout the system.
3.1.9 Foul Air Exhaust
Each vent terminal shall extend to the outer air and be so installed as to minimize the possibilities of clogging and the return of foul air to the building, as it conveys potentially noxious or explosive gases to the outside atmosphere. All vent pipes shall be provided with a cowl.
3.1.10 Testing
The plumbing system shall be subjected to required tests to effectively disclose all leaks and defects in the work or the material.
3.1.11 Exclusion from Plumbing System
No substance that will clog or accentuate clogging of pipes, produce explosive mixtures, destroy the pipes or their joints, or interfere unduly with the sewage-disposal process shall be allowed to enter the drainage system.
3.1.12 Light and Ventilation
Wherever water closet or similar fixture is located in a room or compartment, it should be properly lighted and ventilated.
3.1.13 Individual Sewage Disposal Systems
If water closets or other plumbing fixtures are installed in buildings where connection to public sewer is not possible, suitable provision shall be made for acceptable treatment and disposal.
3.1.14 Maintenance
Plumbing systems shall be maintained in a safe and serviceable condition.
3.1.15 Approach for Use and Cleaning
All plumbing fixtures shall be so installed with regard to spacing as to be approachable for their intended use and for cleaning. All doors, windows and any other device needing access within the toilet shall be so located that they have proper approach.
3.1.16 Accessibility for Persons with Disabilities
All doors, windows and fixtures, including WC, urinals, grab bars, wash basin, mirror and all other accessories for use by persons with disabilities shall be so installed/located that they have proper access with appropriate width, height, space, centerlines, and ease of operation
(see 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code).
3.1.17 Structural Safety
Plumbing system shall be installed with due regard to preservation of the structural members and prevention of damage to walls and other surfaces.
3.1.18 Protection of Ground and Surface Water
Sewage or other waste shall not be discharged into surface or sub-surface water without acceptable form of treatment.
3.2Drainage and Sanitation
3.2.1 Preparation and Submission of Plan
No person shall install or carry out any water-borne sanitary installation or drainage installation or any works in connection with anything existing or new buildings or any other premises without obtaining the prior sanction of the Authority.
The owner shall make an application in the prescribed form (see Annex A) to the Authority to carry out such a work.
3.2.2 Site Plan
A site plan of the premises on which the building is to be situated or any such work is to be carried out shall be prepared drawn to a scale not smaller than 1 in 500 (see Part 2 ‘Administration’ of the Code). The site plan of the building premises shall show,
a) the adjoining plots and streets with their names;
b) the position of the municipal sewer and the direction of flow in it;
c) the invert level of the municipal sewer, the road level, and the connection level of the proposed drain connecting the building in relation to the sewer,
d) the angle at which the drain from the building joints the sewer; and
e) the alignment, sizes and gradients of all drains and also of surface drains, if any.
A separate site plan is not necessary if the necessary particulars to be shown in such a site plan are already shown in the drainage plan.
3.2.3 Drainage Plan
The application (see 3.3.1) shall be accompanied by a drainage plan drawn to a scale of not smaller than 1 in 100 and furnished along with the building plan (see Part 2 ‘Administration’ of the Code). The plans shall show the following:
14
a) Every floor of the building in which the pipes or drains are to be used;
b) The position, forms, level and arrangement of the various parts of such building, including the roof thereof;
c) All new drains as proposed with their sizes and gradients;
d) Invert levels of the proposed drains with corresponding ground levels;
e) The position of every manhole, gully, soil and waste pipe, vent pipe, rainwater pipe, water closet, urinal, latrine, bath, lavatory, sink, trap or other appliances in the premises proposed to be connected to any drain and the following colours are recommended for indicating sewers, waste water pipes, rainwater pipes an existing work:
Description of Work
Colour
Sewers
Red
Waste water pipes and rainwater pipes
Blue
Existing work
Black
f) The position of refuse chute, inlet hopper and collection chamber.
3.2.3.1 In the case of an alteration or addition to an existing building, this clause shall be deemed to be satisfied if the plans as furnished convey sufficient information for the proposals to be readily identified with previous sanctioned plans and provided the locations of tanks and other fittings are consistent with the structural safety of the building.
3.2.3.2 The plans for the building drainage shall in every case be accompanied by specifications for the various items of work involved. This information shall be supplied in the prescribed form given in Annex B.
3.2.4 In respect of open drains, cross-sectional details shall be prepared to a scale not smaller than 1 in 50 showing the ground and invert levels and any arrangement already existing or proposed for the inclusion of any or exclusion of all storm water from the sewers.
3.2.5 Completion Certificate
At the completion of the plumbing installation work, the licensed/registered plumber shall give a completion certificate in the prescribed form, which is given in Annex C.
3.3Licensing/Registration of Plumbers
3.3.1 Execution of Work
The work which is required to be carried out under the provisions of this section, shall be executed only by a licensed/registered plumber under the control of the Authority and shall be responsible to carry out all lawful directions given by the Authority. No individual shall engage in the business of plumbing unless so licensed/registered under the provisions of this Section.
3.3.1.1 No individual, firm, partnership or corporation shall engage in the business of installing, repairing or altering plumbing unless the plumbing work performed in the course of such business is under the direct supervision of a licensed/registered plumber from approved Authority.
3.3.2 Examination and Certification
The Authority shall establish standards and procedure for the qualification, examination and licensing/registration of plumbers and shall issue licences to such persons who meet the qualifications thereof and successfully pass the examination.
3.3.3 For guidelines for registration of plumbers including the minimum standards for qualifications for the grant of licences, reference may be made to good practice [9-2(2)] . The Authority may also utilize the services of the certified plumbers who are certified for the required skill level under the appropriate scheme of the Government.
4Drainage and Sanitation
4.1 Types of Sanitary Appliances
4.1.1 Soil Appliances
4.1.1.1 Water closet
It shall essentially consist of a closet consisting of a bowl to receive excretory matter, trap and a flushing apparatus. It is recommended to provide ablution tap adjacent to the water closet, preferably on right hand side wall. The various types/style of water closets may be:
a) Squatting Indian type water closet,
b) Washdown type water closet,
c) Siphonic washdown type water closet, and
d) Universal or Anglo-Indian water closet.
4.1.1.2 Bidet
Bidet is an ablution appliance for cleansing excretory organs with water for personnel hygiene. It may be pedestal type or wall hung with a shallow bowl. Hot and cold water supplied through a mixer is discharged from a spray installed over the rim of the appliance. The bidet outlet should essentially connect to soil pipe in a system.
4.1.1.3 Urinal
It is a soil appliance for urination and is connected to soil pipe after a suitable trap. Urinal should have adequate provision of flushing apparatus. The various types/style of urinal may be:
a) Bowl type urinal: flat back or angle back.
b) Slab (single) type urinal.
c) Stall (single) type urinal.
d) Squatting plate type urinal.
e) Syphon jet urinal with integral trap.
f) Water less (non-water) urinal
4.1.1.4 Slop sink
Slop sink is a large sink, generally of square shape. the appliance is used in hospitals and is installed in the dirty utility room, sluice room and similar locations for disposal of excreta and other foul waste and for washing bed pans and urine bottles/pans. It is provided with a flushing mechanism. It is also provided in Janitor's closet where it is used for cleaning the housekeeping mops, etc.
4.1.1.5 Bed pan sink
Bed pan sink, also known as bedpan washer and disinfector, is a part of medical equipment inventory which is used to clean manually or automatically, the hospital bedpans, urine bottles and other containers used for collecting body fluids. It is provided in dirty utility room, sluice room, similar locations for disposal of excreta and other foul waste and for washing bed pans, urine bottles/pans. It is a soil appliance and is connected to soil pipe after a suitable trap. In manual models, it has a flushing arrangement.
Provision for installing a bedpan washer and disinfector should be made in all intensive care units in hospitals.
4.1.2 Waste Appliances
4.1.2.1 Wash basin
It is of one-piece construction having a combined overflow and preferably should have soap holding recess or recesses that should properly drain into the bowl. Each basin shall have circular waste hole through which the liquid content of the basin shall drain.
4.1.2.2 Wash-trough
It is a linear trough for simultaneous use by number of persons.
4.1.2.3 Sink
It is used in kitchen and laboratory for the purpose of cleaning utensils/ apparatus and also serve the purpose of providing water for general usage. The sink may be made with or without overflow arrangement. The sink shall be of one-piece construction including combined over flow, where provided. The sink shall have a circular waste hole into which the interiors of the sink shall drain.
4.1.2.4 Bath tub
Bath tub may be of enameled steel, cast iron, gel-coated, glass fibre reinforced plastic or may be cast in-situ. It shall be stable, comfortable, easy to get in and out, water tight, with anti-skid base, and easy to install and maintain. The bath tub shall be fitted with overflow and waste pipe of nominal diameter of not less than 32 mm and 40 mm, respectively.
4.1.2.5 Drinking fountain
It is a bowl fitted with a push button tap and a water bubbler or a tap with a swan neck outlet fitting. It has a waste fitting, a trap and is connected to the waste pipe.
4.1.3 The requirements of various soil appliances and waste appliances shall be in accordance with accepted standards [9-2(3)].