5.1 Escalators are typically used for short range of movement between adjacent floors. They are usually situated in an obvious circulation path making it easy for pedestrians to board them. Escalators and moving walks should only be accessed from adjacent
8

FIG. 1 TYPICAL FLOWCHART ON PRELIMINARY DESIGN OF ESCALATORS/MOVING WALKS
| Sl No. | Step Width | Theoretical Capacity, in Persons/h | |||||
| Horizontal Moving Walk (0° Inclination) | Inclined Moving Walk (For 0.5 m/s Speed) | ||||||
| m | For 0.5 m/s Speed | For 0.65 m/s Speed | For 0.75 m/s Speed | For 6° Inclination | For 10° Inclination | For 12° Inclination | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| i) | 0.8 | 3 000 | 3 700 | 4 400 | 3 000 | 3 700 | 3 000 |
| ii) | 1.0 | 3 800 | 4 600 | 5 400 | 3 700 | 3 700 | — |
| iii) | 1.4 | 5 100 | 6 400 | 7 700 | 5 100 | — | — |
| Sl No. | Step Width m | Practical Capacity, in Persons/h | ||
| For 0.5 m/s Speed (3) | For 0.65 m/s Speed (4) | For 0.75 m/s Speed (5) | ||
| (1) | (2) | |||
| i) | 0.6 | 2 250 | 2 925 | 3 375 |
| ii) | 0.8 | 3 375 | 4 388 | 5 063 |
| iii) | 1.0 | 4 500 | 5 850 | 6 750 |
corridors/walkways, landing and lobby areas, where people do not obstruct other pedestrian circulation routes. Space should be available to accommodate queuing at the boarding point.
It is especially important that the boarding and alighting areas adjacent to an escalator or moving walk are not part of another circulation route, in order to provide a safe area for passengers to board and alight at landings. The area of this space is defined as a distance between the handrails plus 160 mm, multiplied by a depth of 2.0 m to 2.5 m, depending on the configuration of escalator or moving walk.
Figure 2 illustrates the above clause with option 1 being a 2.5 m landing depth and option 2 being 2.0 m landing depth. Where successive units are installed, each successive escalator or moving walk should have its own individual unrestricted area.
Escalators occupy more space than stairs in order to accommodate their inclination. There are few standard escalator arrangements as shown in Fig. 3. Type (a) and Type (b) provide efficient circulation by providing the shortest transition path and time from one escalator and the next. Type (b) requires larger structural opening than Type (a) and Type (c) and present users with a higher risk of falling into the void. Type (c) is typical of a store as it allows the store to lengthen the circulation route past goods for sale. This configuration also takes up free space.
Some moving walks are adopted to receive and lock on shopping/baggage trolleys. In these cases the unrestricted area at the landing should be increased to at least 5 m and number of flat/horizontal steps at the boarding and alighting points increased. The most significant effect is the increased footprint required for the equipment. Shopping/baggage trolleys are not permitted on escalator.
In order to encourage pedestrian confidence and to assist efficient and safe boarding/ alighting of escalators, the start and end of escalator should present a number of horizontal/flat steps. At least two flat steps are provided for escalators speeds up to 0.5 m/s; at least three flat steps for speeds above 0.5 m/s and up to 0.65 m/s for escalator having rise more than 6 m; and at least four flat steps for speeds above 0.65 m/s. In locations where it is anticipated that escalators may be used by persons with impaired mobility or heavy passenger traffic, additional flat steps should be considered.

Option 1

FIG. 2 UNRESTRICTED FREE SPACE
| Table 5 Practical Capacities for Moving Walks(Clause 4.4) | |||||||
| SI No. | Step Width | Practical Capacity, in Persons/h | |||||
| Horizontal Moving Walk (0° Inclination) | Inclined Moving Walk (For 0.5 m/s Speed) | ||||||
| m | For 0.5 m/s Speed | For 0.65 m/s Speed | For 0.75 m/s Speed | For 6° Inclination | For 10° Inclination | For 12° Inclination | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| i) | 0.8 | 2 880 | 3 648 | 4 320 | 2 880 | 2 800 | 2 800 |
| ii) | 1.0 | 3 600 | 4 560 | 5 350 | 3 600 | 3 600 | — |
| iii) | 1.4 | 5 040 | 6 350 | 7 560 | 5 040 | — | — |

FIG. 3 ESCALATOR CONFIGURATION
5.2 Ensuring Accessibility for All Users
5.2.1 The accessibility requirements given in Part 3 'Development Control Rules and General Building Requirements' of the Code shall be complied with.
5.2.2 The location of escalators and moving walks should be considered in relation to the position of adjacent fire protected lift shafts and lobbies, staircases and their associated areas of rescue assistance, as at the time of an emergency these become non-functional. A surface of the escalator and moving walks should contrast visually with the approach and there should be audible signals or pre-recorded messages that indicate the start and finish of the escalator to help visually impaired people.
For important reasons of safety, special warning notices and tactile warning indicators shall be provided at the top and bottom of escalators. Escalators shall not be considered as the accessible route. Persons with locomotor disability cannot use them. Hence a lift should also be installed as an alternative accessible route.
For moving walks, the maximum inclination should be up to 6° for use by people with disabilities. People with disability may find it difficult to use moving walks. Hence, alternative like an accessible battery cart, may be provided to them in appropriate cases. Moving walks shall be free of projecting objects and obstacles up to a height of 2 100 mm. A minimum level of illumination of 100 lux shall be provided on moving walks.