18.6.1.1 Transmission length
The considerations affecting the transmission length shall be as follows:
a) The transmission length depends on a number of variables, the most important being the strength of concrete at transfer, the size and
type of tendon, the surface deformations of the tendon. The transmission length of the tendon towards the top of a unit is usually greater than that at the bottom.
The following values may be used, provided the concrete is well-compacted and detailing is as per the relevant provisions of this Section, and its strength at transfer is not less than 35N/mm2 and the tendon is released gradually:
-
For plain and indented wire : 100ϕ
-
For crimped wires : 65φ
-
Strands : 30ϕ
c) The development of stress in the tendon may be assumed to vary linearly along the length of the member.
NOTES
1 ϕ is the diameter of the tendon.
2 The transmission length may vary depending on the site conditions and therefore should be determined from tests carried out under the most unfavourable conditions.
18.6.3 Detailing of Reinforcement (Untensioned) in Prestressed Concrete
18.6.3.1 The detailing of reinforcement in prestressed concrete shall generally conform to the requirements given in relevant clauses of Part 6 ‘Structural Design, Section 5 Concrete, Subsection 5A Plain and Reinforced Concrete’ of the Code. In addition, the requirements of 18.6.3.2 and 18.6.3.3 shall be satisfied.
18.6.3.2 Transverse reinforcement
a) The amount and spacing of transverse reinforcement shall be governed by shear and torsion considerations. It is, however, desirable to provide transverse reinforcement in the web when the web is thin and cables are located in the web.
b) In the case of all members subjected to dynamic loading, webs shall be provided with transverse reinforcement, not less than 0.3 percent of the sectional area of the web in plan. This percentage of reinforcement may be reduced to 0.2 percent in members where the depth of the web is not more than four times the thickness of the web. These values may be reduced to 0.2 and 0.15 percent, respectively when high strength reinforcement is used.
c) In case of members not subjected to dynamic loading, reinforcement shall be provided when the depth of the web is more than 4 times the thickness. Such reinforcement shall not be less than 0.1 percent of the sectional area of the web in plan. The reinforcement shall be spaced
PART 6 STRUCTURAL DESIGN — SECTION 5 CONCRETE: 5B PRESTRESSED CONCRETE
at a distance not greater than the clear depth of the web and the size of such reinforcement shall be as small as possible.
d) Reinforcement in the form of links or helix shall be provided perpendicular to the line of heavy compression or shock loading to resist the induced tensile stresses.
18.6.3.3 Longitudinal reinforcement
a) A minimum longitudinal reinforcement of 0.2 percent of the total concrete area shall be provided in all cases except in the case of pretensioned units of small sections. This reinforcement may be reduced to 0.15 percent in the case of high yield strength deformed reinforcement. The percentage of steel provided, both tensioned and untensioned taken together, should be sufficient so that when the concrete in the precompressed tensile zone cracks, the steel is in a position to take up the additional tensile stress transferred on to it by the cracking of the adjacent fibres of concrete and a sudden failure is avoided.
b) When the depth of the web exceeds 500 mm, longitudinal distribution reinforcement not less than 0.05 percent of the area of the web shall be provided on each face. The spacing of the individual bars of such reinforcement shall not exceed 200 mm.
c) All untensioned longitudinal reinforcement shall be restrained in the lateral direction.