A-1 The total imposed loads from different floor levels (including the roof) coming on the central column of a multi-storeyed building (with mixed occupancy) is shown in Fig. 21. Calculate the reduced imposed load for the design of column members at different floor levels
using 3.3.2.1. Floor loads do not exceed .
A-1.1 Applying reduction coefficients in accordance with 3.3.2.1, total reduced floor loads on the column at different levels is indicated along with Fig. 21.
| FLOOR NO.FROM TOPINCLUDINGROOF | IMPOSEDFLOOR LOADSON COLUMNSAT DIFFERENTFLOORS, kN | DISCOUNTED IMPOSED LOADING ON COLUMNS, kN | |
| 1 | 30 | ROOF | |
| 2 | 40 | 30 | |
| 3 | 50 | (30 + 40) (1 - 0.1) = 63 | |
| 4 | 50 | (30 + 40 + 50) (1 - 0.2) = 96 | |
| 5 | 40 | (30 + 40 + 50 + 50) (1 - 0.3) = 119 | |
| 6 | 45 | (30 + 40 + 50 + 50 + 40) (1 - 0.4) = 126 | |
| 7 | 50 | (30 + 40 + 50 + 50 + 40 + 45) (1 - 0.4) = 153 | |
| 8 | 50 | (30 + 40 + 50 + 50 + 40 + 45 + 50) (1 - 0.4) = 183 | |
| 9 | 40 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50) (1 - 0.4)= 213 | |
| 10 | 40 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40)(1 - 0.4) = 237 | |
| 11 | 40 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40 + 40)(1 - 0.4) = 261 | |
| 12 | 55 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40 + 40+ 40) (1 - 0.5) = 237.5 < 261adopt 261 for design | |
| 13 | 55 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40 + 40+ 40 + 55) (1 - 0.5) = 265 | |
| 14 | 70 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40 + 40+ 40 + 55 + 55) (1 - 0.5) = 292.5 | |
| 15 | 80 | (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40 + 40+ 40 + 55 + 55 + 70) (1 - 0.5) = 327.5 | |
| (30 + 40 + 50 + 50 + 40 + 45 + 50 + 50 + 40 + 40+ 40 + 55 + 55 + 70 + 80) (1 - 0.5) = 367.5 | |||