Where a floor or part of a floor of a building has been designed to sustain a uniformly distributed load exceeding and in assembly, business, mercantile, industrial or storage buildings, a permanent notice in the form shown below indicating the actual uniformly distributed and/or concentrated loadings for which the floor has been structurally designed shall be posted in a conspicuous place in a position adjacent to such floor or on such part of a floor.
| DESIGNED IMPOSED FLOOR LOADING |
|---|
| Distributed......kN/m2 |
| Concentrated......kN |
Label Indicating Designed Imposed Floor Loading
NOTES
1 The lettering of such notice shall be embossed or cast suitably on a tablet whose least dimension shall not be less than and located not less than above floor level with lettering of a minimum size of .
2 If a concentrated load or a bulk load has to occupy a definite position on the floor, the same could also be indicated in the table.